5 Assembly and siting
5
20
Rittal Liquid Cooling Package
Fig. 16:
Air streams with unprotected siting
Key
1
Facade mounting
2
Condenser airflow
3
External air stream
4
Building roof or site floor
5
Console installation
The condenser is weather-resistant and may therefore
be installed completely in the open air, with no need for
a weather protection canopy etc. If the condenser is in-
stalled underneath a canopy, there must be a distance
of at least 4 m between the floor and the canopy.
Fig. 17:
Minimum distances with vertical mounting.
If the distance is less than 4 m, the condenser must be
mounted in such a way that the air outlet is horizontal.
Fig. 18:
Installation options with horizontal air outlet
The condenser may be installed either horizontally or
vertically using the supports included with the supply of
the device.
Fig. 19:
Horizontal or vertical mounting
In the case of vertical mounting (with a horizontal air-
flow), the hot gas line must be laid above the liquid line.
Fig. 20:
Laying the hot gas and liquid lines
Note:
Opening "A" must be at least as large as the
front of the condenser.
1
3
4
5
3
2
2