PB
TROUBLESHOOTING
Maintenance Method for Normal Malfunction
Service Manual
Installation and Maintenance
29
9.3 Maintenance Method for Normal Malfunction
1. Air Conditioner Can't be Started Up
Possible Causes
Discriminating Method (Air conditioner Status)
Troubleshooting
No power supply, or poor
connection for power plug
After energization, operation indicator isn’t bright
and the buzzer can't give out sound
&RQ¿UPZKHWKHULWVGXHWRSRZHUIDLOXUH,I\HV
wait for power recovery. If not, check power
supply circuit and make sure the power plug is
connected well.
Poor connection for wiring
terminals
Under normal power supply circumstances,
operation indicator isn't bright after energization
Check the circuit according to circuit diagram
and connect wires correctly. Make sure all
ZLULQJWHUPLQDOVDUHFRQQHFWHG¿UPO\
Electric leakage for air conditionerAfter energization, room circuit breaker trips off at
once
1.Make sure the air conditioner is grounded
reliably.
2.Make sure wires of air conditioner is
connected correctly.
3.Check the wiring inside air conditioner. Check
whether the insulation layer of power cord is
damaged; if yes, place the power cord.
Model selection for air switch is
improper
After energization, air switch trips off
Select proper air switch
2.Poor Cooling for Air Conditioner
Possible Causes
Discriminating Method (Air conditioner Status)
Troubleshooting
Set temperature is improper
Observe the set temperature on remote controller
or Membrane
Adjust the set temperature.
Rotation speed is set too low
Small wind blow
Set the fan speed at high or medium.
Filter is blocked
&KHFNWKH¿OWHUWRVHHLWVEORFNHG
&OHDQWKH¿OWHU
Installation position for unit is
improper
Check whether the installation postion is proper
according to installation requirement for air
conditioner
Adjust the installation position.
Refrigerant is leaking
Discharged air temperature during cooling is
higher than normal discharged wind temperature;
Discharged air temperature during heating is
lower than normal discharged wind temperature;
Unit's pressure is much lower than regulated
range
Find out the leakage causes and deal with it.
Add refrigerant.
Malfunction of capillary
Discharged air temperature during cooling is
higher than normal discharged wind temperature;
Discharged air temperature during heating is
lower than normal discharged wind temperature;
Unit't pressure is much lower than regulated
range. If refrigerant isn’t leaking, part of capillary
is blocked
Replace the capillary.
Malfunction of fan motor
The fan motor can’t operate
Refer to point 4 of maintenance method for
details.
Malfunction of compressor
Compressor can't operate
Refer to point 5 of maintenance method for
details.
3.Poor Heating for Electric Heater
Possible Causes
Discriminating Method (Air conditioner Status)
Troubleshooting
Electric heating relay on main
board is damaged
(YHQKHDWLQJFRQGLWLRQLVVDWLV¿HGHOHFWULFKHDWHU
can’t be started up under heating mode
Replace the main board with the same model.
Connection needle stand between
main board and display board is
loose
(YHQKHDWLQJFRQGLWLRQLVVDWLV¿HGHOHFWULFKHDWHU
can’t be started up under heating mode
Insert the needle stand tightly.
Set temperature and ambient
temperature are almost the same
Poor heating effect
Increase the set temperature.
Содержание PDE07K Series
Страница 23: ...23 OPERATION DipSwitchFunction 3 4 4 Dip Switch Functions Settings Dip Switch 3 and 4 Disable No Function ...
Страница 39: ...39 UNIT DISASSEMBLY IndoorMotor Wheel HeatingElementAssembly FIGURE 401 Removal of Indoor Fan Wire Harness ...
Страница 41: ...41 UNIT DISASSEMBLY Indoor Motor Wheel Heating Element Assembly FIGURE 403 Removal of Indoor Fan Grommet ...
Страница 42: ...42 UNIT DISASSEMBLY Indoor Motor Wheel Heating Element Assembly Figure 404 Left side Bushing Bushing Housing ...
Страница 47: ...47 UNIT DISASSEMBLY Indoor Motor Wheel Heating Element Assembly Figure 409 Primary Secondary Limits ...
Страница 48: ...48 UNIT DISASSEMBLY OutdoorMotor Blade ShroudAssembly Figure 410 Remove Gussets and Fan Shroud ...
Страница 50: ...50 UNIT DISASSEMBLY ElectronicBoard ElectricalComponentReplacement Figure 412 Remove User Interface ...
Страница 51: ...51 UNIT DISASSEMBLY Electronic Board Electrical Component Replacement Figure 413 Remove User Interface ...
Страница 52: ...52 UNIT DISASSEMBLY Electronic Board Electrical Component Replacement FIGURE 414 Low Voltage Connections ...
Страница 53: ...53 UNIT DISASSEMBLY Electronic Board Electrical Component Replacement Figure 415 Power Cord and Housing ...
Страница 56: ...56 UNIT DISASSEMBLY Electronic Board Electrical Component Replacement Figure 418 Main Board Relay Board ...
Страница 58: ...58 UNIT DISASSEMBLY Electronic Board Electrical Component Replacement Figure 420 Transformer ...
Страница 59: ...59 UNIT DISASSEMBLY Electronic Board Electrical Component Replacement Figure 421 Transformer Removed ...
Страница 96: ...96 COMPONENTS TESTING TestingLineVoltage 208 230 265V AC FIGURE 709 LINE VOLTAGE ...