Page 27
Ceiling Expose FCU
a) Decide the open size of the ceiling according to the picture above.
b) The choice of the hanging base:
H
anging base should be the wooden frame and armoured concrete frame that are firm, dependable and
can bear 200kg or more object. The hanging base should be bear a certain weight for a long term. Before
construction, please consult the constructor and the decorator to confirm whether can install or not.
c) The fixup of the bolt.
Use the following method to fix the bolts or use hob and wooden frame to hang the bolt:
a: ceiling b: girder c: beam d: attic e: hanging bolt M10(3/8”)
f: reinforcing steel bar g: hook that can bear 120kg or more
reixfocing steel bar
hanging
bolt
hook
Connection the pipe
Connect condensate water pipe with the water inlet and water outlet pipe of the Coil with 3/4 inch outer worm nut,
the connector for water-in and water-out of the coil ia as following drawing.