RESTRICTED REFRIGERANT SYSTEM

 A quick check for either condition begins at the evaporator. With 
a partial restriction, there may be gurgling sounds at the metering 
device entrance to the evaporator. The evaporator in a partial 
restriction could be partially frosted or have an ice ball close to the 
entrance of the metering device. Frost may continue on the suction 
line back to the compressor.

Often a partial restriction of any type can be found by feel, as 
there is a temperature difference from one side of the restriction 
to the other.

With a complete restriction, there will be no sound at the metering 
device entrance. An amperage check of the compressor with a 
partial restriction may show normal current when compared to the 
unit specifi cation. With a complete restriction the current drawn may 
be considerably less than normal, as the compressor is running 
in a deep vacuum (no load). Much of the area of the condenser 
will be relatively cool since most or all of the liquid refrigerant will 
be stored there.

The following conditions are based primar ily on a system in the 
cooling mode.

Troubleshooting a restricted refrigerant system can be 
diffi cult. The following proce dures are the more common 
problems and solutions to these problems. There are two 
types of refrigerant restrictions: Partial restrictions and 
complete restrictions.

•  A partial restriction allows some of the refrigerant to circulate 

through the system.

•  With a complete restriction there is no circulation of refrigerant 

in the system.

•  Restricted refrigerant systems display the same symptoms as 

a “low-charge condition.”

•  When  the  unit  is  shut  off,  the  gauges  may  equal ize very 

slowly.

•  Gauges connected to a completely re stricted system will run 

in a deep vacuum.  When the unit is shut off, the gauges will 
not equalize at all.

Refrigerant Charging

Содержание CP14-18-24 CP14N10

Страница 1: ...Service Parts Manual 2007 Compact Programmable Models CP14N10 CP18N30 CP24N30 CP 14 18 24 Svc Prts 07 3 07...

Страница 2: ...ion and repair and who is equipped with the proper tools and test instruments Installation or repairs made by unqualified persons can result in hazards subjecting the unqualified person making such re...

Страница 3: ...15 59 15 59 15 59 Fan Motor Speed rpm H M L 900 780 730 900 780 730 1000 900 800 Output of Fan Motor W 200 200 190 Fan Motor RLA A 3 1 45 1 35 Fan Motor Capacitor uF 15 MFD 7 MFD 7 MFD Permissible Exc...

Страница 4: ...4 Outer Component Identification Models CP14N10 CP18N30 CP24N30 Cabinet Air inlet louver Front grille Power cord Control panel cover Front intake grille Air filter behind front intake grille...

Страница 5: ...5 Installation Dimensions Models CP14N10 CP18N30 CP24N30 Top View Fence obstruction Over 2 Over 1 Over 1 Wall Or window Front View Side View Ceiling Over 1 Over 1 25 98 16 85 Less than 8 66 Over 2...

Страница 6: ...6 CP24N30 CP18N30 CP14N10 Wiring Diagrams...

Страница 7: ...OMPONENTS Thermostat Used to maintain the specified room side comfort level Capacitor Reduces line current and steadies the voltage supply while greatly improving the torque characteristics of the fan...

Страница 8: ...consuming if not in some cases entirelyimpossible Therefrigerationsystemusesfourbasic principles laws in its operation they are as follows 1 Heat always flows from a warmer body to a cooler body 2 Hea...

Страница 9: ...leaks found 8 Reduce the system to zero gauge pressure 9 Connect vacuum pump to high side and low side of system with deep vacuum hoses or copper tubing Do not use regular hoses 10 Evacuate system to...

Страница 10: ...pressor eventually causing a mechanical failure within the compressor This mechanical failure can manifest itself as valve failure bearing failure and or other mechanical failure The specific type of...

Страница 11: ...10 to 15 minutes check the gauge pressures Gauges connected to system with an undercharge will have low head pressures and substantially low suction pressures UNDERCHARGED REFRIGERANT SYSTEMS NOTE He...

Страница 12: ...considerably less than normal as the compressor is running in a deep vacuum no load Much of the area of the condenser will be relatively cool since most or all of the liquid refrigerant will be stored...

Страница 13: ...perative Broken loose or incorrect wiring Refer to applicable wiring diagram Open capacitor Test capacitor replace if inoperative Fan speed switch open Test switch replace if inoperative Inoperative f...

Страница 14: ...emp differential delta T across coil Touch test coil return bends for same temp Test for low running current Problem Possible Cause Action Compressor runs continually does not cycle off Excessive heat...

Страница 15: ...stat terminals to check if unit operates If unit operates replace t stat Loose or broken parts in t stat Check as above Incorrect wiring Refer to appropriate wiring diagram Problem Possible Cause Acti...

Страница 16: ...ntial too narrow Replace t stat Plenum gasket not sealing allowing discharge air to short cycle t stat Check gasket Reposition or replace as needed Restricted coil or dirty filter Clean advise custome...

Страница 17: ...ontacts remain closed between terminals 2 3 of the defrost control after preselected time interval has passed replace control Defrost control bulb removed from or not making good coil contact Reinstal...

Страница 18: ...h Problem Possible Cause Action Cooling adequate but heating insufficient Heating capillary tube partially restricted Check for partially starved outer coil Replace heating capillary tube Check valve...

Страница 19: ...19 Components Model CP14N10...

Страница 20: ...67700205 15 Washer 4 1 67700158 16 Screw ST4 2X22 4 67700153 17 Top Rail Assy 1 67700206 18 Screw ST4X10 4 67700152 19 Condenser Assy 1 67700207 20 Nut with Washer M10 1 67700157 21 Washer 10 1 67700...

Страница 21: ...10 120V 1 67700220 50 Transformer 41X26 5C 1 67700221 51 Capacitor clamp 1 67700114 52 Main PCB M2A91J 1 67700222 53 Electric box 1 67700136 54 Isolation Washer D 1 67700223 55 Wire Clamp 1 67700160 5...

Страница 22: ...7700150 15 Washer 4 1 67700158 16 Self threading Screw ST4 2x22 6 67700153 17 Top Rail 1 67700134 18 Self threading Screw with Gasket ST4X10 4 67700152 19 Condenser Assy 1 67700104 20 Nut with Washer...

Страница 23: ...200V 240V TUV 1 67700147 50 Power Transformer 41X26 5F 1 67700146 51 Capacitor Clamp 1 67700114 52 Electric box 1 67700136 53 Main PCB J25713J 1 67700142 54 Fixed Clamp 1 67700160 55 Power cord 1 677...

Страница 24: ...24 Components Model CP24N30...

Страница 25: ...er 4 1 67700158 16 Screw ST4 2X22 4 67700153 17 Top Rail Assy 1 67700206 18 Screw ST4X10 4 67700152 19 Condenser Assy 1 67700239 20 Nut with Washer M10 1 67700157 21 Washer 10 1 67700159 22 Fan Blade...

Страница 26: ...ransformer 41X26 5C 1 67700247 51 Capacitor clamp 1 67700114 52 Main PCB M2A91J 1 67700248 53 Electric box 1 67700136 54 Isolation Washer D 1 67700223 55 Wire Clamp 1 67700160 56 Power cord 1 67700249...

Страница 27: ...been removed 3 Products which have defects or damage which results from improper installation wiring electrical current characteristics or maintenance or caused by accident misuse or abuse fire flood...

Страница 28: ...Prts 07 3 07 Friedrich Air Conditioning Co Post Office Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 FAX 210 357 4480 www friedrich com Print...

Отзывы: