C. Indoor-Air (Conditioned Supply Air) System

The VEB/VHB series unit may be applied in either a free return air configuration or a ducted return air configuration.  The supply
air path is intended to be ducted.  The design and construction of the indoor-air system must provide adequate air distribution
to ensure comfort levels throughout the structure.

The combined pressure losses of the return and supply air paths must not exceed the external static capabilities of the system
at the design airflow (See Table 2).

If the unit is installed in a closet behind a door and the return air louver or grille is directly opposite the unit RA opening, 2-
in. clearance is required between the front of the unit and the back side of the louver or grille.  If the louver or grille is located
elsewhere on the door so it is not directly in front of the RA opening, a minimum of 7-in. clearance is required between the
front of the unit and the back side of the door.  The minimum "net free open area" required for the RA louver or grille is listed
in Table 2.

Return Air Options

Front Free

Front Free

Front Free

Front Free

Front Free

Return

Return

Return

Return

Return

Side Ducted

Return

Front Ducted

Return

Figure 10

NOTE:  Ducted return air configurations require field fabrication of a duct-mounted filter box.  Filters are not
supplied with units configured for ducted return.

Indoor Fan Performance

Table 2

Indoor Blower Air Flow, SCFM (ARI RATED as shown)

Model

ESP

0.1

0.2

0.3

0.4

0.5

VE/HB18

Indoor

850

750

640

550

450

250

VE/HB24

Indoor

980

890

800

720

650

300

VE/HB30

Indoor

1120

1070

1000

940

830

375

VE/HB36

Indoor

1220

1120

1050

990

860

400

VE/HB42

Indoor

1570

1510

1470

1400

1350

525

VE/HB49

Indoor

1670

1610

1570

1500

1450

525

VE/HB60

Indoor

1980

1920

1860

1800

1700

675

Note: 

Italic

 indicates performance outside the required operating window of +/- 10% of rated SCFM.  All values are wet

coil with filter installed.

RA Grille Minimum Net

Free Open Area (Sq. In.)

Содержание Vert-I-Pak VEB18K05

Страница 1: ...840 170 38 Single Package Vertical Air Conditioning System B Series 18 000 24 000 30 000 36 000 42 000 49 000 60 000 Btuh INSTALLATION OPERATION MANUAL...

Страница 2: ...Fan Performance 10 C Indoor Air Conditioned Supply air System 11 Indoor Fan Performance 12 2 Electrical A Grounding 12 B Power Supply 12 3 Thermostat Mounting and Wiring 13 14 A Thermostat Location 13...

Страница 3: ...zes DO insulate ALL conditioned air duct system components DO NOT locate room thermostat near conditioned air diffusers DO locate thermostat on an interior wall DO check that condensate drain line dra...

Страница 4: ...wer W 5000 10000 5000 10000 10000 15000 10000 15000 Heating Current A 20 8 41 6 20 8 41 6 41 6 62 4 41 6 62 4 H E A T P U M P D A T A Heating Cap Btu h 17000 17000 22000 22000 30000 30000 34000 34000...

Страница 5: ...n Ckt Amps A 33 52 33 26 52 40 5 26 52 40 5 52 52 49 52 52 49 26 52 52 Power Connection Hard Wire Hard Wire Hard Wire Hard Wire Hard Wire Hard Wire P H Y S I C A L D A T A Unit Width in 38 00 38 00 38...

Страница 6: ...he unit Units are available in three return air configurations front free return with disposable filter front ducted return with 1 duct flange and left side ducted return with 1 duct flange See Figure...

Страница 7: ...oor Air System A Outdoor Air System A Outdoor Air System Asacompletelyself containedsystem theVert I Pakunitrequiresanadequatesupplyofoutdoorairtoexchangeheatfrom the outdoor air coil The outdoor air...

Страница 8: ...8 VPBWP4 8 14 Wall Plenum Figure 6 VPBWP3 8 14 Wall Plenum Figure 5 For Models VE VHB18 VE VHB24 For Models VE VHB18 VE VHB24 VE VHB30 VE VHB36...

Страница 9: ...9 VPBWP5 8 14 Wall Plenum Figure 7 VPBWP6 8 14 Wall Plenum Figure 8 For Models VE VHB42 VE VHB49 For Model VE VHB60...

Страница 10: ...AIR INTAKE OUTSIDE WALL FLOOR CEILING EXHAUST OUTDOOR AIR EXHAUST INTAKE OUTSIDE WALL FLOOR OUTDOOR AIR EXHAUST OUTDOOR AIR INTAKE CEILING EXHAUST BACK OF UNIT OUTSIDE WALL Model 0 1 0 2 0 3 0 4 0 5...

Страница 11: ...e front of the unit and the back side of the door The minimum net free open area required for the RA louver or grille is listed in Table 2 Return Air Options Front Free Front Free Front Free Front Fre...

Страница 12: ...ound connection is made before connecting line voltage Failure to do so can result in property damage personal injury and or death Unit Wiring with VPDB1 Distribution Block 1 If wire is applied at amb...

Страница 13: ...to prevent drafts that may affect thermostat performance 4 Loosely secure the thermostat to the wall with screws through the two mounting holes in the middle of the thermo stat 5 Level the thermostat...

Страница 14: ...provide a field supplied secondary drain pan Always refer to local and national codes Test Run Test run in Heating Cooling and Emergency Heat mode as follows a Set fan control to ON If fan runs retur...

Страница 15: ...to operate to satisfy the call for heating To minimize energy costs do not increase the HEAT mode temperature set point by more than 2 F at a time Depending on the design of your home and its ventila...

Страница 16: ...mp youwillappreciateitsconstant evenheatandlowerenergyconsumption Heat Mode Operation Duringtheheatmodeofoperation frostoricemaybuildupontheoutdoor aircoilafteroperatingforextendedperiodsduring partic...

Страница 17: ...doors are frequently opened and closed Laundryappliancesarebeingoperated A shower is running More than the usual number of people are present in the home More than the normal number of electric lights...

Страница 18: ...it be extremely careful when handling parts or reaching into the unit REPLACE AIR FILTER A dirty air filter reduces the efficiency of your Vert I Pak and allows lint and dirt to accumulate on the indo...

Страница 19: ...utdoor air exhaust paths must remain clear Check the OA exhaust frequently Keep it free of all debris snow or ice The OA intake should also be kept free of obstructions Blocking the OA exhaust or OA i...

Страница 20: ...NDITIONING CO FRIEDRICH AIR CONDITIONING CO FRIEDRICH AIR CONDITIONING CO FRIEDRICH AIR CONDITIONING CO Post Office Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 782...

Отзывы: