Floor Console/Under Ceiling Dual Type

INSTALLATION INSTRUCTION
SHEET

(PART NO. 9359945031)

For authorized service personnel only.

STANDARD PARTS

The following installation parts are furnished. Use them as required.

INDOOR UNIT ACCESSORIES

Name and Shape

Cover plate (left)

Cover plate (right)

Tapping screw (ø4 

×

 10)

Installation template

Bracket (left)

Bracket (right)

Anchor bolt (M12)

Spring washer

Special nut

Wall bracket

Tapping screw (ø4 

×

 20)

Coupler heat insulator
(large)

Coupler heat insulator
(small)

Nylon fastener

Q’ty

1

1

2

1

1

1

4

4

4

2

6

1

1

1

Application

For positioning the indoor
unit
For under ceiling type

For suspending the indoor
unit from ceiling

For suspending the indoor
unit on the wall.

For fixing the wall bracket.

For indoor side pipe joint
(Large pipe)

For indoor side pipe joint
(Small pipe)

For fixing the drain hose

Name and Shape

Drain hose

Insulation (drain hose)

VT wire

Remote control unit

Battery (penlight)

Remote control unit holder

Tapping screw (ø3 

×

 12)

Q’ty

1

1

1

1

2

1

2

Application

Adhesive type 70 

×

 230

For fixing the drain hose
L 280 mm

Use for air conditioner
operation

For remote control unit

Use as remote control unit
holder

For remote control unit
holder installation

IMPORTANT!
Please Read Before Starting

This air conditioning system meets strict safety and operating standards.
As the installer or service person, it is an important part of your job to
install or service the system so it operates safely and efficiently.

For safe installation and trouble-free operation, you must:

Carefully read this instruction booklet before beginning.

Follow each installation or repair step exactly as shown.

Observe all local, state, and national electrical codes.

Pay close attention to all danger, warning, and caution notices given in
this manual.

This symbol refers to a hazard or unsafe practice which
can result in severe personal injury or death.

This symbol refers to a hazard or unsafe practice which
can result in personal injury and the potential for
product or property damage.

Hazel alerting symbols

Electrical

Safety / alert

If Necessary, Get Help

These instructions are all you need for most installation sites and mainte-
nance conditions. If you require help for a special problem, contact our
sales/service outlet or your certified dealer for additional instructions.

In Case of Improper Installation

The manufacturer shall in no way be responsible for improper installation
or maintenance service, including failure to follow the instructions in this
document.

SPECIAL PRECAUTIONS

When Wiring

ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR
DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD
ATTEMPT TO WIRE THIS  SYSTEM.

Do not supply power to the unit until all wiring and tubing are completed
or reconnected and checked.

Highly dangerous electrical voltages are used in this system. Carefully
refer to the wiring diagram and these instructions when wiring. Improper
connections and inadequate grounding can cause accidental injury or
death.

Ground the unit following local electrical codes.

Connect all wiring tightly. Loose wiring may cause overheating at con-
nection points and a possible fire hazard.

WARNING:

CAUTION:

When Transporting

Be careful when picking up and moving the indoor and outdoor units. Get
a partner to help, and bend your knees when lifting to reduce strain on
your back. Sharp edges or thin aluminum fins on the air conditioner can
cut your fingers.

When Installing...

...In a Ceiling or Wall

Make sure the ceiling/wall is strong enough to hold the unit’s weight. It
may be necessary to construct a strong wood or metal frame to provide
added support.

...In a Room

Properly insulate any tubing run inside a room to prevent “sweating” that
can cause dripping and water damage to walls and floors.

...In Moist or Uneven Locations

Use a raised concrete pad or concrete blocks to provide a solid, level
foundation for the outdoor unit. This prevents water damage and abnor-
mal vibration.

...In an Area with High Winds

Securely anchor the outdoor unit down with bolts and a metal frame.
Provide a suitable air baffle.

...In a Snowy Area (for Heat Pump-type Systems)

Install the outdoor unit on a raised platform that is higher than drifting
snow. Provide snow vents.

When Connecting Refrigerant Tubing

Keep all tubing runs as short as possible.

Use the flare method for connecting tubing.

Apply refrigerant lubricant to the matching surfaces of the flare and
union tubes before connecting them, then tighten the nut with a torque
wrench for a leak-free connection.

Check carefully for leaks before starting the test run.

NOTE:

Depending on the system type, liquid and gas lines may be either narrow
or wide. Therefore, to avoid confusion the refrigerant tubing for your
particular model is specified as either “small” or “large” rather than as
“liquid” or “gas”.

When Servicing

Turn the power OFF at the main circuit breaker panel before opening
the unit to check or repair electrical parts and wiring.

Keep your fingers and clothing away from any moving parts.

Clean up the site after you finish, remembering to check that no metal
scraps or bits of wiring have been left inside the unit being serviced.

After installation, explain correct operation to the customer, using the
operating manual.

OPTIONAL PARTS

The following options are available.

•••••

WIRED REMOTE CONTROLLER UNIT: UTB-UUB (P/N9075887004)

Содержание MS24Y3F

Страница 1: ...SONAL INJURY OR DEATH ONLY A QUALIFIED EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked H...

Страница 2: ...unit Floor console This air conditioner uses new refrigerant HFC R410A The basic installation work procedures are the same as conventional refrigerant models However pay careful attention to the foll...

Страница 3: ...installed on the top or right side When the directions are selected drill 80 mm 3 1 8 and 50 mm 2 or 150 mm 6 dia hole on the wall so that the hole is tilted downward to ward the outdoor for smooth w...

Страница 4: ...ened smoothly If the flare nut is forced to turn the threads will be damaged 2 Install the outdoor unit wall cap supplied with the optional installation set or procured at the site to the wall hole pi...

Страница 5: ...OPERATION lamp Red TIMER lamp Green SWING lamp Orange SWING lamp Orange Operation can be checked by lighting and flashing of the display section OPERATION and TIMER lamps Perform judgement in accordan...

Страница 6: ...the remote control unit normal 2 Does each lamp light normally 3 Do not air flow direction louvers operate normally 4 Is the drain normal 5 Is there any abnormal noise and vibration during operation D...

Страница 7: ...nges must be made to the settings if the unit is to be used as a wired type 3 Changing the settings for the electrical circuits Switch 4 SW4 on the printed circuit board inside the electric compo nent...

Страница 8: ...be operated at the same time using a single remote controller 1 Wiring method indoor unit to remote controller 3 AUTO RESTART When the air conditioner power was temporarily turned off by a power fail...

Отзывы: