12 – TEMPERATURE SETBACK DELAY - HEAT

 00-120 

(20* factory setting) Select the time delay (in minutes) for which the room 

that is in the guest occupancy mode needs to be unoccupied before the temperature 

setback is initiated. 

 

This feature prevents initiating temperature setback prematurely while the guest is 

still in the room but in an area where occupancy cannot be detected by the occupancy 

sensor. 

 

Setting the “Temperature Setback Delay - Heat” to “00”, disables the setback in the heat 

mode. Set to “00” to disable EMS.

Custom Energy Savings Settings

13 – MINIMUM SETBACK TEMPERATURE

 

 52-72  (64°F* factory setting) Select the “Minimum Setback Temperature” in °F.

 

 

Setback temperature is calculated by measuring PTAC unit’s ability to attain “Recovery 

Temperature - Heat” within “Temperature Recovery Time”. 

 

 

If recovery is disabled (“Temperature Recovery Time” is set to “0”) or if setback 

temperatures have not yet been calculated, the “Minimum Setback Temperature” value 

will be used as the setback temperature for heating.

 

 

If calculated setback temperature for heating is lower than “Minimum Setback 

Temperature”, then the “Minimum Setback Temperature” will be used as setback 

temperature for heating.

 

 

This feature allows defining the minimum temperature in a room when room is 

unoccupied and the thermostat is in the setback mode. 

Содержание EMRT-1

Страница 1: ...Friedrich Wireless Thermostat with an Occupancy Sensor EMWRT 1 Instruction Manual 99211002_00...

Страница 2: ...THERMOSTAT SETTINGS SCREENS 11 01 FAN CONTROL MODE 11 02 1ST STAGE DIFFERENTIAL HEAT 11 03 2ND STAGE DIFFERENTIAL HEAT 12 04 1ST STAGE DIFFERENTIAL COOL 12 05 INCIDENTAL OCCUPANCY THRESHOLD 13 06 NIG...

Страница 3: ...22 Replacing Thermostat Batteries 22 Troubleshooting 23 Error Codes 23 Thermostat is not controlling the PTAC unit 23 APPENDIX 1 Energy Saving Presets 24 APPENDIX 2 Glossary 25 Technical Specificatio...

Страница 4: ...or C and control the fan speed Comprehensive configuration options ensure full compatibility with virtually any existing or emerging hospitality HVAC system with up to 2 heat and 1 cool stages Built...

Страница 5: ...er wireless control cards and the server Ensure that the contol card is not and cannot fall into the PTAC unit Condensation Pan Replace the PTAC front cover Plug in the PTAC unit power cord into an el...

Страница 6: ...ment settings configured on the thermostat will be ignored and the thermostat settings configured through the network will be applied Thermostat Configuration SETTING THE THERMOSTAT CLOCK Set the ther...

Страница 7: ...e to the next digit Press the F C button to advance to the next menu Entering the room number correctly is crucial for proper operation of networked thermostats Thermostat Configuration CONFIGURING TH...

Страница 8: ...l turn on the heating when air conditioning is requested and turn on the air conditioning when heating is requested Press the Fan button to advance to the next setting Press the F C button to advance...

Страница 9: ...to the Custom Energy Savings Settings section Press the Power button to save the Thermostat Configuration and start using the thermostat Indicates factory setting TESTING THE THERMOSTAT Following the...

Страница 10: ...he thermostat must be turned on to access the thermostat settings USING THE THERMOSTAT SETTINGS SCREENS Use the Up and Down buttons to change the setting Press the F C button to advance to the next se...

Страница 11: ...mand for heating or air conditioning Indicates factory setting Custom Energy Savings Settings 02 1ST STAGE DIFFERENTIAL HEAT 02 30 0 2 F 3 0 F 0 5 F factory setting Select the number of degrees the th...

Страница 12: ...nd 2nd stage heating initiation 04 1ST STAGE DIFFERENTIAL COOL 02 30 0 2 F 3 0 F 0 5 F factory setting Select the number of degrees the thermostat has to sense between the automatic changeover tempera...

Страница 13: ...bserve energy saving functions that were in effect before the room became occupied This setting allows ignoring incidental room visits If occupancy is detected for a period of time longer than the Inc...

Страница 14: ...ime longer than the Night Occupancy Threshold selected here the thermostat will disable the occupancy sensor and consider the room occupied until the end of the Night Occupancy period This feature ens...

Страница 15: ...f the Night Occupancy period This feature ensures that energy saving functions that may affect guest comfort will not come in effect during the Night Occupancy period if room was occupied for a period...

Страница 16: ...time ensure that a comfortable room temperature defined as Heat and Cool Recovery Temperature will be restored within the selected Temperature Recovery Time Setting the Temperature Recovery Time to 0...

Страница 17: ...NIMUM SETBACK TEMPERATURE 52 72 64 F factory setting Select the Minimum Setback Temperature in F Setback temperature is calculated by measuring PTAC unit s ability to attain Recovery Temperature Heat...

Страница 18: ...ory setting Select the Maximum Setback Temperature in F Setback temperature is calculated by measuring PTAC unit s ability to attain Recovery Temperature Cool within Temperature Recovery Time If recov...

Страница 19: ...ctory setting Select the room temperature in F that a PTAC unit will have to attain within the selected Temperature Recovery Time when there is a need for air conditioning 17 MINIMUM SETPOINT 64 84 65...

Страница 20: ...and the heat and cool changeover temperatures This value plus the 1st stage differential defined in steps 02 and 04 defines the value at which the thermostat would automatically change heating coolin...

Страница 21: ...be turned off it will not automatically restore the most recent guest settings 02 When room is unoccupied and the thermostat is in the setback mode or turned off it will NOT maintain the temperature...

Страница 22: ...onths to ensure continuous thermostat operation To replace thermostat batteries Unscrew the fixing screw and remove the thermostat cover Replace the two 2 C cell batteries not supplied Replace the the...

Страница 23: ...ss Control Card is properly wired to the PTAC unit specifically make sure that the RED and the BLACK wire are properly connected If the red light is blinking with one 1 flash The Wireless Control Card...

Страница 24: ...5 F 0 5 F 0 5 F 07 Forced 2nd Stage Heating 30 30 30 30 30 30 10 Recovery Time 0 15 20 25 30 0 16 Recovery Temperature Cool 71 F 72 F 73 F 74 F 75 F 76 F 11 Recovery Temperature Heat 70 F 69 F 68 F 6...

Страница 25: ...setback mode Temperature Setback Delay the length of time for which the room that is in the guest occupancy mode needs to be unoccupied before the temper ature setback is initiated Incidental Occupan...

Страница 26: ...NY MAY VOID THE USER S AUTHORITY TO OPERATE THE EQUIPMENT Technical Specifications Thermostat Wireless Control Card Case Dimensions Imperial 5 125 x 4 6875 x 1 25 3 875 x 2 125 x 0 75 Case Dimensions...