23
PB
OPERATION
Compressor Lock Out Time
The lockout feature ensures that the compressor is de-energized for a period of time. The timer varies randomly
from 180 to 240 seconds.
The compressor lockout is initiated every time the compressor is “off” due to:
(1)
Satisfying the T-stat temperature set point
(2)
Changing mode to fan only or heat
(3)
Turning the unit off
(4)
Power is restored after failure
(5)
Line power is restored from a brown out condition
Cooling Fan Delay
This is only for t-stat Fan Auto Mode only.
When unit cycles cooling ON – starts the fan 5 seconds EARLY. When unit cycles cooling OFF – DELAYS the fan off for 30
seconds
Heating Fan Delay
This is only for Fan Auto Mode (Fan cycles with cool/heat operation) and not for continuous fan mode. When unit cycles Heat-
ing ON – starts the fan 5 seconds EARLY. When unit cycles Heating OFF – DELAYS the fan off for 15 seconds.
Continuous fan operation enables fan to run continuously.
Fan Speed Change Delay
Relay activation is delayed by a minimum number of seconds. The default for this value is 2 seconds and is used to eliminate
relay chatter.
Room Air Sampling Feature
The room air sampling feature maintains a balanced temperature throughout the room by circulating the air for 90 seconds
once every 9 minutes that the unit is not running when it is set to cooling or heating mode. By circulating the air, the unit can
detect hot or cold areas in the room and operate the unit to cool or warm the room as neces-sary. This function is only avail-
able when the fan mode is set to ‘AUTO’ during COOL or HEAT Mode.
Low Voltage Interface Connections
All Vert-I-Pak units have a low voltage interface connector through
which a Remote Wall Thermostat, Desk Control and Auxiliary Fan’s
Relay can be connected. The interface connector is located on the electronic control board.
Interface Connector Definitions
FP
Factory use only.
(Ensure there is no jumper at FP an F2)
F2
Used with F1 to provide 24 VAC to external
fan relay. (Ensure there is no jumper at FP an F2
F1
Used with F2 to provide 24 VAC to external fan relay.
D2
Used with D1 for desk control on or off operation.
D1
Used with D2 for desk control on or off operation.
C
Common Ground TerminaL
GH
Call for high fan
GL
Call for low fan
B
Call for heat pump reversing valve
Y
Call for compressor
W
Call for heating
R
24V Power from Electronic Control to Wall
Figure 301 (Inteface Connections)
Figure 302 (Inteface Connections)
Содержание VERT-I-PAK VHA-18K75RTP
Страница 59: ...59 TROUBLESHOOTING ElectricalTroubleshooting Chart Cooling 9KBtu 12KBtu 18KBtu FIGURE 716 TROUBLESHOOTING...
Страница 62: ...62 TROUBLESHOOTING TroubleshootingChart Cooling FIGURE 719 TROUBLESHOOTING...
Страница 76: ...76 PARTS CATALOG 9K 12KRefrigerationAssy 6 9 5 3 14 1 2 11 7 8 10 4 12 13 Figure 902...
Страница 78: ...78 PARTS CATALOG 9K 12K208 230V 3 1 2 8 7 5 9 6 10 11 4 Figure 903...
Страница 80: ...80 PARTS CATALOG 9K 12K265V 9 10 3 12 13 14 18 11 1 7 6 2 4 19 15 16 17 8 Figure 904...
Страница 82: ...82 PARTS CATALOG 18KUnitAssembly 3 8 4 6 5 9 10 1 2 7 Figure 905...
Страница 86: ...86 PARTS CATALOG 18K 24K RefrigerationAssembly 15 14 12 11 8 7 6 3 4 5 16 1 2 19 18 18 9 10 13 17 20 Figure 907...
Страница 89: ...89 PARTS CATALOG 18KBlowerAssembly 8 1 2 3 7 5 10 9 4 6 Figure 908...
Страница 91: ...91 PARTS CATALOG 24KBlowerAssembly 9 7 2 3 4 1 8 Figure 909...
Страница 93: ...93 PARTS CATALOG 18K 230V ControlBox 1 4 5 3 7 8 2 6 9 Figure 910...
Страница 95: ...95 PARTS CATALOG 24K 230V ControlBox 12 1 9 11 3 5 2 10 6 13 8 7 4 Figure 911...
Страница 97: ...97 PARTS CATALOG 18K 265V ControlBox 14 15 17 16 18 19 20 21 22 1 3 9 2 4 11 5 6 7 8 10 12 13 Figure 912...
Страница 99: ...99 PARTS CATALOG 24K 265V ControlBox 17 18 19 21 22 23 25 1 11 5 8 13 7 9 10 12 14 15 6 4 3 16 2 20 Figure 913...