background image

RWB II ROTARY SCREW COMPRESSOR UNITS

MAINTENANCE

S70-200 IOM

Page 27

13. Pack lubrication chamber between inner ball bearing

and double-row ball bearing in the thrust-bearing assembly
approximately one-half full of multipurpose grease, NLGI #2.
The thrust-bearing assembly will take the remaining space.
See Figure 22 and 23.

14. Pack double-row ball bearing with multipurpose grease,

NLGI #2.

GG, HJ, HL: Install ball bearing into bearing housing with
shield side toward coupling end of shaft. See Figure 22. In-
stall snap ring into bearing housing to retain ball bearing.
This snap ring has a tapered edge to fit tapered groove in
bearing housing. The tapered edge is located away from ball
bearing.

AS, AK, AL: Install ball bearing into bearing housing. Install
lip seal in bearing housing end cap. The lip should face to-
wards end of shaft. Put bearing spacer collar in lip seal and
install in bearing housing and tighten setscrews securely. See
Figure 23.

15. Insert brass bar or hardwood through port opening be-

tween rotor teeth to keep shaft from turning.

16. Start thrust-bearing assembly into casing. Turn by hand

until tight. This forces rotor against head. Replace and tighten
locknut or shaft.

17. Remove brass bar or hardwood from port opening.

18. Adjust pump end clearance.

BEFORE STARTING PUMP, EN-
SURE THAT ALL DRIVE EQUIP-
MENT GUARDS ARE IN PLACE.

FAILURE TO PROPERLY MOUNT GUARDS MAY RESULT
IN  SERIOUS INJURY OR DEATH.

THRUST BEARING ADJUSTMENT

See Figures 22 and 23.

Loosen two screws in face of thrust-bearing assembly.

If shaft cannot be rotated freely, turn thrust-bearing assem-
bly counterclockwise until shaft can be turned easily.

1. While turning rotor shaft, rotate thrust-bearing assembly
clockwise until noticeable drag occurs. This is zero end
clearance.

2. Mark position of bearing housing with respect to the casing.

3. Rotate thrust-bearing assembly counterclockwise the dis-
tance listed below as measured on outside of bearing
housing.

4. Tighten two setscrews in face of bearing housing after
adjustment is made to secure thrust-bearing assembly
position.

For viscosities above 2500 SSU, add additional end clear-
ance (0.004" for GG, HJ and HL size pumps and 0.005" for
AS, AK and AL size pumps).

Pump

Distance (in.) on O.D.

End Clearance

Size

of Bearing Housing

(in.)

GG

7/16

.003

HJ, HL

9/16

.003

AS, AK, AL

1/2

.

003

INSTALLATION OF CARBON GRAPHITE

BUSHINGS

When installing carbon graphite bushings, extreme care must
be taken to prevent breaking. Carbon graphite is a brittle
material and easily cracked. If cracked, the bushing will quickly
disintegrate. Using a lubricant and adding a chamfer on the
bushing and the mating part will help in installation. The ad-
ditional precautions listed below must be followed for proper
installation:

1. A press must be used for installation.

2. Be certain bushing is started straight.

3. Do not stop pressing operation until bushing is in proper
position. Starting and stopping will result in a cracked bushing.

4. Check bushing for cracks after installation.

DISASSEMBLY

BEFORE OPENING ANY PUMP LIQUID CHAMBER
(PUMPING CHAMBER, RESERVOIR, JACKET ETC.) EN-

SURE:

1. THAT ANY PRESSURE IN CHAM-
BER HAS BEEN COMPLETELY
VENTED THROUGH SUCTION OR

DISCHARGE LINES OR OTHER APPROPRIATE OPEN-
INGS OR CONNECTIONS.

2. THAT THE DRIVING MEANS (MOTOR, TURBINE, EN-
GINE, ETC.) HAS BEEN “LOCKED OUT” OR MADE NON-
OPERATIONAL SO THAT IT CANNOT BE STARTED
WHILE WORK IS BEING DONE ON PUMP.

FAILURE TO FOLLOW ABOVE LISTED PRECAUTIONARY
MEASURES MAY RESULT IN SERIOUS INJURY
  OR
DEATH.

Mark valve and head before disassembly to ensure proper
reassembly.

TROUBLESHOOTING

NOTE: Before making any pump adjustment or opening
the pump liquid chamber in any manner, make sure that:

1. Any pressure in the pumping chamber has been vented
through the suction or discharge lines or other openings pro-
vided for this purpose.

2. The driver has been “locked out” so that it cannot inadvert-
ently be started while work is being done on the pump.

3. The pump has been allowed to cool down to the point that
there is no chance of anyone being burned.

If trouble does develop, one of the first steps toward finding
the difficulty is to 

install a vacuum gauge in the suction port

and a pressure gauge in the discharge port. Readings on
these gauges often will give a clue as to where to start look-
ing for the trouble.

Vacuum Gauge—Suction Port

1. High reading would indicate:

a. Suction line blocked - foot valve stuck, gate valve

closed, strainer plugged.

b. Liquid too viscous to flow through the piping.
c. Lift too high.
d. Line too small.

Содержание RWB II 480

Страница 1: ...ANUAL CONTAINS RIGGING ASSEMBLY START UP AND MAINTENANCE INSTRUCTIONS READ THOROUGHLY BEFORE BEGINNING INSTALLATION FAILURE TO FOLLOW THESE IN STRUCTIONS COULD RESULT IN DAMAGE OR IMPROPER OPERA TION...

Страница 2: ...in death or serious injury Indicates a potentially hazardous situation or practice which if not avoided will result in death or serious injury SAFETY PRECAUTION DEFINITIONS Indicates a potentially ha...

Страница 3: ...r slugging protection that load surges are known and provisions made for control operat ing cycles and defrosting periods are reasonable and that high side condensers are sized within system and compr...

Страница 4: ...r package When installing on the upper floors of buildings extra pre cautions should be taken to prevent normal package vibra tion from being transferred to the building structure It may be necessary...

Страница 5: ...the shaft by tightening the clamp screws Torque is transmitted from the motor through the elas tomeric gear which floats freely between the hubs Install as follows 1 Slide one hub onto each shaft as...

Страница 6: ...HE SAME OR DER Mark the adjoining bolt holes of each part the two hubs the two disc packs and the center spool so they are put back together in the same position 2 Mount the coupling hubs on their res...

Страница 7: ...arings it is necessary to secure the two cou pling hubs with a bolt to prevent them from drifting apart when rotating 2 Rotate both coupling hubs several revolutions until they seek their normal axial...

Страница 8: ...salignment is within specified tolerance 10 Check parallel lateral misalignment by positioning dial indicator so the stem is in contact with the rim of the com pressor hub at 3 o clock as shown in Fig...

Страница 9: ...turers or types Mixing of oils may cause excessive oil foaming nuisance oil level cutouts oil pressure loss gas or oil leakage and catastrophic compressor failure Use of oils other than Frick Oil in F...

Страница 10: ...refrigerant to boil and vaporize The vapor rises in the return line The density of the refrigerant liquid vapor mixture in the return line is considerably less than the density of the liquid in the s...

Страница 11: ...upply of high pres sure liquid refrigerant be provided to the injection system at all times Two items of EXTREME IMPORTANCE are the design of the receiver liquid injection supply and the size of the l...

Страница 12: ...r volume quanti ty of refrigerant required for 5 minutes of liquid injection oil cooling are given in the following table LIQUID LINE SIZE and RECEIVER VOLUME LINE SIZE POUND LIQUID RWB II SCH 80 OD P...

Страница 13: ...2 HIGH PRESSURE LIQUID INTERMEDIATE PRESSURE GAS TO COMPRESSOR SUCTION STR VCK SUBCOOLED HIGH PRESSURE LIQUID TO EVAPORATOR ECONOMIZER COOLER WIRING ECON2 HV 2 HIGH PRESSURE LIQUID INTERMEDIATE PRESS...

Страница 14: ...rter Wiring Diagram Figure 15 All Frick motor starter pack ages have the timer relay as standard Motor starter and interlock wiring requirements are shown in the Starter Wiring Diagram All of the equi...

Страница 15: ...5 300 5 300 5 100 5 50 5 250 800 5 800 5 500 5 400 5 300 5 100 5 50 5 300 1000 5 1000 5 600 5 500 5 400 5 100 5 50 5 350 1000 5 800 5 500 5 500 5 100 5 100 5 400 800 5 600 5 500 5 200 5 100 5 450 1000...

Страница 16: ...pressure for increased seal life 10 Oil injected into the rotors to maintain good volumetric and adiabatic efficiency even at very high compression ra tios 11 Shaft rotation clockwise facing compresso...

Страница 17: ...n S90 010 O COLD START VALVE DEMAND PUMP OIL SYSTEM This system is designed to provide adequate compressor lubrication for some high stage applications that operate with low differential pressure acro...

Страница 18: ...inder port SC 1 and enters the unload side of the cylinder Simultaneously oil contained in the load side of the cylinder flows out com pressor port SC 2 through valve ports B andT to compressor closed...

Страница 19: ...NJECTION The dual port liquid injection system is designed to obtain the most efficient compressor performance at high and low compression ratios by permitting injection of liquid refriger ant into on...

Страница 20: ...leakage into the system during shut down However on high stage or booster systems with check valve HV 2 can remain open HV 2 also should be closed on systems that utilize autocycle to restart the comp...

Страница 21: ...gnment and adjust as necessary NORMAL START UP PROCEDURE 1 Confirm system conditions permit starting the compressor 2 Press the RUN key 3 Allow the compressor to start up and stabilize Press the AUTO...

Страница 22: ...cable Re move tags 3 Close disconnect switches for compressor motor and oil pump starters 4 Turn off oil heater circuit breaker 5 Perform checkpoints on prestart check list then start unit GENERAL MAI...

Страница 23: ...disconnect switches for compressor and oil pump motor starters If dual oil filters are installed open the outlet then inlet ser vice valves of the standby filter Open inlet service valve slowly to pr...

Страница 24: ...er filter element and 2 O rings Discard filter elements 5 Install new coalescer filter element s Seat element in center of locating tabs on separator bulk head 6 Replace coalescer filter retainer and...

Страница 25: ...RBON GRAPHITE BUSHINGS fFigure 22 Thrust Bearing assembly GG HJ HL Figure 23 Thrust Bearing assembly AS AK AL 5 Insert a brass bar or piece of hardwood in the port open ing and between rotor teeth to...

Страница 26: ...ousing bore Make sure both are free from dirt and grit Coat outer diameter of seal seat and inner diameter of seal housing bore with refrigera tion oil 3 Start seal seat in seal housing bore If force...

Страница 27: ...ize pumps and 0 005 for AS AK and AL size pumps Pump Distance in on O D End Clearance Size of Bearing Housing in GG 7 16 003 HJ HL 9 16 003 AS AK AL 1 2 003 INSTALLATION OF CARBON GRAPHITE BUSHINGS Wh...

Страница 28: ...ck alignment d May have a bent shaft or rotor tooth Straighten or replace e May be a foreign object trying to get into the pump through the suction port 4 Pump not up to capacity a Starving or cavitat...

Страница 29: ...NTENANCE PROGRAM In order to obtain maximum compressor unit performance and ensure reliable operation a regular maintenance pro gram should be followed The compressor unit should be checked daily for...

Страница 30: ...se responsible for its maintenance and servicing Continual recording of gauge pressures tempera tures and other pertinent information enables the observer and serviceman to be constantly familiar with...

Страница 31: ...ssively high suction superheat 4 Excessively high discharge pressure 5 Inadequate refrigerant charge or low receiver level 6 Excessively high or low temperature coolant to the oil cooler 7 Liquid retu...

Страница 32: ...ler 5 Disconnect transducer leads by loosening the terminal screws for the transducer to be changed 6 Tape a 3 ft length of pull wire to the leads of the transdu cer to be removed Below 0 PSIG measure...

Страница 33: ...next step Adjustment of POT 2 and POT 1 are interactive and POT 1 may require adjustment to allow POT 2 to come into range Now completely increase the slide stop The display at this time should indica...

Страница 34: ...front of the sepa rator near the bottom center See Figure 30 The linear transmitter with hermetic enclosure is based on the capacitive measuring principle It features removable elec tronics from the...

Страница 35: ...Frick Factor or Frick for assistance NOTE Troubleshooting the compressor is limited to identifying the probable cause If a mechanical problem is suspected contact the Frick Service Department DO NOT A...

Страница 36: ...OAD Dirt inside solenoid valve preventing valve from operating both ways clean Solenoid may be mechanically actuated by inserting a piece of 3 16 rod against armature pin and pushing spool to opposite...

