![FRIEDHELM LOH 3313.410 Скачать руководство пользователя страница 48](http://html1.mh-extra.com/html/friedhelm-loh/3313-410/3313-410_assembly-and-operating-instructions-manual_2332659048.webp)
11 Technical specifications
11
48
Rittal Liquid Cooling Package
11.5 Total refrigerant charge
11.6 Refrigerant pipes
Connection diameter LCP Rack DX/LCP Inline DX 12 kW: 12 mm/12 mm
System: LCP DX + con winter kit mod-
ule (in case of it)
Fill volume up to a line length
of 5 m [kg]
Fill volume per metre above
5 m [kg]
System with standard condenser
2.8
0.03
System with low temperature condenser and winter
kit module
4.8
0.03
System with high temperature condenser
2.65
0.03
Tab. 23:
Total refrigerant charge
Type of
condenser
Connection diameter condenser
liquid line/hot gas line
[mm]
Equivalent
length
External diameter of coolant lines
liquid line/hot gas line
[mm]
Standard
22/22
Up to 45 m
12/12
Low temperature
16/16
Up to 45 m
12/12
High temperature
22/22
Up to 45 m
12/12
Tab. 24:
Refrigerant pipes