background image

10

NOTE:  

In order to access the sealed system it will be necessary to install Schrader type fi ttings to the process tubes 

on the discharge and suction of the compressor. Proper refrigerant recovery procedures need to be adhered to as 
outlined in EPA Regulations. THIS SHOULD ONLY BE ATTEMPTED BY QUALIFIED SERVICE PERSONNEL.

Refrigerant Charging

NOTE: 

BECAUSE THE RAC SYSTEM IS A SEALED SYSTEM, 

SERVICE PROCESS TUBES WILL HAVE TO BE INSTALLED. 
FIRST INSTALL A LINE TAP AND REMOVE REFRIGERANT 
FROM SYSTEM. MAKE NECESSARY SEALED SYSTEM 
REPAIRS AND VACUUM SYSTEM.  CRIMP PROCESS TUBE 

LINE AND SOLDER END SHUT.  DO NOT LEAVE A SERVICE 

VALVE IN THE SEALED SYSTEM.

Proper refrigerant charge is essential to proper unit operation. 

Operating a unit with an improper refrigerant charge will result in 
reduced performance (capacity) and/or effi ciency.  Accordingly, 

the use of proper charging methods during servicing will insure 
that the unit is functioning as designed and that its compressor 
will not be damaged.

Too much refrigerant (overcharge) in the system is just as bad (if 

not worse) than not enough refrigerant (undercharge). They both 
can be the source of certain compressor failures if they remain 
uncorrected for any period of time. Quite often, other problems 

(such as low air fl ow across evaporator, etc.) are misdiagnosed as 

refrigerant charge problems. The refrigerant circuit diagnosis chart 
will assist you in properly diagnosing these systems.

An overcharged unit will at times return liquid refrigerant (slugging) 

back to the suction side of the compressor eventually causing a 
mechanical failure within the compressor. This mechanical failure 

can  manifest  itself  as  valve  failure,  bearing  failure,  and/or  other 
mechanical failure. The specifi c type of failure will be infl uenced 

by the amount of liquid being returned, and the length of time the 
slugging continues.

Not enough refrigerant (Undercharge) on the other hand, will cause 
the temperature of the suction gas to increase to the point where it 
does not provide suffi cient cooling for the compressor motor. When 
this occurs, the motor winding temperature will increase causing 
the motor to overheat and possibly cycle open the compressor 
overload protector. Continued overheating of the motor windings 
and/or cycling of the overload will eventually lead to compressor 
motor or overload failure.

METHOD OF CHARGING

The acceptable method for charging the RAC system is the 

Weighed in Charge Method.  The weighed in charge method is 
applicable to all units. It is the preferred method to use, as it is the 
most accurate.

The weighed in method should always be used whenever a charge 

is removed from a unit such as for a leak repair, compressor 
replacement, or when there is no refrigerant charge left in the unit. 

To charge by this method, requires the following steps:

1.  Install a piercing valve to remove refrigerant from the 

sealed system.  (Piercing valve must be removed from 

the system before recharging.)

2.  Recover Refrigerant in accordance with EPA 

regulations.

3.  Install a process tube to sealed system.

4.  Make necessary repairs to system.

5.  Evacuate system to 250 - 300 microns or less.

6.  Weigh in refrigerant with the property quantity of R-22 

refrigerant.

7. 

Start unit, and verify performance.

8.  Crimp the process tube and solder the end shut.

Содержание CP14-18-24 CP14N10

Страница 1: ...Service Parts Manual 2007 Compact Programmable Models CP14N10 CP18N30 CP24N30 CP 14 18 24 Svc Prts 07 3 07...

Страница 2: ...ion and repair and who is equipped with the proper tools and test instruments Installation or repairs made by unqualified persons can result in hazards subjecting the unqualified person making such re...

Страница 3: ...15 59 15 59 15 59 Fan Motor Speed rpm H M L 900 780 730 900 780 730 1000 900 800 Output of Fan Motor W 200 200 190 Fan Motor RLA A 3 1 45 1 35 Fan Motor Capacitor uF 15 MFD 7 MFD 7 MFD Permissible Exc...

Страница 4: ...4 Outer Component Identification Models CP14N10 CP18N30 CP24N30 Cabinet Air inlet louver Front grille Power cord Control panel cover Front intake grille Air filter behind front intake grille...

Страница 5: ...5 Installation Dimensions Models CP14N10 CP18N30 CP24N30 Top View Fence obstruction Over 2 Over 1 Over 1 Wall Or window Front View Side View Ceiling Over 1 Over 1 25 98 16 85 Less than 8 66 Over 2...

Страница 6: ...6 CP24N30 CP18N30 CP14N10 Wiring Diagrams...

Страница 7: ...OMPONENTS Thermostat Used to maintain the specified room side comfort level Capacitor Reduces line current and steadies the voltage supply while greatly improving the torque characteristics of the fan...

Страница 8: ...consuming if not in some cases entirelyimpossible Therefrigerationsystemusesfourbasic principles laws in its operation they are as follows 1 Heat always flows from a warmer body to a cooler body 2 Hea...

Страница 9: ...leaks found 8 Reduce the system to zero gauge pressure 9 Connect vacuum pump to high side and low side of system with deep vacuum hoses or copper tubing Do not use regular hoses 10 Evacuate system to...

Страница 10: ...pressor eventually causing a mechanical failure within the compressor This mechanical failure can manifest itself as valve failure bearing failure and or other mechanical failure The specific type of...

Страница 11: ...10 to 15 minutes check the gauge pressures Gauges connected to system with an undercharge will have low head pressures and substantially low suction pressures UNDERCHARGED REFRIGERANT SYSTEMS NOTE He...

Страница 12: ...considerably less than normal as the compressor is running in a deep vacuum no load Much of the area of the condenser will be relatively cool since most or all of the liquid refrigerant will be stored...

Страница 13: ...perative Broken loose or incorrect wiring Refer to applicable wiring diagram Open capacitor Test capacitor replace if inoperative Fan speed switch open Test switch replace if inoperative Inoperative f...

Страница 14: ...emp differential delta T across coil Touch test coil return bends for same temp Test for low running current Problem Possible Cause Action Compressor runs continually does not cycle off Excessive heat...

Страница 15: ...stat terminals to check if unit operates If unit operates replace t stat Loose or broken parts in t stat Check as above Incorrect wiring Refer to appropriate wiring diagram Problem Possible Cause Acti...

Страница 16: ...ntial too narrow Replace t stat Plenum gasket not sealing allowing discharge air to short cycle t stat Check gasket Reposition or replace as needed Restricted coil or dirty filter Clean advise custome...

Страница 17: ...ontacts remain closed between terminals 2 3 of the defrost control after preselected time interval has passed replace control Defrost control bulb removed from or not making good coil contact Reinstal...

Страница 18: ...h Problem Possible Cause Action Cooling adequate but heating insufficient Heating capillary tube partially restricted Check for partially starved outer coil Replace heating capillary tube Check valve...

Страница 19: ...19 Components Model CP14N10...

Страница 20: ...67700205 15 Washer 4 1 67700158 16 Screw ST4 2X22 4 67700153 17 Top Rail Assy 1 67700206 18 Screw ST4X10 4 67700152 19 Condenser Assy 1 67700207 20 Nut with Washer M10 1 67700157 21 Washer 10 1 67700...

Страница 21: ...10 120V 1 67700220 50 Transformer 41X26 5C 1 67700221 51 Capacitor clamp 1 67700114 52 Main PCB M2A91J 1 67700222 53 Electric box 1 67700136 54 Isolation Washer D 1 67700223 55 Wire Clamp 1 67700160 5...

Страница 22: ...7700150 15 Washer 4 1 67700158 16 Self threading Screw ST4 2x22 6 67700153 17 Top Rail 1 67700134 18 Self threading Screw with Gasket ST4X10 4 67700152 19 Condenser Assy 1 67700104 20 Nut with Washer...

Страница 23: ...200V 240V TUV 1 67700147 50 Power Transformer 41X26 5F 1 67700146 51 Capacitor Clamp 1 67700114 52 Electric box 1 67700136 53 Main PCB J25713J 1 67700142 54 Fixed Clamp 1 67700160 55 Power cord 1 677...

Страница 24: ...24 Components Model CP24N30...

Страница 25: ...er 4 1 67700158 16 Screw ST4 2X22 4 67700153 17 Top Rail Assy 1 67700206 18 Screw ST4X10 4 67700152 19 Condenser Assy 1 67700239 20 Nut with Washer M10 1 67700157 21 Washer 10 1 67700159 22 Fan Blade...

Страница 26: ...ransformer 41X26 5C 1 67700247 51 Capacitor clamp 1 67700114 52 Main PCB M2A91J 1 67700248 53 Electric box 1 67700136 54 Isolation Washer D 1 67700223 55 Wire Clamp 1 67700160 56 Power cord 1 67700249...

Страница 27: ...been removed 3 Products which have defects or damage which results from improper installation wiring electrical current characteristics or maintenance or caused by accident misuse or abuse fire flood...

Страница 28: ...Prts 07 3 07 Friedrich Air Conditioning Co Post Office Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 FAX 210 357 4480 www friedrich com Print...

Отзывы: