SIRe Advanced Air Curtains Electric
34
GB
Time between
opening [s]
High speed over
run [s]
Low speed over
run [s]
t < 60
30
90
60 < t < 300
10
300
t > 300
0
180
>Installer menu>Fan
settings>Door over run
Over run mode
Auto
>Installer menu>Fan
settings>Door over run
Over run mode
High speed over run
Low speed over run
•
>Installer menu>Fan
settings>Door over run
Over run mode
Fixed time
>Installer menu>Fan
settings>Door over run
Over run mode
High speed over run
Low speed over run
•
>Installer menu>Fan settings
Door over run
Door mode
>Installer menu>Fan settings
Door mode
Fixed flexible
•
Filter guard settings
Fan settings
Heating settings
>Installer menu
Door mode
Fan speed increase
Door over run
>Installer menu>Fan settings
Stepless fan
>Installer menu>Fan settings
Stepless fan
•
>Installer menu>Fan settings
Door mode
Door over run
Stepless fan
>Installer menu>Heating
settings
Outdoor temp. limit
>Installer menu>Heating
settings
Outdoor temp. limit
Eco / Comfort
Open door setp. diff.
•
>Installer menu>Heating
settings
Outdoor temp. limit
Eco / Comfort
>Installer menu>Heating
settings
Eco / Comfort
Comfort mode
•
Open door setp. diff.
OFF
15°C
Eco mode
Outdoor temp. limit
Blocking heating summer time.
Factory setting
Outdoor temp. limit: 15°C (5 – 30°C)
Eco / Comfort
Select between Eco and Comfort mode depending
on whether energy savings or optimal comfort
is more important. Comfort mode gives faster
Door over run
Settings for overrun.
In over run mode Auto, SIRe controls the over
run time depending on how frequently the door
is opened between openings, according to fixed
preset values, according to the table.
Over run mode Fixed time is selected is one wants
fixed over run times, the times can be changed
during High speed over run and Low speed over
run.
Factory setting
Over run mode:
Auto (Set time)
High speed over run:
30 s (0 – 180 s)
Low speed over run:
120 s (0 – 300 s)
Door mode
There are three different door modes to choose
from; Auto, Fixed flexible and Fixed open.
In Fixed flexible mode, the control function notes
whether the door is open or closed. In Fixed open
mode the door is considered always open and is
only controlled according to Current stage. In
Auto mode, the control automatically switches
between Fixed flexible and Fixed open modes
depending on how often the door has been open.
Factory setting
Door mode: Fixed flexible (Fixed open/
Auto)
Stepless fan control
Settings for stepless fan control.
Fans are controlled in 3 or 5 steps as standard.
If stepless fan control is selected, the fans can be
controlled steplessly via an external frequency
converter for example.
Factory setting
Stepless fan control: Off (On)
Heating settings
Make settings for heating.