background image

EXHAUST SYSTEM REQUIREMENTS

Use only 4 inch (10.16 cm) diameter (minimum) rigid or
flexible metal duct and approved vent hood which has a
swing-out damper(s) that opens when the dryer is in
operation. When the dryer stops, the damper(s)
automatically closes to prevent drafts and the entrance
of insects and rodents. To avoid restricting the outlet,
maintain a minimum of 12 inches (38.5 cm) clearance
between the vent hood and the ground or any other
obstruction.

    Do not allow combustible materials (for

example: clothing,draperies/curtains, paper) to come in contact
with the exhaust system. The dryer 

MUST NOT 

be exhausted

into a chimney, a wall, a ceiling, or any concealed space of a
building which can accumulate lint, resulting in a fire hazard.

    Do not exceed the length of duct pipe or

number of elbows allowed in the

” EXHAUST DUCT LENGTHS”

chart. Lint can accumulate in the system, plugging the system
and creating a fire hazard, as well as increasing drying times.

  Do not screen the exhaust ends of the vent

system, nor use any screws or rivets to assemble the exhaust
system. Lint can become caught in the screen, on the screws or
rivets, clogging the exhaust system and creating a fire hazard
as well as increasing drying times. Use an approved vent hood
to terminate the duct outdoors, and seal all joints with duct
tape. All male duct pipe fittings 

MUST 

be installed downstream

with the flow of air.

 

 Explosion hazard. 

Do not install the laundry

center where gasoline or other flammables are kept or stored.If
the laundry center is installed in a garage, it must be a minimum
of 18 inches (45.7 cm) above the floor. Failure to do so can
result in death, explosion, fire or burns.  The exhaust system
back pressure 

MUST 

not exceed 0.6 inches (1.52 cm) of water

column, measured with an inclined manometer at the point the
exhaust connects to the dryer.  The exhaust system should be
inspected and cleaned a  minimum of 

every 18 months

 with

normal usage. The more the dryer is used, the more often you
should check the exhaust system and vent hood for proper
operation.

The maximum length of the exhaust system depends upon the
type of duct used, number of elbows and type of exhaust hood.

The maximum length for both rigid and semi-rigid duct is shown
in the chart below.

MAXIMUM LENGTH OF 4-INCH (10.2 CM)

DIAMETER  SEMI-RIGID METAL DUCT

EXHAUST DUCT LENGTHS

Number

of 90°

Turns

MAXIMUM LENGTH OF 4-INCH (10.2 CM)

DIAMETER  RIGID METAL DUCT

EXHAUST HOOD TYPE

0
1
2
3

56 ft. (17.07 m)
46 ft. (14.02 m)
34 ft. (10.36 m)
32 ft. (9.75 m)

42 ft. (12.8 m)
36 ft. (10.97 m)
28 ft. (8.53 m)
18 ft. (5.48 m)

0
1
2
3

30 ft. (9.14 m)
22 ft. (6.7 m)
16 ft. (4.88 m)
10 ft. (3.05 m)

22 ft. (6.7 m)
14 ft. (4.27 m)
10 ft. (3.05 m)
5 ft. (1.5 m)

Louvered

4”

(10.2 CM)

2.5”

(6.35 CM)

4

CORRECT

CORRECT

INCORRECT

INCORRECT

 

The following are specific requirements for proper

and safe operation of your laundry center. Failure to follow
these instructions can create excessive drying times and fire
hazards.

 

Do not install a laundry center with flexible

plastic venting materials.  

If your present system is made up

of plastic duct or metal foil duct, 

replace it

 with a rigid or semi-

rigid metal duct.  In Canada and the United States if metal (foil
type) duct is installed, it must be of a specific type identified by
the appliance manufacturer as suitable for use with clothes dryers
and in the United States must also comply with the Outline for
Clothes Dryer Transition Duct, UL standard 2158A.   Flexible
venting materials  are known to collapse, be easily crushed and
trap lint.  These conditions will obstruct clothes dryer airflow and
increase the

 risk of fire.  

  

Ensure the present duct is free of

any lint prior to installing dryer duct.

 

- Risk of Fire

 - 

A clothes dryer must be

exhausted outdoors

.  Do not exhaust dryer into  a chimney, a

wall, a ceiling, an attic, a crawl space or any concealed space of
a building.  A clothes dryer produces combustible lint.  If the
dryer is not exhausted outdoors, some fine lint will be expelled
into the laundry area. An accumulation of lint in any area of the
home can create a health and fire hazard. 

The dryer must be

connected to an exhaust outdoors.

  Regularly inspect the

outdoor exhaust opening and remove any accumulation of lint
around the outdoor exhaust opening and in the surrounding area

.

