Part 4 Trouble Shooting
5. Cycle Troubleshooting Guide
Problem
Possible causes
Corrective action
Error Code
Abnormal operat-
ing conditions.
• There is a burning smell
and a strange sound
coming from the unit.
• Turn off the air conditioner, unplug the power cord
and contact the service center.
• Water leaks from the
indoor unit even when
the humidity level is low.
• The power cord is dam-
aged or generating
excessive heat.
• A switch, a circuit breaker
(safety, ground) or a fuse is
not operated properly.
The air conditioner
does not work.
• The air conditioner is
unplugged.
• Check whether the power cord is plugged into the
outlet.
• A fuse is blown or the
power supply is blocked.
• Replace the fuse or check if the circuit breaker
has tripped.
27
• A power failure has
occurred.
• Turn off the air conditioner when a power failure
occurs.
• When the power is restored, wait 3 minutes, and
then turn on the air conditioner.
23
• The voltage is too high
or too low.
• Check if the circuit breaker has tripped.
23, 40
• The air conditioner
turned off automatically
at a preset time.
• Press the power button again.
10
• Battery setting is wrong
in the remote controller.
• Is the battery inserted in Remote controller? Is the
battery inserted with the correct terminal (+)(-)?
• Even if you check the upper lists, the air-conditioner
does not operate. Please replace new batteries.
The air conditioner
does not work.
• The type of the indoor
units is not compatible
with that of the outdoor
unit.
• Replace the outdoor unit to suitable one.
05, 53
• The outdoor air tempera-
ture is unsuitable for
operating the air condi-
tioner.
• Heating operation can be used when the outdoor
air temperature is under 18°C, and cooling opera-
tion can be used when the outdoor air tempera-
ture is over -10°C.
Содержание AS - W126BMS0
Страница 3: ...3 1 Safety Precautions 4 2 Nomenclature 7 Part 1 General Information...
Страница 16: ...16 Part 3 Test Run 1 Check before Test Run 17 2 Test Run Flow chart 18 3 Test Run Detail 19...
Страница 37: ...Part 4 Trouble Shooting 37 Troubleshooting Guide Indoor Unit...
Страница 41: ...Part 4 Trouble Shooting 41 verify with hands verify with hands...
Страница 44: ...Part 4 Trouble Shooting 44 Case of field defect IPM Over Current Limit Bending Folding SVC Valve close...
Страница 46: ...Part 4 Trouble Shooting 46 3 CH23 DC Link Low Voltage Error...
Страница 51: ...Part 4 Trouble Shooting 51 8 CH40 CT Sensor Error Open Short Tester Tester...
Страница 52: ...Part 4 Trouble Shooting 52 9 CH41 44 45 65 Inv D Pipe Outdoor Inlet Cond Pipe Heat sink Sensor Error...
Страница 53: ...Part 4 Trouble Shooting 53 10 CH53 Outdoor Unit Indoor Unit Communication Error...
Страница 56: ...Part 4 Trouble Shooting 56 13 CH62 Heat Sink Overheat Error...
Страница 57: ...Part 4 Trouble Shooting 57 14 CH67 Outdoor BLDC Fan Lock Error Case of field defect BLDC Fan Motor short...
Страница 59: ...Part 4 Trouble Shooting 59 Resistance between the lines of each 1 5 2 1 5 2 1 5 2 U V V W W U...
Страница 61: ...Part 4 Trouble Shooting 61 3 CH23 DC Link Low Voltage Error...
Страница 66: ...Part 4 Trouble Shooting 66 8 CH41 44 45 65 Inv D Pipe Outdoor Inlet Cond Pipe Heat sink Sensor Error...
Страница 67: ...Part 4 Trouble Shooting 67 9 CH53 Outdoor Unit Indoor Unit Communication Error...
Страница 68: ...Part 4 Trouble Shooting 68 10 CH60 Outdoor Unit PCB EEPROM Error...
Страница 71: ...Part 4 Trouble Shooting 71 13 CH67 Outdoor BLDC Fan Lock Error...
Страница 72: ...P No MFL41161608...