background image

RWB II ROTARY SCREW COMPRESSOR UNITS

MAINTENANCE

S70-200 IOM
Page 30

 13. Pack lubrication chamber between inner ball bearing 
and double-row ball bearing in the thrust-bearing as sem bly 
ap prox i mate ly one-half full of multipurpose grease, NLGI #2. 
The thrust-bearing assembly will take the remaining space. 
See Figure 26 and 27.

 14. Pack double-row ball bearing with multipurpose grease, 
NLGI #2.

GG, HJ, HL: Install ball bearing into bearing hous ing with 
shield side toward coupling end of shaft. See Figure 26. 
In stall snap ring into bearing hous ing to retain ball bearing. 
This snap ring has a ta pered edge to fi t tapered groove in 
bearing housing. The tapered edge is lo cat ed away from 
ball bearing.

AS, AK, AL: Install ball bearing into bearing hous ing. In stall 
lip seal in bearing housing end cap. The lip should face to-
 wards end of shaft. Put bearing spac er col lar in lip seal and 
install in bearing housing and tighten setscrews se curely. 
See Figure 27.

 15. Insert brass bar or hard wood through port open ing be-
 tween rotor teeth to keep shaft from turn ing.

 16. Start thrust-bearing as sem bly into casing. Turn by hand 
un til tight. This forces rotor against head. Replace and tight en 
locknut or shaft.

 17. Remove brass bar or hardwood from port opening.

 18. Adjust pump end clearance.

BEFORE STARTING PUMP, EN-
 SURE THAT ALL DRIVE EQUIP-
 MENT GUARDS ARE IN PLACE. 

FAIL URE TO  PROP ER LY MOUNT GUARDS MAY RE SULT 
IN  SE RI OUS IN JU RY OR DEATH.

THRUST BEARING AD JUST MENT

See Figures 26 and 27.

Loosen two screws in face of thrust-bearing as sem bly.

If shaft cannot be rotated freely, turn thrust-bearing as sem bly 
coun ter clock wise until shaft can be turned easily.

1. While turning rotor shaft, rotate thrust-bearing assembly 
clockwise until noticeable drag oc curs. This is zero end 
clear ance.

2. Mark position of bearing housing with respect to the 
cas ing.

3. Rotate thrust-bearing assembly coun ter clock wise the 
dis tance listed below as measured on out side of bearing 
hous ing.

4. Tighten two setscrews in face of bearing housing after 
adjust ment is made to secure thrust-bearing assembly 
po si tion.

For viscosities above 2500 SSU, add additional end clear-
 ance (0.004" for GG, HJ and HL size pumps and 0.005" for 
AS, AK and AL size pumps).

 

Pump 

Distance (in.) on O.D. 

End Clearance

 

Size 

of Bearing Housing 

(in.)

 

GG 7/16  .003

 HJ, 

HL 

9/16 

.003

  AS, AK, AL

 

1/2 

.

003

IN STAL LA TION OF CARBON GRAPHITE 

BUSH INGS

When installing carbon graphite bushings, extreme care 
must be taken to prevent breaking. Carbon graphite is a 
brittle material and easily cracked. If cracked, the bushing will 
quick ly disinte grate. Us ing a lubricant and adding a cham fer 
on the bush ing and the mating part will help in in stal la tion. 
The ad di tion al precautions listed below must be fol lowed for 
proper installation:

1. A press must be used for in stal la tion.

2. Be certain bushing is started straight.

3. Do not stop pressing operation until bushing is in proper 
position. Start ing and stopping will result in a cracked 
bush ing.

4. Check bushing for cracks after in stal la tion.

TROUBLESHOOTING THE DEMAND PUMP

BEFORE OPENING ANY PUMP 
LIQ UID CHAM BER (PUMP ING 
CHAM BER, RES ER VOIR, JACK ET 
ETC.) EN SURE:

1. THAT ANY PRESSURE IN CHAM BER HAS BEEN COM-
 PLETE LY VENT ED THROUGH SUC TION OR DIS CHARGE 
LINES OR OTH ER AP PRO PRI ATE OPEN INGS OR CON-
 NEC TIONS.

2. THAT THE  DRIVING  MEANS  (MOTOR, TUR BINE, 
EN GINE, ETC.) HAS BEEN “LOCKED OUT” OR MADE 
NON OPERATIONAL SO THAT IT CAN NOT BE STARTED 
WHILE WORK IS BEING DONE ON PUMP.

FAILURE TO FOLLOW ABOVE LISTED PRE CAU TION ARY 
MEASURES MAY RESULT IN SERIOUS INJURY
  OR 
DEATH.

Mark valve and head before disassembly to ensure proper 
reassembly.

If trouble does de vel op, one of the fi rst steps toward fi nd ing 
the diffi culty is to in stall a vacuum gauge in the suc tion port 
and a pressure gauge in the dis charge port
. Read ings on 
these gaug es often will give a clue as to where to start look-
 ing for the trouble.

Vacuum Gauge—Suction Port

1. High reading would indicate:

a. Suction line blocked - foot valve stuck, gate valve 

closed, strainer plugged.

b. Liquid too viscous to fl ow through the piping.
c. Lift too high.
d. Line too small.

2. Low reading would indicate: 

a. Air leak in suction line.
b. End of pipe not in liquid.
c. Pump is worn.
d. Pump is dry - should be primed.

3. Fluttering, jumping, or erratic reading:

a. Liquid va por iz ing.
b. Liquid coming to pump in slugs - possibly an air leak or 

in suf fi  

cient liquid above the end of the suc tion pipe.

c. Vibrating from cav i ta tion, mis align ment, or dam aged 

parts.

Содержание RWB II

Страница 1: ...MANUAL CONTAINS RIGGING ASSEMBLY START UP AND MAINTENANCE INSTRUCTIONS READTHOROUGHLY BEFORE BE GINNING INSTALLATION FAILURE TO FOLLOW THESE INSTRUC TIONS COULD RESULT IN DAMAGE OR IMPROPER OPERATION...

Страница 2: ...t in death or serious injury Indicates a potentially hazardous situation or practice which if not avoided will result in death or serious injury SAFETY PRECAUTION DEFINITIONS Indicates a potentially h...

Страница 3: ...lator or slugging protection that load surges are known and provisions made for control operating cycles and defrosting periods are reasonable and that high side condensers are sized within system and...

Страница 4: ...essor package When installing on the upper floors of buildings extra precau tions should be taken to prevent normal package vibration from being transferred to the building structure It may be necessa...

Страница 5: ...make sure that they are free of burrs dirt and grit CH COUPLING DATA TABLE 3 Check that the keys fit the hubs and shafts properly CH COUPLING The T B Woods Elastomeric CH Coupling is used in most app...

Страница 6: ...ocated Injury may occur if loose clothing etc becomes entangled on the spinning motor shaft If the motor is coupled to the compressor using a fixed end play coupling such as the Series 52 coupling and...

Страница 7: ...lignment compensates for thermal growth when the unit is at operating temperature The following procedure is applicable to both the CH and DBZ B couplings Dial indicators are to be used to measu re th...

Страница 8: ...isalignment is within specified tolerance 10 Check parallel lateral misalignment by positioning dial indicator so the stem is in contact with the rim of the com pressor hub at 3 o clock as shown in Fi...

Страница 9: ...charge checked periodically COMPRESSOR UNIT OIL DO NOT MIX OILS of different brands manufacturers or types Mixing of oils may cause excessive oil foaming nuisance oil level cutouts oil pressure loss g...

Страница 10: ...and vaporize The vapor rises in the return line The density of the refrigerant liquid vapor mixture in the return line is considerably less than the density of the liquid in the supply line This imbal...

Страница 11: ...pply of high pres sure liquid refrigerant be provided to the injection system at all times Two items of EXTREME IMPORTANCE are the design of the receiver liquid injection supply and the size of the li...

Страница 12: ...liquid injection oil cooling are given in the following table LIQUID LINE SIZE and RECEIVER VOLUME LINE SIZE POUND LIQUID RWB II SCH 80 OD PER VOLUME MODEL PIPE TUBING 5 MIN CU FT R 717 HIGH STAGE 100...

Страница 13: ...ect Expansion Economizer System Figure 11 Shell and Coil Economizer System Figure 14 Multiple Compressor Economizer System Figure 13 Flash Economizer System For refrigeration plants employing multiple...

Страница 14: ...the use of UPS power systems in front of the Quantum panel With a UPS power system providing shutdown protection for the Quantum the panel may not see the loss of the 3 phase voltage on the motor bec...

Страница 15: ...each normally open compressor motor and oil pump motor starter auxiliary contact should be supplied In addition to the compressor and oil pump motor starter coils the CT and CPT secondaries should be...

Страница 16: ...VE FERRITE TUBE WHEN SOLA IS ADDED 6B 6 H NOTE AT SOLA ASSEMBLY MAKE WIRES 6 2 GND 6B 2B 10 FT LONG CUT WIRESTO LENGTH AT INSTALLATION H5 REGULATOR H3 H4 OUTPUT INPUT X1 120 240 V IN 120 V OUT SOLA 63...

Страница 17: ...seal well below discharge pressure for increased seal life 10 Oil injected into the rotors to maintain good volumetric and adiabatic efficiency even at very high compression ratios 11 Shaft rotation c...

Страница 18: ...START VALVE DEMAND PUMP OIL SYSTEM This system is designed to provide adequate compressor lubrication for some high stage applications that operate with low differential pressure across the compresso...

Страница 19: ...rough valve ports P and A to cylinder port SC 1 and enters the unload side of the cylinder Simultaneously oil contained in the load side of the cylinder flows out com pressor port SC 2 through valve p...

Страница 20: ...system contains all the components of the single port system with the addition of a double acting so lenoid valve SV7 and operates as outlined Solenoid valve SV5 is energized by the microprocessor whe...

Страница 21: ...injection valve look at the power head of the Thermal Expansion Valve If the unit is using Ammonia as a refrigerant and is for low temperature the Sporlan number on the power head should be Y764 or Y8...

Страница 22: ...diagram in S90 010 M Quantum or S70 200 OM Plus shows the wiring included when required Introduction of high discharge pressure gas is made to the check valve A timer limits the high pressure gas to o...

Страница 23: ...ressor s economizer port If an electric shut off is not installed in the economizer vapor line valve HV 2 must remain closed to avoid a gas bypass from the economizer line through the suction check va...

Страница 24: ...hut down on Comp Differential 4 After running the unit for approximately three hours adjust liquid injection oil cooling if applicable If unit has thermosy phon or water cooled oil cooling adjust wate...

Страница 25: ...pplicable Re move tags 3 Close disconnect switches for compressor motor and oil pump starters 4 Turn off oil heater circuit breaker 5 Perform checkpoints on prestart check list then start unit GENERAL...

Страница 26: ...vice valves of the standby filter Open inlet service valve slowly to prevent a sudden pressure drop which could cause an oil filter dif ferential alarm 2 Close outlet then inlet service valves of fil...

Страница 27: ...alescer filter retainer 4 Remove retainer coalescer filter element and 2 O rings Discard filter elements 5 Install new coalescer filter element s Seat element in center of locating tabs on separator b...

Страница 28: ...GRAPHITE BUSHINGS fFigure 26 Thrust Bearing assembly GG HJ HL Figure 27 Thrust Bearing assembly AS AK AL 5 Insert a brass bar or piece of hardwood in the port open ing and between rotor teeth to keep...

Страница 29: ...sure both are free from dirt and grit Coat outer diameter of seal seat and inner diameter of seal housing bore with refrigeration oil 3 Start seal seat in seal housing bore If force is nec essary pro...

Страница 30: ...ditional end clear ance 0 004 for GG HJ and HL size pumps and 0 005 for AS AK and AL size pumps Pump Distance in on O D End Clearance Size of Bearing Housing in GG 7 16 003 HJ HL 9 16 003 AS AK AL 1 2...

Страница 31: ...a Starving or cavitating increase suction pipe size or reduce length b Strainer partially clogged clean c Air leak in suction piping or along pump shaft d Running too slowly is motor the correct spee...

Страница 32: ...rom the new unit at start up as the base line reference 3 Evaluate vibration readings carefully as the instrument range and function used can vary Findings can be easily misinterpreted 4 Vibration rea...

Страница 33: ...and servicing Continual recording of gauge pressures temperatures and other pertinent information enables the observer and serviceman to be constantly familiar with the operation of the system and to...

Страница 34: ...perheat 4 Excessively high discharge pressure 5 Inadequate refrigerant charge or low receiver level 6 Excessively high or low temperature coolant to the oil cooler 7 Liquid return from system slugging...

Страница 35: ...cer leads by loosening the terminal screws for the transducer to be changed 6 Tape a 3 ft length of pull wire to the leads of the transdu cer to be removed Below 0 PSIG measured in inches of mercury P...

Страница 36: ...TE The total travel on theVOLUMIZER potentiometer is 394 inch SV POSITION POTENTIOMETER REPLACEMENT AND ADJUSTMENT The Slide Valve Position potentiometer is located on the end of the compressor unload...

Страница 37: ...crews 7 Apply DIN connector plug to transmitter 8 Turn on control power Figure 34 TROUBLESHOOTING THE RWB II COMPRESSOR SYMPTOM PROBABLE CAUSES and CORRECTIONS EXCESSIVE NOISE and VIBRATION Main oil i...

Страница 38: ...operating both ways clean Solenoid may be mechanically actuated by inserting a piece of 3 16 rod against armature pin and pushing spool to opposite end If valve works problem is electrical SLIDE STOP...

Страница 39: ...ervice valves are open Filter cartridges may be blocked Check PSID across filters Strainer may be blocked Clean Oil pressure regulator set too low or stuck open Readjust or repair Pump worn out Repair...

Страница 40: ...hieved by increasing or decreasing discharge tube size NOTE DO NOT ATTEMPT TO ADJUST SUPERHEAT ADJUSTMENT STEM ON BOTTOM OF VALVE IN AN EF FORT TO CHANGE THE VALVE S PERFORMANCE THIS ADJUSTMENT IS PRE...

Страница 41: ...t seems to be a total absence of oil cooling you will need to check the action of the valve To check the action you will need to remove the cap flange and disc guide If the hole in the valve plate is...

Страница 42: ...e closed the oil pressure should be 1 1 times suction pressure 15 psi Differential pressure is defined as de fined as discharge pressure minus suction pressure The shutdown should occur if the conditi...

Страница 43: ...RWB II ROTARY SCREW COMPRESSOR UNITS MAINTENANCE S70 200 IOM Page 43 P I DIAGRAM...

Страница 44: ...PRESSURE SAFETY VALVE SP SUCTION PRESSURE STR STRAINER TAH HIGH TEMPERATURE ALARM TAHH HIGH TEMPERATURE SHUTDOWN TAL LOW OIL TEMPERATURE ALARM TALL LOW OIL TEMPERATURE SHUTDOWN TC TEMPERATURE CONTROLL...

Страница 45: ...RWB II ROTARY SCREW COMPRESSOR UNITS MAINTENANCE S70 200 IOM Page 45 P I DIAGRAM LIQUID INJECTION SINGLE PORT P I DIAGRAM LIQUID INJECTION DUAL PORT...

Страница 46: ...RWB II ROTARY SCREW COMPRESSOR UNITS MAINTENANCE S70 200 IOM Page 46 P I DIAGRAM LIQUID INJECTION BOOSTER...

Страница 47: ...erride any rules by the NEC but are to be used in conjunction with the NEC code WIRE SIZING Size supply wires one size larger than required for amperage draw to reduce instantaneous voltage dips cause...

Страница 48: ...the same conduit with 120 volt wires Figure 46 Never run any wires through an electronic control panel that do not relate to the function of the panel Electronic control panels should never be used as...

Страница 49: ...y destroy the electronics If the electronic control panel has a starter built into the same panel be sure to run the higher voltage wires where indicated by the manufacturer EMI from the wires can int...

Страница 50: ...RWB II PLUS ROTARY SCREW COMPRESSOR UNITS FORMS S70 200 IOM Page 50 OPERATING LOG SHEET...

Страница 51: ...ontrol wiring is run in a separate conduit from oil pump and compressor motor wiring __ Confirm no high voltage wiring enters the micro panel at any point __ Check current transformer for correct sizi...

Страница 52: ...and Date _________ Analog Board 1 Serial ______________Rev _____ U13 Analog Ver _________ and Date ______________ Analog Board 2 Serial ______________Rev _____ U13 Analog Ver _________ and Date _____...

Страница 53: ...nment Ambient Temperature at Time of Alignment _______ Oil Separator Temperature at Time of Alignment ________ Motor Coupling Type ___________ Size ___________ Distance Between Coupling Hub Faces ____...

Страница 54: ...___________________ Installing Contractor _____________________________ Address ______________________________________ Service Technician ______________________________ Equipment ID As in Microlog ___...

Страница 55: ...0 200 PSIA Quantum only 1 ALL 913A0110H01 Transducer Pressure 0 500 PSIA Quantum only 1 ALL 913A0110H02 Potentiometer Slide Stop 1 ALL 111Q0041148 Kit Potentiometer Slide Valve 1 ALL 534D0523G02 Valve...

Страница 56: ...systems Q NET means precise control 24 hours a day seven days a week Q NET distributed architecture means faster easier economical installations Q NET delivers increased operating efficiency and lowe...

Отзывы: