background image

Flare tool for R410A, clutch type

0 to 0.5 mm

(0 to 0.0197 in.)

3

4

CONNECTING THE  PIPING

 WARNING

Do not use the existing piping and flare nuts.

If the existing materials are used, the pressure inside the
refrigerant cycle will rise and cause breakage, injury, etc.
(Use the special R410A materials.)

 CAUTION

(1) Do not use mineral oil on flared part.

Prevent mineral oil from getting into the system as this
would reduce the lifetime of the units.

(2) Never use piping which has been used for previous

installations. Only use parts which are delivered with
the unit.

(3) While welding the pipes, be sure to blow dry nitrogen

gas through them.

4. HEAT INSULATION ON THE PIPE JOINTS

(INDOOR SIDE ONLY)

Put coupler heat insulator on the joints (indoor side only).

Indoor unit

No gap

Coupler heat
insulator
(large)

Coupler heat
insulator (small)

No gap

Coupler heat
insulation

Be sure to overlap
the insulation

Large pipe

Small pipe

- Continued on back -

1. FLARING PROCESSING

(1) Cut the connection pipe to the necessary length with a pipe cutter.
(2) Hold the pipe downward so that cuttings will not enter the pipe and

remove the burrs.

(3) Insert the flare nut (always use the flare nut attached to the indoor

and outdoor units respectively) onto the pipe and perform the flare
processing with a flare tool.
Use the special R410A flare tool, or the conventional flare tool.
When using the conventional flare tool, always use an allowance ad-
justment gauge and secure the A dimension shown in table.

Check if [L] is flared uniformly
and is not cracked or scratched.

Die

A

Pipe

Pipe outside diameter

L

2. BENDING PIPES

(1) When bending the pipe, be careful not to crush it.
(2) To prevent breaking of the pipe, avoid sharp bends. Bend the pipe

with a radius of curvature of 150 mm (6") or over.

(3) If the copper pipe is bend the pipe or pulled to often, it will become

stiff. Do not bend the pipes more than three times at one place.

Pipe outside

diameter

6.35 mm (1/4 in.)
9.52 mm (3/8 in.)
12.7 mm (1/2 in.)

15.88 mm (5/8 in.)

A

Indoor unit side

Optional parts

 CAUTION

Be sure to apply the pipe against the port on the indoor
unit correctly. If the centering is improper, the flare nut
cannot be tightened smoothly. If the flare nut is forced to
turn, the threads will be damaged.

(2) Install the outdoor unit wall cap (supplied with the optional installation

set or procured at the site) to the wall hole pipe.

(3) Connect the outdoor unit and indoor unit piping.
(4) After matching the center of the flare surface and tightening the nut

hand tight, tighten the nut to the specified tightening torque with a
torque wrench.

Flare nut tightening torque

Flare nut

6.35 mm (1/4 in.) dia.

9.52 mm (3/8 in.) dia.

12.7 mm (1/2 in.) dia.

15.88 mm (5/8 in.) dia.

Tightening torque

16 to 18 N·m (160 to 180 kgf·cm)

30 to 42 N·m (300 to 420 kgf·cm)

49 to 61 N·m (490 to 610 kgf·cm)

63 to 75 N·m (630 to 750 kgf·cm)

Tighten with two wrenches.

Wrench (fixed)

Flare nut

Connection pipe

Indoor unit
pipe

Torque wrench

To prevent gas leakage,
coat the flare surface with
alkylbenzene oil (HAB).
Do not use mineral oil.

 CAUTION

Be sure to connect the large pipe after connecting the small
pipe completely.

Do not remove the cap from the connection pipe before connecting
the pipe.

A. Solid wire

Str

ip 25 mm (15/16")

Insulation

Loop

B. Strand wire

Str

ip 10 mm (3/8")

Round
terminal

Wire

Screw with
special washer

Round terminal

Terminal
board

Wire

Screw with
special washer

Round
terminal

A. For solid core wiring

(1) Cut the wire end with a wire cutter or wire-cutting pliers, then strip

the insulation to about 25 mm (15/16") of expose the solid wire.

(2) Using a screwdriver, remove the terminal screw(s) on the terminal

board.

(3) Using pliers, bend the solid wire to form a loop suitable for the

terminal screw.

(4) Shape the loop wire properly, place it on the terminal board and

tighten securely with the terminal screw using a screwdriver.

B. For strand wiring

(1) Cut the wire end with a wire cutter or wire-cutting pliers, then strip

the insulation to about 10 mm (3/8") of expose the strand wiring.

(2) Using a screwdriver, remove the terminal screw(s) on the terminal

board.

(3) Using a round terminal fastener or pliers, securely clamp a round

terminal to each stripped wire end.

(4) Position the round terminal wire, and replace and tighten the ter-

minal screw using a screwdriver.

HOW TO  CONNECT WIRING

TO THE TERMINALS

3. CONNECTION PIPES

(1) Centering the pipe against port on the indoor unit, turn the flare nut

with your hand.
Be sure that the small pipe is completely installed before connecting
the large the pipe.

Содержание MS24Y3F

Страница 1: ...SONAL INJURY OR DEATH ONLY A QUALIFIED EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked H...

Страница 2: ...unit Floor console This air conditioner uses new refrigerant HFC R410A The basic installation work procedures are the same as conventional refrigerant models However pay careful attention to the foll...

Страница 3: ...installed on the top or right side When the directions are selected drill 80 mm 3 1 8 and 50 mm 2 or 150 mm 6 dia hole on the wall so that the hole is tilted downward to ward the outdoor for smooth w...

Страница 4: ...ened smoothly If the flare nut is forced to turn the threads will be damaged 2 Install the outdoor unit wall cap supplied with the optional installation set or procured at the site to the wall hole pi...

Страница 5: ...OPERATION lamp Red TIMER lamp Green SWING lamp Orange SWING lamp Orange Operation can be checked by lighting and flashing of the display section OPERATION and TIMER lamps Perform judgement in accordan...

Страница 6: ...the remote control unit normal 2 Does each lamp light normally 3 Do not air flow direction louvers operate normally 4 Is the drain normal 5 Is there any abnormal noise and vibration during operation D...

Страница 7: ...nges must be made to the settings if the unit is to be used as a wired type 3 Changing the settings for the electrical circuits Switch 4 SW4 on the printed circuit board inside the electric compo nent...

Страница 8: ...be operated at the same time using a single remote controller 1 Wiring method indoor unit to remote controller 3 AUTO RESTART When the air conditioner power was temporarily turned off by a power fail...

Отзывы: