Page 8
General Data - Ceiling Concealed FCU (3 rows coil)
50/60Hz
Model
FCR
200E
300E
400E
500E
600E
800E
1000E
1200E
1400E
Air Flow
High
CMH
350
520
680
850
1030
1380
1710
2040
2400
CFM
206
306
400
500
606
812
1006
1200
1412
Medium
CMH
270
380
510
640
780
1030
1290
1540
1975
CFM
160
224
300
376
459
606
759
906
1160
Low
CMH
190
280
340
450
560
740
890
1040
1255
CFM
112
165
200
265
329
435
524
612
738
Total Cooling Capacity
High
W
2250
3180
4050
4920
5830
8115
9300
11800
13000
Medium
W
2025
2765
3480
4130
4895
6895
8185
10265
11700
Low
W
1665
2290
2875
3245
4255
5760
6325
7905
7560
Sensible Cooling Capacity
High
W
1450
2080
2920
3535
4320
5660
6695
7480
9360
Medium
W
1275
1750
2455
2900
3675
4695
5760
6280
7950
Low
W
960
1415
1960
2190
2980
3790
4285
4635
5710
External Static Pressure
High
Pa
60
Low
30
Filter
Type
Washable Type
Material
Nylon
Thickness
8mm
Fan
Type
Centrifugal forward curved blades
Quantity
1
2
2
2
2
3
4
4
4
Material
Galvanized Steel
Drive
Direct-drive
Motor
Type
Permanent split capacitor with thermal overload protection
Insulation Class
Class B
Power Supply
V / Ph / Hz
220~240/1/50~60
Quantity
1
1
1
1
1
2
2
2
2
Rated Power Input
at ESP: 60 Pa (H)
W
65
75
90
110
150
178
228
270
340
at ESP: 30 Pa (L)
W
42
55
65
82
105
148
171
212
253
Cooling Coil
Type
Seamless copper tubes mechanically bonded to aluminium hydrophilic fins and collars
Max. Working Pressure
MPa
2.0
Pipe Connection
DN20 (
3/4
") -
Female Threaded
Water Flow Rate
l/s
0.11
0.15
0.20
0.25
0.28
0.39
0.44
0.56
0.62
Water Pressure Drop
kPa
10
25
18
21
30
30
39
28
49
Net Weight
kg
13
17
17
18
20
27
31
34
39
Dimension
Length
mm
705
805
895
995
1105
1435
1635
1765
1765
Width
mm
470
470
470
470
470
470
470
490
490
Height
mm
240
240
240
240
240
240
240
250
300
Sound Pressure Level
at ESP: 60 Pa (H)
dB (A)
42
44
47
47
50
52
54
54
56
at ESP: 30 Pa (L)
dB (A)
39
41
43
44
46
47
49
51
52
Condensate Drain Size
DN20 (
3/4
") -
Male Threaded
Note:
1) Nominal cooling capacity is based on the following condition:
a) Water temperature: 7.0°C (inlet) / 12.0°C (outlet)
b) Air entering condition: 27.0°C DB / 19.5°C WB
2) Air volume is tested under entering air condition of 20.0°C DB and dry coil condition.
3) All the units airflow value stated is at high speed.
4) Sound pressure level is based on 11.5 dB(A) anechoic room background noise.
Engineering Specifications
mm(in)
mm(in)
5) The manufacturer reserves the rights to make changes to the above specification without prior notice.
Содержание FC550-1500A
Страница 6: ...Page 5 Cassette Type Fan Coil Unit FKM 300 A A Product Generation 300 FKM Cassette FCU Unit size ...
Страница 8: ...Page 7 FCR E FCRQ B FCR B FFM FC FKM ...
Страница 25: ...Page 23a Model FCR B Model FF FC Field supply ...
Страница 26: ...Page 24 Field supply Model FKM ...
Страница 37: ... 2016 FRIMEC International www frimec international com A member of FRIMEC International Group ...