Part 3 Test Run
Check to see whether there is any refrigerant leakage, and check whether the power or transmission
cable is connected properly.
NOTE
: Check that there should be no disconnection when all pins and wires are pulled by hands.
Check whether the liquid pipe and gas pipe valves are fully opened.
NOTE
: Be sure to tighten caps.
Confirm that 500 V megger shows 2.0 MΩ or more between power supply terminal block and
ground. Do not operate in the case of 2.0 MΩ or less.
NOTE
: Never carry out mega ohm check over terminal control board.
Otherwise the control board may break.
Immediately after mounting the unit or after leaving it turned off for an extended length of
time, the resistance of the insulation between the power supply terminal board and the
ground maydecrease to approx. 2.0 MΩ as a result of refrigerant accumulation in the internal
compressor.
If the insulation resistance is less than 2.0 MΩ, turn on the main power supply.
1
2
3
1. Check before Test Run
Содержание AS - W126BMS0
Страница 3: ...3 1 Safety Precautions 4 2 Nomenclature 7 Part 1 General Information...
Страница 16: ...16 Part 3 Test Run 1 Check before Test Run 17 2 Test Run Flow chart 18 3 Test Run Detail 19...
Страница 37: ...Part 4 Trouble Shooting 37 Troubleshooting Guide Indoor Unit...
Страница 41: ...Part 4 Trouble Shooting 41 verify with hands verify with hands...
Страница 44: ...Part 4 Trouble Shooting 44 Case of field defect IPM Over Current Limit Bending Folding SVC Valve close...
Страница 46: ...Part 4 Trouble Shooting 46 3 CH23 DC Link Low Voltage Error...
Страница 51: ...Part 4 Trouble Shooting 51 8 CH40 CT Sensor Error Open Short Tester Tester...
Страница 52: ...Part 4 Trouble Shooting 52 9 CH41 44 45 65 Inv D Pipe Outdoor Inlet Cond Pipe Heat sink Sensor Error...
Страница 53: ...Part 4 Trouble Shooting 53 10 CH53 Outdoor Unit Indoor Unit Communication Error...
Страница 56: ...Part 4 Trouble Shooting 56 13 CH62 Heat Sink Overheat Error...
Страница 57: ...Part 4 Trouble Shooting 57 14 CH67 Outdoor BLDC Fan Lock Error Case of field defect BLDC Fan Motor short...
Страница 59: ...Part 4 Trouble Shooting 59 Resistance between the lines of each 1 5 2 1 5 2 1 5 2 U V V W W U...
Страница 61: ...Part 4 Trouble Shooting 61 3 CH23 DC Link Low Voltage Error...
Страница 66: ...Part 4 Trouble Shooting 66 8 CH41 44 45 65 Inv D Pipe Outdoor Inlet Cond Pipe Heat sink Sensor Error...
Страница 67: ...Part 4 Trouble Shooting 67 9 CH53 Outdoor Unit Indoor Unit Communication Error...
Страница 68: ...Part 4 Trouble Shooting 68 10 CH60 Outdoor Unit PCB EEPROM Error...
Страница 71: ...Part 4 Trouble Shooting 71 13 CH67 Outdoor BLDC Fan Lock Error...
Страница 72: ...P No MFL41161608...