COMPONENTS TESTING
Fan Motor
A single phase permanent split capacitor motor is used to drive the evaporator blower and condenser fan. A self-
resetting overload is located inside the motor to protect against high temperature and high amperage conditions.
WARNING
ELECTRIC SHOCK HAZARD
Turn off electric power before service or
installation. Extreme care must be used, if it
becomes necessary to work on equipment with
power applied.
Failure to do so could result in serious injury or
death.
Blower / Fan Motor Test
1. Visually inspect the motor’s wiring, housing etc., and determine that the capacitor is serviceable.
2. Make sure the motor has cooled down.
3. Disconnect the fan motor wires from the control board.
4. Test for continuity between the windings also, test to ground.
5. If any winding is open or grounded replace the motor.
6. Apply “live” test cord probes on black wire and common terminal of capacitor. Motor should run at high speed.
7. Apply “live” test cord probes on red wire and common terminal of capacitor. Motor should run at low speed.
8. Apply “live” test cord probes on each of the remaining wires from the speed switch or system switch to test intermediate
speeds.
Capacitors
WARNING
ELECTRIC SHOCK HAZARD
Turn off electric power before service or
installation. Extreme care must be used, if it
becomes necessary to work on equipment with
power applied.
Failure to do so could result in serious injury or
death.
Many motor capacitors are internally fused. Shorting the terminals will blow the fuse, ruining the capacitor. A 20,000 ohm 2
watt resistor can be used to discharge capacitors safely. Remove wires from capacitor and place resistor across terminals.
When checking a dual capacitor with a capacitor analyzer or ohmmeter, both sides must be tested.
Capacitor Check
The meter will show whether the capacitor is “open” or “shorted.” It will tell whether the capacitor is within its micro
farads rating and it will show whether the capacitor is operating at the proper power-factor percentage. The instrument will
automatically discharge the capacitor when the test switch is released.
Capacitor Connections
The starting winding of a motor can be damaged by a shorted and grounded running capacitor. This damage usually can be
avoided by proper connection of the running capacitor terminals.
From the supply line on a typical 230 volt circuit, a 115 volt potential exists from the “R” terminal to ground through a possible
short in the capacitor. However, from the “S” or start terminal, a much higher potential, possibly as high as 400 volts, exists
because of the counter EMF generated in the start winding. Therefore, the possibility of capacitor failure is much greater when
the identified terminal is connected to the “S” or start terminal. The identified terminal should always be connected to the
supply line, or “R” terminal, never to the “S”
terminal.
When connected properly, a shorted or grounded running capacitor will result in a direct short to ground from the “R”
terminal and will blow the line fuse. The motor protector will protect the main winding from excessive temperature.
Dual Rated Run Capacitor Hook-up
Figure 706 (Blower/ Fan Motor)
Figure 707 Dual Rated Capacitor Hook-Up
Содержание VERT-I-PAK VHA-18K75RTP
Страница 59: ...59 TROUBLESHOOTING ElectricalTroubleshooting Chart Cooling 9KBtu 12KBtu 18KBtu FIGURE 716 TROUBLESHOOTING...
Страница 62: ...62 TROUBLESHOOTING TroubleshootingChart Cooling FIGURE 719 TROUBLESHOOTING...
Страница 76: ...76 PARTS CATALOG 9K 12KRefrigerationAssy 6 9 5 3 14 1 2 11 7 8 10 4 12 13 Figure 902...
Страница 78: ...78 PARTS CATALOG 9K 12K208 230V 3 1 2 8 7 5 9 6 10 11 4 Figure 903...
Страница 80: ...80 PARTS CATALOG 9K 12K265V 9 10 3 12 13 14 18 11 1 7 6 2 4 19 15 16 17 8 Figure 904...
Страница 82: ...82 PARTS CATALOG 18KUnitAssembly 3 8 4 6 5 9 10 1 2 7 Figure 905...
Страница 86: ...86 PARTS CATALOG 18K 24K RefrigerationAssembly 15 14 12 11 8 7 6 3 4 5 16 1 2 19 18 18 9 10 13 17 20 Figure 907...
Страница 89: ...89 PARTS CATALOG 18KBlowerAssembly 8 1 2 3 7 5 10 9 4 6 Figure 908...
Страница 91: ...91 PARTS CATALOG 24KBlowerAssembly 9 7 2 3 4 1 8 Figure 909...
Страница 93: ...93 PARTS CATALOG 18K 230V ControlBox 1 4 5 3 7 8 2 6 9 Figure 910...
Страница 95: ...95 PARTS CATALOG 24K 230V ControlBox 12 1 9 11 3 5 2 10 6 13 8 7 4 Figure 911...
Страница 97: ...97 PARTS CATALOG 18K 265V ControlBox 14 15 17 16 18 19 20 21 22 1 3 9 2 4 11 5 6 7 8 10 12 13 Figure 912...
Страница 99: ...99 PARTS CATALOG 24K 265V ControlBox 17 18 19 21 22 23 25 1 11 5 8 13 7 9 10 12 14 15 6 4 3 16 2 20 Figure 913...