Figure 48
FRR011
Installation Instructions for WSE Sleeve
(WSE Sleeve Accessory Sold Separately)
Wall Preparation
STEP 1.
The wall opening required for a WSE SLEEVE is 17 ¼″ high by
27 ¼″ wide.
STEP 2.
LINTELS must be used in opening of brick veneer and masonry
walls to support the material above the WSE SLEEVE. The
following considerations should also be given:
A.
Masonry walls to support the material above the WSE SLEEVE.
B.
Adjustable SUBBASE (SB) or other unit support must be
provided for panel wall type construction and for walls less
than 8″ thick.
WARNING
Falling Object Hazard
Not following Installation Instructions
for mounting your air conditioner can
result in property damage, injury, or
death.
Mounting Hardware
ITEM
NO
DESCRIPTION
QTY.
1
SCREW, #12A x 2″
7
24″ MINIMUM REQUIRED FROM
TOP OF UNIT TO CEILING
INSIDE
WALL
LINTELS
1″ MINIMUM SPACING REQUIRED
ON ALL SIDES OF UNIT
7
/
8
″ MINIMUM BEYOND
INSIDE WALL
1″ MINIMUM
3
1
/
2
″ FOR SUBBASE
5
1
/
2
″ MAXIMUM FOR SUBBASE
OUTSIDE WALL
WSE SLEEVE
WALL MOUNT
SCREW LOCATIONS
DRAIN EXTENSION
5″ (127 mm)
5″ (127 mm)
9
/
16
″ MINIMUM BEYOND
OUTSIDE WALL
SIDE VIEW