Страница 37: ...roblem Thermal valve power head lost charge replace Liquid strainer blocked clean Liquid solenoid coil failed replace Excessive load Thermovalve undersized Reduce load or install larger thermovalve LO...

Страница 38: ...RENTIAL ALARM OIL PRESSURE FLUCTUATES Liquid injection overfeeding or refrigerant flood back from system Make necessary adjustments or corrections NOISE and VIBRATION Pump strainer blocked Clean Liqui...

Страница 39: ...achieved by increasing or decreasing discharge tube size NOTE DO NOT ATTEMPT TO ADJUST SUPERHEAT ADJUSTMENT STEM ON BOTTOM OF VALVE IN AN EF FORTTO CHANGETHEVALVE S PERFORMANCE THIS ADJUSTMENT IS PRE...

Страница 40: ...seems to be a total ab sence of oil cooling you will need to check the action of the valve To check the action you will need to remove the cap flange and disc guide If the hole in the valve plate is...

Страница 41: ...closed the oil pressure should be 1 1 times suction pressure 15 psi Differential pressure is defined as de fined as discharge pressure minus suction pressure The shutdown should occur if the conditio...

Страница 42: ...RWB II ROTARY SCREW COMPRESSOR UNITS MAINTENANCE S70 200 IOM Page 42 P I DIAGRAM...

Страница 43: ...RESSURE SAFETY VALVE SP SUCTION PRESSURE STR STRAINER TAH HIGH TEMPERATURE ALARM TAHH HIGH TEMPERATURE SHUTDOWN TAL LOW OIL TEMPERATURE ALARM TALL LOW OIL TEMPERATURE SHUTDOWN TC TEMPERATURE CONTROLLE...

Страница 44: ...RWB II ROTARY SCREW COMPRESSOR UNITS MAINTENANCE S70 200 IOM Page 44 P I DIAGRAM LIQUID INJECTION SINGLE PORT P I DIAGRAM LIQUID INJECTION DUAL PORT...

Страница 45: ...RWB II ROTARY SCREW COMPRESSOR UNITS MAINTENANCE S70 200 IOM Page 45 P I DIAGRAM LIQUID INJECTION BOOSTER...

Страница 46: ...be used in conjunction with the NEC code WIRE SIZING Size supply wires one size larger than required for am perage draw to reduce instantaneous voltage dips caused by large loads such as heaters and c...

Страница 47: ...the same conduit with 120 volt wires Fig ure 42 Never run any wires through an electronic control panel that do not relate to the function of the panel Electronic control panels should never be used...

Страница 48: ...estroy the electronics If the electronic control panel has a starter built into the same panel be sure to run the higher voltage wires where indicated by the manufacturer EMI from the wires can in ter...

Страница 49: ...RWB II PLUS ROTARY SCREW COMPRESSOR UNITS FORMS S70 200 IOM Page 49 OPERATING LOG SHEET...

Страница 50: ...ontrol wiring is run in a separate conduit from oil pump and compressor motor wiring __ Confirm no high voltage wiring enters the micro panel at any point __ Check current transformer for correct sizi...

Страница 51: ...rd 1 Serial _____________ Rev _____ U13 Analog Ver _________ and Date ______________ Analog Board 2 Serial _____________ Rev _____ U13 Analog Ver _________ and Date ______________ Compressor Motor Inf...

Страница 52: ...nment Ambient Temperature at Time of Alignment _______ Oil Separator Temperature at Time of Alignment ________ Motor Coupling Type ___________ Size ___________ Distance Between Coupling Hub Faces ____...

Страница 53: ...____________________ Installing Contractor _____________________________ Address ______________________________________ Service Technician ______________________________ Equipment ID As in Microlog __...

Страница 54: ...333Q0001326 Relay 3PDT 115V 1 ALL 333Q0000206 UNIT Temperature Probe TE 1 4 1 ALL 640A0035H01 Transducer Pressure 0 200 PSIA PE 4 Quantum only 1 ALL 111Q0280887 Transducer Pressure 0 500 PSIA PE 1 3 Q...

Страница 55: ...RWB II ROTARY SCREW COMPRESSOR UNITS NOTES S70 200 IOM Page 55...

Страница 56: ...Q NET can be applied to both new and existing systems Q NET means precise control 24 hours a day seven days a week Q NET distributed architecture means faster easier economical installations Q NET del...

Отзывы: