Operating modes

Door that is opened and closed

The control function notes whether the door is 
open or closed as standard, this mode is default 
set and is called Fixed flexible (the setting is 
under Installer menu > Settings fan > Door mode). 
 

Open door

Indicates OP on the installer status screen. 
Fan control runs at high speed mode and is 
controlled to outdoor temperature. During 
dropping outdoor temperatures during the winter 
and increasing outdoor temperatures during 
summer the fan speed increases. High speed limit 
is set under Main Menu > Fan control > High 
speed limit.
The control curves to the outdoor temperature 
are set under Installer menu > Settings fan > Fan 
speed increase where temperatures for min- and 
max speed are set for summer and winter modes.
 Normally it is requested that heat is engaged 
when the door is opened. The set point value 
(Room temp. day) is then increased with the fixed 
set point value difference that can be changed 
under Installer menu> Settings heating > Open 
door setp. diff., factory setting 3.0 K. The set 
point is set under Main Menu > Temperature 
settings > Room temp. day. If week program is 
used the night time set point value is set under 
Main menu > Temp. settings > Room temperature 
night. The room temperature is regulated using 
the integrated room temperature sensor or the 
external room temperature sensor, SIReRTX 
(option). 
 

Closed door

Indicated CL on the installer status screen. 
When heating demand the fan speed runs at 
low speed which is set under Main menu > Fan 
speed > Speed closed door. Heating is regulated to 
Room temp. Day which is set under Main Menu > 
Temperature settings > Room temp. day.
 If week program is used the night time set point 
value is regulated against the Room temperature 
is set under Main menu > Temp. settings > Room 
temperature night. The room temperature is 
regulated using the integrated room temperature 

sensor or the external room temperature sensor, 
SIReRTX (option).  
 

When the door is closed - over run

When the door has been closed, high speed mode 
remains during the fixed time that is set under  
Installer menu > Settings fan > Door over run 
> High speed over run and at low speed during 
a fixed time under Installer menu > Settings 
fan> Door over run > Low speed over run, on 
the condition that it is sufficiently warm in the 
premises, otherwise the fans run until the desired 
temperature has been reached.
When the door is closed, the set point value shifts 
from room tempe fixed set point value 
difference for open door to Room temp. day/night.

 Over run is factory set so that the over run 

times are controlled according to how often the 
door is opened (Auto mode under Installer menu 
> Settings fan > Door over run > Over run mode).

Doors that are always or often left open for 
longer periods

If a door is always, or often, left open it is possible 
to use a function called CURRENT STAGE instead. 
The fan and heating steps increase/decrease 6 or 
9 steps (depending on the type of unit) and are 
only controlled by the room temperature.  Actual 
Current stage is shown in the status screen.

The function current stage is activated in two 

ways:

Door that are always open

For a door that is always open, door mode Fixed 
open > can be selected under >Settings fan> Door 
mode.

Doors that are often open

For a door that is often open  Auto can be selected 
under Installer menu > Settings fan > Door mode. 
In Auto mode, the control automatically switches 
between Fixed flexible and Fixed open modes 
depending on how often the door has been open 
(when the door has been open for longer than 300 
seconds the function changes from Fixed Flexible 
to Fixed Open).
 

Содержание SIReAA

Страница 1: ...SIRe Advanced Air Curtains Electric With quick guide SIReAA For wiring diagram please see last pages Original instructions 102 IT 82 ES 122 NL 142 NO 181 RU 162 PL 22 GB 2 SE 42 DE 62 FR...

Страница 2: ...ed using mo dular cable RJ11 4p 4c on HUB SIReA1X Door switch SIReDC and outdoor sensor SIRe OTX is connected on PC Board HUB SIReA1X Control board Base SIReB1 X in at the unit and control unit SIReUA...

Страница 3: ...est 5 Start up wizard Function test Test completed Restart test 6 Start up wizard Start up finished Proceed Restart wizard 10 Start up wizard Eco Comfort Comfort mode Eco mode 7 Start up wizard Screen...

Страница 4: ...of current stage 28 Control unit SIReUA1 Overview 30 Statuswindow 30 Main menu Current settings 31 Temperature settings 31 Fan control 31 System on off 31 Installer menu 31 Installer menu Installer st...

Страница 5: ...ced 202x139x50 SIReOTX Outdoor temperature sensor 70x33x23 SIReDC Magnetic door contact SIReCC603 Modular cable RJ12 6 6 3 SIReCC605 Modular cable RJ12 6 6 5 Integrated in the air curtain Dimensions c...

Страница 6: ...7 87 510 17 Modular cable RJ11 4 4 3 SIReCC405 673 09 28 87 510 18 Modular cable RJ11 4 4 5 SIReCC410 673 09 29 87 510 19 Modular cable RJ11 4 4 10 SIReCC415 673 09 30 87 510 20 Modular cable RJ11 4 4...

Страница 7: ...int value is regulated against the Room temperature is set under Main menu Temp settings Room temperature night The room temperature is regulated using the integrated room temperature sensor or the ex...

Страница 8: ...s the current stage increases by 1 step If the room temperature is more than 2 degrees above the current setting the current stage decreases by 1 step Summer When the outdoor temperature is greater th...

Страница 9: ...Current stage Fan Heating 0 0 0 1 1 0 2 2 0 3 2 1 4 3 1 5 3 2 Current stage Fan Heating 0 0 0 1 1 0 2 2 0 3 2 1 4 3 1 5 3 2 6 4 2 7 5 2 8 5 3 Table Current stage for units with 5 fan controls Table Cu...

Страница 10: ...Night Explanations Statuswindow The display shows the prevailing room temperature fan and heating step door status and day night mode or Off when the week program is used Forward arrow Confirm selecti...

Страница 11: ...settings Set the desired room temperatures to apply for day respectively night mode when the door is closed room temperature night is used for week program night reduction At open door these set poin...

Страница 12: ...Day Installer menu To enter the Installer menu code 1932 is entered Select the digits using the rotary dial and confirm using the forward arrow To check which days a certain program is active select a...

Страница 13: ...on off In On mode a sun moon or Off in the Status window appears to indicate day night respectively Off function Fan settings Make settings for fan mode see also Operating modes section Fan speed incr...

Страница 14: ...30 C Eco Comfort Select between Eco and Comfort mode depending on whether energy savings or optimal comfort is more important Comfort mode gives faster Door over run Settings for overrun In over run m...

Страница 15: ...he set room temperature In Eco mode the heating adapts to the desired level a little more slowly when a temperature change occurs which gives lower energy consumption only valid for units with interna...

Страница 16: ...filter guard Installer menu Filter guard settings Filter alarm alarms when the set fixed run time has been exceeded Filter timer setting Under Filter timer setting set the desired run time to between...

Страница 17: ...3 2 1 11 V V 7 2 7 6 5 0 5 4 2 8 3 2 3 2 1 10 9 8 7 6 5 4 3 2 1 11 V 6 8 7 2 2 8 3 2 2 1 10 9 8 7 6 5 4 3 2 1 11 V Diagram Fan step at incoming 0 10V DC voltage level 5 step Diagram Fan step for incom...

Страница 18: ...est Test completed Restart test Installer menu General settings Heating step off 1 Fan step 1 5 Installer menu General settings Possibility of making general settings that are also in the Start up wiz...

Страница 19: ...alarm can be read At the first start up alarm and error codes can occur these can usually be reset without action Power failure Note that in case of power failure the time settings need to be checked...

Страница 20: ...ct the power when connecting or disconnecting sensors Check connection of the sensor E20 Communication Control unit SIReUA1 has no contact with SIReA1X Check the connection Replace any modular cables...

Страница 21: ...Connecting external control including BMS functions RPM indication 0 10V DC OUT max 5 mA Signal from SIRe indicates fan control corresponds to 0 100 fan control Always active Heating indication 0 10V...

Страница 22: ...DC ALARM OUT BMS potential free contact max 3A 230V 7 8 9 10 1112 15 161718 19 20 COM 1 COM 2 BUS ROOM SIReA1X C2 X5 C1 X4 ROOM X3 Pot Unit ID SIReB1 N L PE N L PE BMS INDICATION OUT potential free co...

Страница 23: ...15 161718 19 20 COM 1 COM 2 BUS ROOM SIReA1X C2 X5 C1 X4 ROOM X3 Pot Unit ID SIReB1X N L PE N L PE BMS INDICATION OUT potential free contact max 3A 230V 1 2 3 4 5 6 13 14 RPM INDICATION 0 10V DC out m...

Страница 24: ...718 19 20 COM 1 COM 2 BUS ROOM SIReA1X BMS INDICATION OUT potential free contact max 3A 230V 1 2 3 4 5 6 13 14 RPM INDICATION 0 10V DC out max 5 mA EXTERNAL HEAT 0 10V DC IN 21 22 SIReOTX HEAT INDICAT...

Страница 25: ...B Tel 46 31 336 86 00 Box 102 Fax 46 31 26 28 25 SE 433 22 Partille mailbox frico se Sweden www frico se For latest updated information and information about your local contact www frico se Art no E44...

Отзывы: