Problem

Possible Cause

Action

Room temperature 

uneven 

(Heating cycle)

Heat anticipator (resistor) shorted (on applicable 
models)

Disconnect power to unit. Remove resistor from t-
stat bulb block. Plus in unit & allow to operate. Feel 
resistor for heat. If not heat, replace resistor

Wide differential - partial loss of t-stat bulb charge

Replace t-stat & check

Incorrect wiring

Refer to appropriate wiring diagram. Resistor is 
energized during "ON" cycle of compressor or fan.

Problem

Possible Cause

Action

Unit will not defrost

Incorrect wiring

Refer to appropriate wiring diagram

Defrost control timer motor not advancing 
(applicable models)

Check for voltage at "TM" & "TM1" on timer. If no 
voltage, replace control

Defrost control out of calibration (applicable models)

If outside coil temperature is 25F or below, & 
preselected time limit has elapsed, replace defrost 
control

Defrost control contacts stuck

If contacts remain closed between terminals "2" 
& "3" of the defrost control after preselected time 
interval has passed, replace control

Defrost control bulb removed from or not making 
good coil contact

Reinstall & be assured that good bulb to coil contact 
is made

Problem

Possible Cause

Action

Does not heat 

adequately

Exhaust or fresh air door open

Check if operating properly. Instruct customer on 
proper use of control

Dirty fi lter

Clean as recommended in Owner's Manual

Unit undersized

Check heat rise across coil. If unit operates 
effi ciently, check if insulation can be added to attic 
or walls. If insulation is adequate, recommend 
additional unit or larger one

Outdoor t-stat open (applicable models)

T-stat should close at 38°F. Check continuity of 
control. If temperature is below 38°F, replace control

Heater hi-limit control cycling on & off

Check for adequate fan air across heater. Check 
control for open at 160°F & close at 150°F

Shorted supplementary heater

Ohmmeter check, approx. 32-35 ohms

Incorrect wiring

Check applicable wiring diagram

Heat / Cool Room Air Conditioners: Troubleshooting Tips

Содержание CP14-18-24 CP14N10

Страница 1: ...Service Parts Manual 2007 Compact Programmable Models CP14N10 CP18N30 CP24N30 CP 14 18 24 Svc Prts 07 3 07...

Страница 2: ...ion and repair and who is equipped with the proper tools and test instruments Installation or repairs made by unqualified persons can result in hazards subjecting the unqualified person making such re...

Страница 3: ...15 59 15 59 15 59 Fan Motor Speed rpm H M L 900 780 730 900 780 730 1000 900 800 Output of Fan Motor W 200 200 190 Fan Motor RLA A 3 1 45 1 35 Fan Motor Capacitor uF 15 MFD 7 MFD 7 MFD Permissible Exc...

Страница 4: ...4 Outer Component Identification Models CP14N10 CP18N30 CP24N30 Cabinet Air inlet louver Front grille Power cord Control panel cover Front intake grille Air filter behind front intake grille...

Страница 5: ...5 Installation Dimensions Models CP14N10 CP18N30 CP24N30 Top View Fence obstruction Over 2 Over 1 Over 1 Wall Or window Front View Side View Ceiling Over 1 Over 1 25 98 16 85 Less than 8 66 Over 2...

Страница 6: ...6 CP24N30 CP18N30 CP14N10 Wiring Diagrams...

Страница 7: ...OMPONENTS Thermostat Used to maintain the specified room side comfort level Capacitor Reduces line current and steadies the voltage supply while greatly improving the torque characteristics of the fan...

Страница 8: ...consuming if not in some cases entirelyimpossible Therefrigerationsystemusesfourbasic principles laws in its operation they are as follows 1 Heat always flows from a warmer body to a cooler body 2 Hea...

Страница 9: ...leaks found 8 Reduce the system to zero gauge pressure 9 Connect vacuum pump to high side and low side of system with deep vacuum hoses or copper tubing Do not use regular hoses 10 Evacuate system to...

Страница 10: ...pressor eventually causing a mechanical failure within the compressor This mechanical failure can manifest itself as valve failure bearing failure and or other mechanical failure The specific type of...

Страница 11: ...10 to 15 minutes check the gauge pressures Gauges connected to system with an undercharge will have low head pressures and substantially low suction pressures UNDERCHARGED REFRIGERANT SYSTEMS NOTE He...

Страница 12: ...considerably less than normal as the compressor is running in a deep vacuum no load Much of the area of the condenser will be relatively cool since most or all of the liquid refrigerant will be stored...

Страница 13: ...perative Broken loose or incorrect wiring Refer to applicable wiring diagram Open capacitor Test capacitor replace if inoperative Fan speed switch open Test switch replace if inoperative Inoperative f...

Страница 14: ...emp differential delta T across coil Touch test coil return bends for same temp Test for low running current Problem Possible Cause Action Compressor runs continually does not cycle off Excessive heat...

Страница 15: ...stat terminals to check if unit operates If unit operates replace t stat Loose or broken parts in t stat Check as above Incorrect wiring Refer to appropriate wiring diagram Problem Possible Cause Acti...

Страница 16: ...ntial too narrow Replace t stat Plenum gasket not sealing allowing discharge air to short cycle t stat Check gasket Reposition or replace as needed Restricted coil or dirty filter Clean advise custome...

Страница 17: ...ontacts remain closed between terminals 2 3 of the defrost control after preselected time interval has passed replace control Defrost control bulb removed from or not making good coil contact Reinstal...

Страница 18: ...h Problem Possible Cause Action Cooling adequate but heating insufficient Heating capillary tube partially restricted Check for partially starved outer coil Replace heating capillary tube Check valve...

Страница 19: ...19 Components Model CP14N10...

Страница 20: ...67700205 15 Washer 4 1 67700158 16 Screw ST4 2X22 4 67700153 17 Top Rail Assy 1 67700206 18 Screw ST4X10 4 67700152 19 Condenser Assy 1 67700207 20 Nut with Washer M10 1 67700157 21 Washer 10 1 67700...

Страница 21: ...10 120V 1 67700220 50 Transformer 41X26 5C 1 67700221 51 Capacitor clamp 1 67700114 52 Main PCB M2A91J 1 67700222 53 Electric box 1 67700136 54 Isolation Washer D 1 67700223 55 Wire Clamp 1 67700160 5...

Страница 22: ...7700150 15 Washer 4 1 67700158 16 Self threading Screw ST4 2x22 6 67700153 17 Top Rail 1 67700134 18 Self threading Screw with Gasket ST4X10 4 67700152 19 Condenser Assy 1 67700104 20 Nut with Washer...

Страница 23: ...200V 240V TUV 1 67700147 50 Power Transformer 41X26 5F 1 67700146 51 Capacitor Clamp 1 67700114 52 Electric box 1 67700136 53 Main PCB J25713J 1 67700142 54 Fixed Clamp 1 67700160 55 Power cord 1 677...

Страница 24: ...24 Components Model CP24N30...

Страница 25: ...er 4 1 67700158 16 Screw ST4 2X22 4 67700153 17 Top Rail Assy 1 67700206 18 Screw ST4X10 4 67700152 19 Condenser Assy 1 67700239 20 Nut with Washer M10 1 67700157 21 Washer 10 1 67700159 22 Fan Blade...

Страница 26: ...ransformer 41X26 5C 1 67700247 51 Capacitor clamp 1 67700114 52 Main PCB M2A91J 1 67700248 53 Electric box 1 67700136 54 Isolation Washer D 1 67700223 55 Wire Clamp 1 67700160 56 Power cord 1 67700249...

Страница 27: ...been removed 3 Products which have defects or damage which results from improper installation wiring electrical current characteristics or maintenance or caused by accident misuse or abuse fire flood...

Страница 28: ...Prts 07 3 07 Friedrich Air Conditioning Co Post Office Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 FAX 210 357 4480 www friedrich com Print...

Отзывы: