13

GB

3. The fan heater is fitted with a transport protection that is attached 
to the top and bottom. Loosen the four screws that have the Torx 20 
head as shown in Figure C and remove the transport guard. Replace the 
screws, see figure D. 

4.  The fan heater may be mounted with the connection pipes facing 
left or right, as seen from the front. In rooms with high ceilings, the 
fan heater should be installed in a low position, but not so low that it 
intrudes on the working space. Make sure that the wall is able to support 
the weight of the fan heater. 

6. Mount the fan heater as shown in photo F 
when mounting it on the ceiling for a vertical 
air stream. The minimum distance to the 
wall should be 700 mm. If the fan heater 
is mounted on a ceiling, near a corner, the 
minimum distance to one of the walls should 
be 700 mm and to the other 1000 mm. Make 
sure that the ceiling is able to support the 
weight of the fan heater. 

5.  The fan heaters are delivered with the air 
deflector installed for water connection on the 
left hand side. If the fan heater is mounted 
with the pipes facing right, the air deflector 
must be turned for the air to be deflected 
downward. Remove the six screws (Torx 20) 
attaching the air deflector as shown in picture 
E, lift out the air deflector and turn it 180°. 
Then reattach it. 

Содержание SWXCE12

Страница 1: ...SWX CE Original instructions 7 SE 12 GB 17 NO 22 DE 27 ES 32 FR 37 IT 42 NL 47 PL 52 RU ...

Страница 2: ...X CE 2 SWX CE mm A B C D E F G H ØI SWXCE12 550 530 380 630 R3 4 250 330 410 10 SWXCE22 705 655 430 700 R1 270 420 505 10 Electrical installation 230V 0 85 m cable Terminal box min 150 B E F C D A G H ØI ...

Страница 3: ...650x15 SWXHFT SD20 Controls SWX CE Note Only for mounting outside corrosive environment Type RSK nr SE NRF nr NO SD20 672 70 37 85 021 57 TVV20 672 70 35 85 021 47 TVV25 672 70 36 85 021 48 Water regulation SWX CE TVV20 25 SWXRT35 Type RSK nr SE NRF nr NO HxWxD mm SWXRT35 175x150x100 ...

Страница 4: ...at only SWX CE SWX CE CS 12 22 SWXD 13 23 M N L BK BU WT RD 11 10 L N 230V SWXRT35 SWXCE CS 12 22 SD20 M TVV20 25 L 7 6 5 4 3 2 1 N 8 N L BK BU WT RD 11 10 SWXCE CS 12 22 M N L BK BU WT RD 11 10 SD20 TVV20 25 Note Only for mounting outside corrosive environment ...

Страница 5: ...ć ES Volumen de agua IT Volume acqua NL Water volume GB Voltage SE Spänning NO Spenning FR Tension RU Напряжение DE Spannung PL Napięcie ES Tensión IT Tensione motore NL Voltage GB Amperage SE Ström NO Strøm FR Intensité RU Сила тока DE Stromstärke PL Natężenie ES Intensidad IT Corrente motore NL Stroom sterkte GB Weight SE Vikt NO Vekt FR Poids RU Вес DE Gewicht PL Waga ES Peso IT Peso NL Gewicht...

Страница 6: ...ir temp in 5 C Air temp in 15 C Type Airflow m h Output kW Air temp out C Water flow l s Pressure drop kPa Output kW Air temp out C Water flow l s Pressure drop kPa SWXCE12 2100 25 2 39 4 0 31 9 0 20 6 44 2 0 26 6 1 SWXCE22 4200 48 5 38 1 0 60 23 1 39 8 43 2 0 49 15 9 Incoming outgoing water temperature 60 40 C Air temp in 5 C Air temp in 15 C Type Airflow m h Output kW Air temp out C Water flow l...

Страница 7: ...lly for use in corrosive environments such as offshore or chemical industry Fitting the wall brackets 1 Remove the eight screws indicated by the arrows in picture A 2 Install the brackets with the holes toward the fan motor as shown in picture B Meets the requirements for corrosion class C5 M Uses hot water as the energy medium Casing air deflector grille and brackets made of acid proof stainless ...

Страница 8: ...eater 6 Mount the fan heater as shown in photo F when mounting it on the ceiling for a vertical air stream The minimum distance to the wall should be 700 mm If the fan heater is mounted on a ceiling near a corner the minimum distance to one of the walls should be 700 mm and to the other 1000 mm Make sure that the ceiling is able to support the weight of the fan heater E F 5 The fan heaters are del...

Страница 9: ... highest position according to the arrows in Figure G The connection is R3 4 on SWXCE12 and R1 on the SWXCE22 7 When tightening the couplings on the connection nipples these must be held so that no torque is transferred to the fan heater s inlet and outlet pipes see figure H Important Make sure the entire system is close to the water connection Any potential leakage can cause expensive water damag...

Страница 10: ...e grille and on the water coil s aluminum fins impedes the airflow and reduces its heat exchanging performance The water coil must therefore be kept clean Use mild detergents that do not affect the surface treatment of the coil The fan cooling flanges also need to be kept clean to obtain the lowest possible motor operating temperature With the inspection hatch picture K removed the water coil s al...

Страница 11: ... hazards involved Children shall not play with the appliance Cleaning and user maintenance shall not be made by children without supervision Children of less than 3 years should be kept away unless continuously supervised Children aged from 3 years and less than 8 years shall only switch on off the appliance provided that it has been placed or installed in its intended normal operating position an...

Страница 12: ...in office Frico AB Tel 46 31 336 86 00 Box 102 SE 433 22 Partille mailbox frico se Sweden www frico se For latest updated information and information about your local contact www frico se 2018 04 18 HH CH ...

Отзывы: