C
D
SWX CE
13
GB
3. The fan heater is fitted with a transport protection that is attached
to the top and bottom. Loosen the four screws that have the Torx 20
head as shown in Figure C and remove the transport guard. Replace the
screws, see figure D.
4. The fan heater may be mounted with the connection pipes facing
left or right, as seen from the front. In rooms with high ceilings, the
fan heater should be installed in a low position, but not so low that it
intrudes on the working space. Make sure that the wall is able to support
the weight of the fan heater.
6. Mount the fan heater as shown in photo F
when mounting it on the ceiling for a vertical
air stream. The minimum distance to the
wall should be 700 mm. If the fan heater
is mounted on a ceiling, near a corner, the
minimum distance to one of the walls should
be 700 mm and to the other 1000 mm. Make
sure that the ceiling is able to support the
weight of the fan heater.
E
F
5. The fan heaters are delivered with the air
deflector installed for water connection on the
left hand side. If the fan heater is mounted
with the pipes facing right, the air deflector
must be turned for the air to be deflected
downward. Remove the six screws (Torx 20)
attaching the air deflector as shown in picture
E, lift out the air deflector and turn it 180°.
Then reattach it.