2 Safety instructions
2
8
Rittal Liquid Cooling Package
Leak test pursuant to Article 4 (leak checks)
The leak checks shall be carried out with the following
frequency, depending on the CO
2
equivalent quantities
of fluorinated greenhouse gases.
–
5 t – 50 t
at 12-month intervals, (or where a leakage
detection system is installed, at least every
24 months),
–
50 t – 500 t
at 6-month intervals, (or where a leakage
detection system is installed, at least every
12 months),
–
more than 500 t
at 3-month intervals, (or where a
leakage detection system is installed, at least every
6 months).
2.3.4
Chemicals – Climate Protection Ordinance
This Ordinance applies in addition to the aforementioned
Regulation (EC) No. 517/2014 of the European Parlia-
ment and of the Council of 16 April 2014.
2.4
RoHS compliance
The LCP DX fulfils the requirements of EU Directive
2011/65/EC on the Restriction of Use of Certain Hazard-
ous Substances in Electrical and Electronic Equipment
(RoHS) of 1 July 2011.
Note:
Corresponding information about the RoHS
Directive may be found on our website at
www.rittal.com/RoHS.