Adjusting the unit and the airflow

Direction and speed of the airflow should be 
adjusted according to the load on the door. 
Outside pressure forces the air stream to 
bend towards the interior of the room (when 
the room is heated and the outside is cold). 
To reduce this effect, the airflow should be 
directed outwards. The air director/grille is 
adjustable and should be angled outwards 
(5°-10°) to achieve the best protection of 
the door. The more load caused by negative 
pressure differential, temperature differences 
and wind, the more should the airflow 
be directed outwards. The airflow can be 
adjusted by use of the control box (CB22 or 
CB20). The efficiency of the air curtain(s) 
depends on the air temperature and pressure 
differences across the doorway and any wind 
forces. 

NOTE! Negative pressure differential in 
buildings considerably reduces the efficiency 
of the air curtain, ventilation should 
therefore be balanced.  

The airflow is set with the airflow selector so 
that the air velocity is 3-4 m/s 1 m above the 
floor. NOTE! When PS210E09 or PS215E14 
is set on high heat output, the fan speed 
is automatically set to high. A baffle on 
each side of the doorway will improve the 
efficiency of the air curtains. 

Trouble shooting

If the fans stop, check the following: 

a) Power supply; check fuses, safety cut-out 
and time switch (if any) that starts and stops 
the unit. 
b) That the airflow selector is correctly set.  
If the error cannot be fixed, please contact 
qualified service technician.  

If there is no heat, check the following: 

a) Power supply to electric heater; check 
fuses and safety cut-out (if any). 
b) Thermostat settings and actual 
temperature. 
c) That the output selector (if any) is set 
correctly. 
d) That the overheat protection has not 
been released. If so, please check description 
below.  

Overheating 

Portier is equipped with an overheat 
protector. 

If it is released due to overheating, reset as 
follows: 

a) Disconnect the electric supply. 
b) Investigate the problem and repair the 
fault. 
c) Reset is performed as follows: Locate the 
red button which is located inside the air 
curtain at the inner gable to which the fan 
and the motor are attached. It can be seen 
through the outlet grille see fig. D. Press the 
button with at screw driver until a click is 
heard. 
d) Connect the air curtain again.  

If the error cannot be fixed, please contact 
qualified service technician.

Maintenance 

NOTE! Always disconnect the electricity prior 
to cleaning or inspection (units with electric 
heat can be supplied from more than one 
connection).  The fan motors and the other 
components require no maintenance other 
than cleaning, once a year is recommended. 
Grille, impeller and elements are vacuum 
cleaned or cleaned with a damp cloth. 
Open the front panel to reach elements and 
impellers. 

Содержание Portier PS210A

Страница 1: ...Portier 10 SE 13 GB 16 FR 19 RU...

Страница 2: ...Portier 2 PS210 1020 PS215 1530 PS210 816 PS215 1335 291 138 280 M6 4x K O 29 K O 23 111 96 100...

Страница 3: ...Portier 3 Threaded bar M6 not included Wire not included Screw eye M6 Fig A Fig C B A A min 80 mm A B min 120 mm Fig B Reset Temp limiter To open T o o p e n Fig E Fig D...

Страница 4: ...Portier 4 Fig F PS210 215E...

Страница 5: ...Portier 5 Fig G PS210 215E...

Страница 6: ...Portier 6 Fig H CB20 PS210 215A PS210A PS215A 230V 11 14 12 L N DC DC MDC 21 24 22 31 34 32...

Страница 7: ...Portier 7 Fig I CB20 PS210 215A PS210A PS215A...

Страница 8: ...3N PS210E03 400V 3N 1 5 mm PS210E06 400V 3N 1 5 mm L N L1 L2 L3 230V 3 PS210E6 230V 3 2 5 mm L N L1 L2 L3 PS210E09 400V 3N 2 5 mm PS210E09 230V 3 6 mm PS215E09 400V 3N 2 5 mm PS215E09 230V 3 6 mm PS21...

Страница 9: ...upply if the current is greater than 16 A Applies when connecting several units Protection class IP21 CE compliant Type Output steps kW Airflow m3 h t 2 C Sound level dB A 1 Voltage V Amperage A Lengt...

Страница 10: ...onnected to the lifting loops included See fig A It s also possible to use threaded bars M6 connected directly to the threaded holes on top of the unit See fig C Electrical installation The air curtai...

Страница 11: ...wer supply check fuses safety cut out and time switch if any that starts and stops the unit b That the airflow selector is correctly set If the error cannot be fixed please contact qualified service t...

Страница 12: ...ionally be run for a short time when it is not being used for extended periods of time Safety For all installations of electrically heated products should a residual current circuit breaker 300 mA for...

Страница 13: ......

Страница 14: ......

Страница 15: ...20 HH S CH Main office Frico AB Tel 46 31 336 86 00 Box 102 Fax 46 31 26 28 25 SE 433 22 Partille mailbox frico se Sweden www frico se For latest updated information and information about your local...

Отзывы: