5 Assembly and siting
5
18
Rittal Liquid Cooling Package
item 4).
Using a sharp knife, cut additional pieces from the
foam strip that are at least as long as the height of the
built-in devices.
Attach the foam strips to the cold air side of the devic-
es set back towards the rear (fig. 14, item 4), making
sure that all fans built into the devices can draw air and
that none of them are blocked.
Fig. 14:
Placement of foam strips for devices with sideways air
throughput (top view) – LCP Rack DX
Key
1
LCP Rack DX
2
Server enclosure
3
Foam strips on hot air side
4
Foam strips on cold air side
If there is any surplus length of the foam strip on the
server rack, cut it off at the top edge of the rack.
On the side of the server enclosure opposite the
LCP DX, mount a side panel on the two side panel
mountings. Align it with the front and rear of the enclo-
sure.
Using the 8 assembly screws, screw the side panel
firmly onto the side panel holders and the side panel
mounting brackets.
Seal off any cable entries which may be present with
corresponding brush strips or similar.
5.2.5
Installation and baying of the LCP DX
Position the LCP DX on the side of the server enclo-
sure to which it is to be bayed.
Align the LCP DX with the server enclosure. Ensure
that the LCP DX is aligned horizontally and that both
enclosures are adjusted to the same height and are
vertically aligned to each other.
Dismantle the door of the LCP DX whose hinges are
on the side on which the server enclosure is to be
bayed.
Using the corresponding assembly screws, fasten two
baying connectors each (fig.15, item 2) onto the at-
tachment points provided in the mounting strips on
the front and rear of the LCP DX (fig.15, item 1).
Note:
The foam strips can be attached between the
front and rear uprights of the server rack
along the entire depth of the devices with
sideways air throughput (fig. 14).
Note:
The LCP DX may optionally be bayed onto a
server enclosure either 600 mm or 800 mm
wide. For this reason, the LCP DX accesso-
ries include a total of four foam strips or cor-
responding air baffle plates with differing
dimensions (see section 13 "Accessories").
IT rack
4
3
1
2
Note:
If the LCP DX is to be bayed between two
server enclosures, both doors of the LCP DX
must be dismantled before the baying con-
nectors are installed, so that the attachment
points for the baying connectors are accessi-
ble.