5 | Assembly
60
M0691622_en | Installation instructions TM 320-550
Combustion chamber temperature sensor (F):
r
Unscrew the connector box cover. Connect up the compensating line as follows:
- green wire to the terminal with the green dot
- white wire to the unmarked terminal
- shield not connected up.
5.5.20 Installing the air flap actuators
r
Check that the air flaps are at the left stop
Ä
All air flaps should be are closed
Ä
Where necessary, turn the air flaps to the left stop using pliers
L
r
Set the direction of rotation of the servo-motor (1) to left (L)
r
Press the unlock key (2) and turn the drive for the shaft to the air duct (3) to the left as
far as the stop
E
r
Fit the servo-motor for primary air (A) and secondary air (B)
r
Fit the servo-motor for tertiary air (C)
r
Fit the servo-motor for primary air (D) and secondary air (E) for the flue gas
recirculation (FGR)