background image

13

B. Thermostat Mounting and Wiring

The thermostat is a precision instrument and was carefully adjusted at the factory.  Handle it carefully.

  CAUTION:  Disconnect the power supply before beginning installation of the thermostat to prevent electrical shock

or equipment damage.  Do not short across the thermostat terminals.  This can burn out the thermostat anticipator.

All wiring for the thermostat circuit must comply with NEC, state and local codes.  Use No. 20 AWG color-coded,
insulated (35°C minimum) wire.  If the thermostat is located more than 100 ft. from the unit (as measured along the
control voltage wires), use No. 18 AWG color-coded wires to avoid excessive voltage drop.

1.

In replacement applications, check the existing thermostat wiring for cracked or frayed insulation.  Replace any
wiring in poor condition.  All wiring must comply with local codes and ordinances.

2.

Run wiring (if necessary) to the location.  Thread the wires through a hole in the packing material saved in Step 2.
Connect the wires to the terminals on the back of the thermostat.  (See Figure 11.)

3.

Push the excess wire back through the hole and plug any opening with packing material to prevent drafts that may
affect thermostat performance.

4.

Loosely secure the thermostat to the wall with screws through the two mounting holes in the middle of the thermo-
stat.

5.

Level the thermostat.  Tighten the two mounting  screws.

6.

Replace the thermostat cover.

C. W

C. W

C. W

C. W

C. Wire Thermostat Cable to Unit T

ire Thermostat Cable to Unit T

ire Thermostat Cable to Unit T

ire Thermostat Cable to Unit T

ire Thermostat Cable to Unit Terminal Strip

erminal Strip

erminal Strip

erminal Strip

erminal Strip

Attach thermostat wires to low-voltage terminal block on left side of control box in locations indicated in Figures 1, 2 & 3.

Figure 11

Thermostat

Wiring

G

R

Y

B

W2

E

C

Fan

Compressor

Auxiliary

Common

Heat

24V

Reversing

Emergency

Valve

Heat

G

R

Y

B

W2

E

X

3) THERMOST

3) THERMOST

3) THERMOST

3) THERMOST

3) THERMOSTA

A

A

A

AT MOUNTING AND WIRING

T MOUNTING AND WIRING

T MOUNTING AND WIRING

T MOUNTING AND WIRING

T MOUNTING AND WIRING

A. Thermostat Location

Locate the thermostat about 5 ft. above the floor in an area with good circulation at average indoor temperature.

Do not mount the thermostat where it may be affected by:

Drafts or dead-air spots behind doors and in corners.

Hot or cold air flow from ducts.

Radiant heat from sun or appliances.

Concealed pipes or chimneys.

Unheated (uncooled) areas behind thermostat, such as an outside wall.

Содержание Vert-I-Pak VEB18K05

Страница 1: ...840 170 38 Single Package Vertical Air Conditioning System B Series 18 000 24 000 30 000 36 000 42 000 49 000 60 000 Btuh INSTALLATION OPERATION MANUAL...

Страница 2: ...Fan Performance 10 C Indoor Air Conditioned Supply air System 11 Indoor Fan Performance 12 2 Electrical A Grounding 12 B Power Supply 12 3 Thermostat Mounting and Wiring 13 14 A Thermostat Location 13...

Страница 3: ...zes DO insulate ALL conditioned air duct system components DO NOT locate room thermostat near conditioned air diffusers DO locate thermostat on an interior wall DO check that condensate drain line dra...

Страница 4: ...wer W 5000 10000 5000 10000 10000 15000 10000 15000 Heating Current A 20 8 41 6 20 8 41 6 41 6 62 4 41 6 62 4 H E A T P U M P D A T A Heating Cap Btu h 17000 17000 22000 22000 30000 30000 34000 34000...

Страница 5: ...n Ckt Amps A 33 52 33 26 52 40 5 26 52 40 5 52 52 49 52 52 49 26 52 52 Power Connection Hard Wire Hard Wire Hard Wire Hard Wire Hard Wire Hard Wire P H Y S I C A L D A T A Unit Width in 38 00 38 00 38...

Страница 6: ...he unit Units are available in three return air configurations front free return with disposable filter front ducted return with 1 duct flange and left side ducted return with 1 duct flange See Figure...

Страница 7: ...oor Air System A Outdoor Air System A Outdoor Air System Asacompletelyself containedsystem theVert I Pakunitrequiresanadequatesupplyofoutdoorairtoexchangeheatfrom the outdoor air coil The outdoor air...

Страница 8: ...8 VPBWP4 8 14 Wall Plenum Figure 6 VPBWP3 8 14 Wall Plenum Figure 5 For Models VE VHB18 VE VHB24 For Models VE VHB18 VE VHB24 VE VHB30 VE VHB36...

Страница 9: ...9 VPBWP5 8 14 Wall Plenum Figure 7 VPBWP6 8 14 Wall Plenum Figure 8 For Models VE VHB42 VE VHB49 For Model VE VHB60...

Страница 10: ...AIR INTAKE OUTSIDE WALL FLOOR CEILING EXHAUST OUTDOOR AIR EXHAUST INTAKE OUTSIDE WALL FLOOR OUTDOOR AIR EXHAUST OUTDOOR AIR INTAKE CEILING EXHAUST BACK OF UNIT OUTSIDE WALL Model 0 1 0 2 0 3 0 4 0 5...

Страница 11: ...e front of the unit and the back side of the door The minimum net free open area required for the RA louver or grille is listed in Table 2 Return Air Options Front Free Front Free Front Free Front Fre...

Страница 12: ...ound connection is made before connecting line voltage Failure to do so can result in property damage personal injury and or death Unit Wiring with VPDB1 Distribution Block 1 If wire is applied at amb...

Страница 13: ...to prevent drafts that may affect thermostat performance 4 Loosely secure the thermostat to the wall with screws through the two mounting holes in the middle of the thermo stat 5 Level the thermostat...

Страница 14: ...provide a field supplied secondary drain pan Always refer to local and national codes Test Run Test run in Heating Cooling and Emergency Heat mode as follows a Set fan control to ON If fan runs retur...

Страница 15: ...to operate to satisfy the call for heating To minimize energy costs do not increase the HEAT mode temperature set point by more than 2 F at a time Depending on the design of your home and its ventila...

Страница 16: ...mp youwillappreciateitsconstant evenheatandlowerenergyconsumption Heat Mode Operation Duringtheheatmodeofoperation frostoricemaybuildupontheoutdoor aircoilafteroperatingforextendedperiodsduring partic...

Страница 17: ...doors are frequently opened and closed Laundryappliancesarebeingoperated A shower is running More than the usual number of people are present in the home More than the normal number of electric lights...

Страница 18: ...it be extremely careful when handling parts or reaching into the unit REPLACE AIR FILTER A dirty air filter reduces the efficiency of your Vert I Pak and allows lint and dirt to accumulate on the indo...

Страница 19: ...utdoor air exhaust paths must remain clear Check the OA exhaust frequently Keep it free of all debris snow or ice The OA intake should also be kept free of obstructions Blocking the OA exhaust or OA i...

Страница 20: ...NDITIONING CO FRIEDRICH AIR CONDITIONING CO FRIEDRICH AIR CONDITIONING CO FRIEDRICH AIR CONDITIONING CO Post Office Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 782...

Отзывы: