Part 4 Trouble Shooting
Lo
Charging
cylinder
Outdoor unit
Indoor unit
Liquid side
Gas side
Open
3-Way
valve
3-Way
valve
OPEN
Open
Check valve
(1)
CLOSE
Vacuum
Gage
• Procedure
(1) Connect the charge hose to the charging
cylinder.
– Connect the charge hose which you dis-con-
nected from the vacuum pump to the valve at
the bottom of the cylinder.
– If you are using a gas cylinder, also use a
scale and reverse the cylinder so that the sys-
tem can be charged with liquid.
(2) Purge the air from the charge hose.
– Open the valve at the bottom of the cylinder
and press the check valve on the charge set to
purge the air. (Be careful of the liquid refriger-
ant). The procedure is the same if using a gas
cylinder.
(3) Open the valve (Lo side on the charge set and
charge the system with liquid refrigerant.
– If the system can not be charged with the spec-
ified amount of refrigerant, it can be charged
with a little at a time (approximately 150g each
time) while operating the air conditioner in the
cooling cycle; however, one time is not suffi-
cient, wait approximately 1 minute and then
repeat the procedure (pumping down-pin).
(4) Immediately disconnect the charge hose from
the 3-way valve’s service port.
– Stopping partway will allow the gas to be dis-
charged.
– If the system has been charged with liquid
refrigerant while operating the air conditioner
turn off the air conditioner before disconnecting
the hose.
(5) Mount the valve stem nuts and the service
port nut.
– Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.
– Be sure to check for gas leakage.
This is different from previous procedures.
Because you are charging with liquid refrigerant
from the gas side, absolutely do not attempt to
charge with larger amounts of liquid refrigerant
while operating the air conditioner.
4. Gas Charging (After Evacuation)
Содержание AS - W126BMS0
Страница 3: ...3 1 Safety Precautions 4 2 Nomenclature 7 Part 1 General Information...
Страница 16: ...16 Part 3 Test Run 1 Check before Test Run 17 2 Test Run Flow chart 18 3 Test Run Detail 19...
Страница 37: ...Part 4 Trouble Shooting 37 Troubleshooting Guide Indoor Unit...
Страница 41: ...Part 4 Trouble Shooting 41 verify with hands verify with hands...
Страница 44: ...Part 4 Trouble Shooting 44 Case of field defect IPM Over Current Limit Bending Folding SVC Valve close...
Страница 46: ...Part 4 Trouble Shooting 46 3 CH23 DC Link Low Voltage Error...
Страница 51: ...Part 4 Trouble Shooting 51 8 CH40 CT Sensor Error Open Short Tester Tester...
Страница 52: ...Part 4 Trouble Shooting 52 9 CH41 44 45 65 Inv D Pipe Outdoor Inlet Cond Pipe Heat sink Sensor Error...
Страница 53: ...Part 4 Trouble Shooting 53 10 CH53 Outdoor Unit Indoor Unit Communication Error...
Страница 56: ...Part 4 Trouble Shooting 56 13 CH62 Heat Sink Overheat Error...
Страница 57: ...Part 4 Trouble Shooting 57 14 CH67 Outdoor BLDC Fan Lock Error Case of field defect BLDC Fan Motor short...
Страница 59: ...Part 4 Trouble Shooting 59 Resistance between the lines of each 1 5 2 1 5 2 1 5 2 U V V W W U...
Страница 61: ...Part 4 Trouble Shooting 61 3 CH23 DC Link Low Voltage Error...
Страница 66: ...Part 4 Trouble Shooting 66 8 CH41 44 45 65 Inv D Pipe Outdoor Inlet Cond Pipe Heat sink Sensor Error...
Страница 67: ...Part 4 Trouble Shooting 67 9 CH53 Outdoor Unit Indoor Unit Communication Error...
Страница 68: ...Part 4 Trouble Shooting 68 10 CH60 Outdoor Unit PCB EEPROM Error...
Страница 71: ...Part 4 Trouble Shooting 71 13 CH67 Outdoor BLDC Fan Lock Error...
Страница 72: ...P No MFL41161608...