19
7425MUM661
Model: CWB FC
- Use and Maintenance Manual
Rev02
•
Use the
DOWN
key until the PAR-Parameters menu is reached, press
ENTER
;
•
Use the
DOWN
key until the rEG-Regulation menu is reached, press
ENTER
;
•
Press
ENTER
at SEt-Setpoint; the description, the code and the value of the
cooling temperature setpoint is displayed;
•
Press
ENTER
to change the value using
UP
/DOWN
key;
•
Press
ENTER
to confirm the value;
•
Press
ESC
several times
to return to main screen.
5.4 C
HANGING THE TYPE OF RESTART AFTER A POWER FAILURE
In the case of a power failure, the chiller can behave in three different ways when power is
restored:
•
Stay OFF;
•
Start;
•
Return to the same condition it was in when the power failed.
To select one of these options, proceed as follows:
•
Starting from the main screen press
ENTER
;
•
Use the
DOWN
key until the PAR-Parameters menu is reached, press
ENTER
;
•
From the PAR GEN-General menu press
ENTER
;
•
From the GEN StU-Setup menu press
ENTER
, the Y02 menu shows the current
restart mode which may be one of the following: