SWX EX12, SWX EX22
EU-Type Examination Certificate
Presafe 15 ATEX 7676X, Issue 0
[16] Report No.:
D0002321.
[17] Specific Conditions of Use
1)
The fan heater must not be connected to hot mains water or steam. The highest
temperature and pressure allowed is
indicated on the identification plate, with the
maximum inlet water temperature is restricted to 125°C
2) The fan motor is fitted with PTC thermistors to protect against overheating, and thus
therefore be connected to certified motor protector U-EK230E and a contactor placed in the
safe area.
3)
Electrical connection to the mains requires fixed wiring. A multi-pole breaker with a
minimum 3 mm length of break
must be used for the permanent installation, using Ex
approved components in the risk area.
[18] Essential Health and Safety Requirements
Essential Health and Safety Requirements (EHSRs) are covered by the standards listed at item 9
[19] Drawings and documents
Number
Title
Rev.
Date
59031
Frico SWX Ex 12/ SW Ex 22 (Type table location and
warning lable location
1
2017-01-18
173123
Installation and maintenance instrcutions
1
-
Refer Confidential report D0002321 for the complete descriptive list of technical drawings.
[20] Certificate History
Issue
Description
Issue date
Report no.
0
Original issue
2017-01-27
D0002321
END OF CERTIFICATE
3 of 3