Содержание 27

Страница 1: ...ric Dryer Use and Care Guide CENTRO DE LAVANDERÍA de 27 69 cm de ancho Lavadora Secadora eléctrica Manual de Uso y Cuidado Models Modelos P N 134897500A 0804 Made in USA Installation Instructions Instrucciones para la instalación Washer Dryer ...

Страница 2: ...h as restaurants or beauty salons etc For your safety the information in this manual must be followed to minimize the risk of fire or explosion or to prevent property damage personal injury or loss of life Do not store or use gasoline or other flammable vapors and liquid in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any el...

Страница 3: ...o the power supply cord is accessible when the laundry center is in an installed position WATER SUPPLY REQUIREMENTS Hot and cold water faucets MUST be installed within 42 inches 106 68 cm of your laundry center s water inlet The faucets MUST be 3 4 inch 1 9 cm garden hose type so inlet hoses can be connected Water pressure MUST be between 10 and 120 pounds per square inch maximum unbalance pressur...

Страница 4: ...and vent hood for proper operation The maximum length of the exhaust system depends upon the type of duct used number of elbows and type of exhaust hood The maximum length for both rigid and semi rigid duct is shown in the chart below MAXIMUM LENGTH OF 4 INCH 10 2 CM DIAMETER SEMI RIGID METAL DUCT EXHAUST DUCT LENGTHS Number of 90 Turns MAXIMUM LENGTH OF 4 INCH 10 2 CM DIAMETER RIGID METAL DUCT EX...

Страница 5: ...d metal duct work should be used Venting vertical through a roof may expose the exhaust system to down drafts causing an increase in vent restriction Running the exhaust system through an uninsulated area may cause condensation and faster accumulation of lint Compression or crimping of the exhaust system will cause an increase in vent restriction GAS SUPPLY REQUIREMENTS 1 Installation MUST conform...

Страница 6: ...16 IN 29 5 CM 1 7 8 IN 4 76 CM 3 IN 9 52 CM 9 3 8 IN 23 81 CM 41 IN 104 77 CM 29 7 16 IN 74 77 CM 27 IN 68 58CM DRAIN OUTLET REAR WATER INLETS REAR VENT 5 IN 13 33 CM GAS SUPPLY PIPE REAR 43 IN 109 22 CM 54 5 16 IN 137 95 CM 75 IN 191 77 CM 43 IN 109 22 CM ELECTRICAL CONNECTION 12 IN 31 75 CM ROUGH IN DIMENSIONS ...

Страница 7: ...clamps form a standpipe to prevent water syphoning DO NOT REMOVE THESE CLAMPS 6 Carefully move the laundry center to within 4 feet 1 22 m of the final location to begin the installation MOBILE HOME INSTALLATION 1 Dryer MUST be exhausted outside outdoors not beneath the mobile home using metal ducting that will not support combustion Metal ducting must be 4 inches 10 16 cm in diameter with no obstr...

Страница 8: ...d laundry center 1 The laundry center MUST be grounded In the event of malfunction or breakdown grounding will reduce the risk of electrical shock by a path of least resistance for electrical current 2 If your laundry center is equipped with a power supply cord having an equipment grounding conductor and a grounding plug the plug MUST be plugged into an appropriate copper wired receptacle that is ...

Страница 9: ...ANADIAN ELECTRIC Laundry Center NEUTRAL GROUND WIRE 1 Remove the screw securing the terminal block access cover to the rear panel and remove cover 2 Install a U L approved strain relief connector in the entry hole on the back panel 3 Remove the neutral ground wire from the green ground screw located above the termial block 4 Insert a NEMA 14 30 Type ST or SRDT U L approved power cord through the s...

Страница 10: ...he ground Gently set the laundry center back down to allow the rear legs to self adjust Place a level on top of the washer Check it side to side then front to back Screw the front leveling legs up or down to ensure the laundry center is resting solid on all four legs no rocking of the laundry center should exist NOTE Keep the leg extension at a minimum to prevent excessive vibration 7 GAS CONNECTI...

Страница 11: ...er make sure the dryer area is clear and free from combustible materials gasoline and other flammable vapors Also see that nothing such as boxes clothing etc obstructs the flow of combustion and ventilation air WARNING WARNING REPLACEMENT PARTS If replacement parts are needed for your laundry center contact the source where you purchased your laundry center Destroy the carton plastic bags and meta...

Страница 12: ...explosión o para evitar daños materiales lesiones personales o la muerte No almacene ni utilice gasolina u otros vapores y líquidos inflamables en la proximidad de éste o de cualquier otro artefacto eléctrico QUEDEBEHACERSIPERCIBEOLORAGAS No trate de encender ningún artefacto eléctrico Notoqueningúninterruptoreléctrico nouseningúnteléfonoensuedificio Haga salir a todos los ocupantes de la habitaci...

Страница 13: ...ipo NEMA 10 30 SRDT calificado para CA mínima de 240 voltios 30 A con 3 conectores de terminal horquilla con extremos doblados hacia arriba o de bucle cerrado y calificados para uso en secadoras de ropa Vea CONEXIONES ELÉCTRICAS PARA UN SISTEMA TRIFILAR Tetrafilar la secadora DEBE emplear un cable de alimentación eléctrica de 4 conductores tipo NEMA 14 30 SRDT o ST según se especifique calificado ...

Страница 14: ...LIDA Preferido Número de Codos a 90 LARGO MÁXIMO del Conducto Metálico Rigido de 4 10 2 cm de Diámetro 4 10 2 cm Apersianada LARGO MÁXIMO del Conducto Metálico Flexible de 4 10 2 cm de Diámetro 6 35 cm 2 0 30 pies 9 14 m 22 pies 5 49 m 1 22 pies 6 71 m 14 pies 4 27 m 2 16 pie 4 88 m 10 pies 3 05 m 3 NO RECOMENDADO INCORRECT INCORRECT REQUERIMIENTOS DEL SISTEMA DE ESCAPE Utilice solamente ductos me...

Страница 15: ...gido 8 pilgadas 20 32 cm de longitud y 4 pulgadas 10 16 cm de diàmetro 1 ducto acodado hacia abajo y un ducto acodado hacia la derecha 4 Hacia la derecha ducto rigido 8 pulgadas 20 32 cm de longitud y 4 pulgadas 10 16 cm de diàmetro 1 ducto acodado hacia abajo y un ducto acodado hacia la derecha Aungue un sistema vertical sea aceptable algunas circunstancias atenuantes pueden afectar el funcionami...

Страница 16: ... 11 7 16 IN 29 5 CM 41 IN 104 77 CM 29 7 16 IN 74 77 CM 27 IN 68 58CM DRAIN OUTLET REAR WATER INLETS REAR VENT 1 7 8 IN 4 76 CM 5 IN 13 33 CM GAS SUPPLY PIPE REAR 43 IN 109 22 CM 54 5 16 IN 137 95 CM 75 IN 191 77 CM 43 IN 109 22 CM ELECTRICAL CONNECTION 12 IN 31 75 CM LINA DE ALIMENTATION DE GAS ATRAS CONEXIÓN ES ELÉCTRICA S ENTRADAS DE AGUA ATRAS SALIDA AL DRENAJE ATRAS ...

Страница 17: ...AM SHIPPING PAD DRAIN HOSE POWER CORD IF EQUIPPED SHIPPING CARTON CORNER POSTS Bloque espaciador de plàstico Perno de embarque Espuma protectora de embareque Manguera de desagüe Bloque de embarque Cordon eléctrico si viene el equipo INSTALACIÓN EN CASAS MÓVILES 1 El tubo de escape de la secadora DEBE ser instalado hacia el exterior El escape debe colocarse en la parte exterior y no debajo de la ca...

Страница 18: ...equipadaconuncordóneléctricoqueposee un conductor de puesta a tierra del equipo y un enchufe de puesta a tierra dicho enchufe DEBE ser conectado a un tomacorriente adecuado debidamente instalado y puesto a tierra de acuerdo con todos los códigos y reglamentos locales Sitienealgunadudaconsulteaunelectricistaprofesional No modifique el enchufe proporcionado la aplicación Para una lavanderia conectad...

Страница 19: ...alicates Conecte con cuidado el tubo superior de entrada a la llave de agua FRIA apriete a mano y luege apriete 2 3 vuelta con unos alicates NO ESTROPEE LAS ROSCAS NI APRIETE ESTAS CONEXIONES EXCESIVAMENTE Abra la llave del agua y compuebe que no haya fugas en ninguna de lasdos conexiones 5 Con cuidado mueve el centro de lavanderia hasta su ubicación definitiva para instalación final 6 Para verifi...

Страница 20: ...emásasegúresedequenohayanada talcomocajas ropas etc queobstruyaelflujodelairedecombustiónyventilación 13 Vuelva a instalar el panel de acceso delantero de la seadora 14 Haga funcionar la secadora durante un ciclo completo para comprobarsubuenfuncionamiento NOTA En las secadoras a gas antes de encender el quemador esnecesariopurgarelairedelatuberíadelgas Sielquemador no enciende dentro de 45 segund...

Отзывы: