14
Custom Energy Savings Settings
When o
ccupancy is detected during the “Night Occupancy Period” for longer than the “Night
Occupancy Threshold” selected here, the thermostat will instantaneously switch to occupied mode.
If occupancy is detected for a period of time shorter than the “Night Occupancy Threshold” selected
here, the thermostat will automatically revert to unoccupied mode and continue to observe energy
saving functions that were in effect before the room became occupied.
If occupancy is detected for a period of time longer than the “Night Occupancy Threshold” selected
here, the thermostat will disable the occupancy sensor and consider the room occupied until the end
of the “Night Occupancy” period.
This feature ensures that energy saving functions that may affect guest comfort will not come in
effect during the “Night Occupancy” period.
07 – FORCED 2ND STAGE HEATING
00-60 (30* factory setting) Select a number of minutes 1st stage heating will run before 2nd
stage heating is automatically initiated if the guest setpoint is not reached and the 2nd
stage heating is not initiated through differential settings.
This feature allows automatically turning on 2nd stage heating to avoid excessive
compressor use.
Set to 00
to disable the feature.