SWX CE
6
Output charts water
Incoming / outgoing water temperature 90/70 °C
Air temp. in = +5 °C
Air temp. in = +15 °C
Type
Airflow
[m³/h]
Output
[kW]
Air temp.
out
[°C]
Water flow
[l/s]
Pressure
drop
[kPa]
Output
[kW]
Air temp.
out
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
SWXCE12
2100
29,5
45,2
0,37
11,9
24,8
50,1
0,31
8,6
SWXCE22
4200
56,6
43,6
0,70
30,3
47,7
48,8
0,59
22
Incoming / outgoing water temperature 80/60 °C
Air temp. in = +5 °C
Air temp. in = +15 °C
Type
Airflow
[m³/h]
Output
[kW]
Air temp.
out
[°C]
Water flow
[l/s]
Pressure
drop
[kPa]
Output
[kW]
Air temp.
out
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
SWXCE12
2100
25,2
39,4
0,31
9,0
20,6
44,2
0,26
6,1
SWXCE22
4200
48,5
38,1
0,60
23,1
39,8
43,2
0,49
15,9
Incoming / outgoing water temperature 60/40 °C
Air temp. in = +5 °C
Air temp. in = +15 °C
Type
Airflow
[m³/h]
Output
[kW]
Air temp.
out
[°C]
Water flow
[l/s]
Pressure
drop
[kPa]
Output
[kW]
Air temp.
out
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
SWXCE12
2100
16,4
27,4
0,20
4,2
11,9
31,9
0,15
2,3
SWXCE22
4200
32,2
26,9
0,40
11,2
23,7
31,8
0,29
6,4
SWX CE