Page 28
Connection the draining pipe
1) PVC pipe with 15mm inner diameter is needed and downward slanting angle should be above 2%.
2) Connect draining pipe with adhesive glue, and tie the PVC pipe.
3) Check every step of the connection.
1) heat insulation material
2) draining pipe support
3) mini slanting angle
4) drainage pipe
5) max distance of water
6) up and fold (not allowed)
7) sullage stimulation (not allowed)
8) air discharge port