35
7425MUM661
Model: CWB FC
- Use and Maintenance Manual
Rev02
10
TROUBLESHOOTING
Cause
Alarm signal or
symptom
Solution
Execution
1. The unit does not start
Contacts of the main differential switch
open.
Electronic controller off
Close the contacts
User
Unit's electrical panel cut-off switch
open.
Electronic controller off
Close the contacts
User
Local/O/REM switch in the O or REM
position
Electronic controller on
Move the switch to I
User
No consent from the water differential
switch
A03
Evaporator flow switch alarm
Check the functioning of the
pump, vent the piping
User
Compressor timer active
The compressor icon on
the display of the
electronic controller is
flashing
Wait 3 minutes
User
No consent from the service
thermostat
Plant water at
temperature (see
display A)
Apply a thermal load to the
machine or lower the set point
User
No consent from the anti-freeze
thermostat
AE1
Evaporator ice alarm
Reset a temperature of the
water (set point) compatible
with the calibration of the anti-
freeze thermostat (see table
in paragraph 6.2)
User
Service and anti-freeze probe
defective
A7B
Alr. Probe Tout evaporator
Check contacts and replace, if
necessary
Specialised
personnel
Entering water temperature probe
defective
A7A
Alr. Probe Tin evaporator
Check contacts and replace, if
necessary
Specialised
personnel
Intervention of the main differential
switch
Electronic controller off
Look for current dispersion
inside the machine
Specialised
personnel
2. The compressor doesn't start
Intervention of the thermal protection
inside the compressor 1 or 2
The contactor of the
compressor is on but
the compressor is
stopped
A32
Compressors 1 2 Internal
Protection
A33
Compressors 3 4 Internal
Protection
Wait for cooling: check that
the compressor is working
under normal conditions.
Check for insufficient
refrigerant in the circuit (see
point 8).
Specialised
personnel
Intervention of the thermal protection
inside the compressor 3 or 4
Содержание PURESTREAM CWB FC
Страница 1: ...WATER CHILLER Model CWB FC Free Cooling User and Maintenance Manual BY FRIULAIR CHILLERS PURESTREAM ...
Страница 2: ...Editions Record Code Revision Edition Notes 7425MUM661 02 09 2019 Original instructions ENGLISH ...
Страница 45: ...40 7425MUM661 Model CWB FC Use and Maintenance Manual Rev02 12 WATER DIAGRAMS LEGEND CWB FC ...