 Installation & Disassembly

4. Installation

4.1 Installation of unit

• 

Ensure that the unit is installed firmly on a level 

and horizontal surface.

• 

Prior to connecting the unit to the duct system, 

all openings must be closed. Then connect the 

ducts to the unit. See the air direction symbols 

at the connection points.

• 

Avoid connecting bends directly to the unit's 

connection points. The duct system should be 

connected in such a manner that vibrations from 

the unit cannot be transferred to the duct system 

and the surroundings.

• 

Installation should be carried out in such a 

manner that the weight of the duct system and 

its components does not overload the unit.

• 

During installation, ensure that there is sufficient 

room to service the unit in front of the unit.

• 

If the unit is installed against a wall, there is 

a risk that vibrations will be transferred to the 

adjacent room and may cause noise problems. 

The recommended distance between the unit 

and walls is 400 mm. If this is not possible, 

install the unit against a wall with a room that is 

not sensitive to noise. Where possible, insulate 

walls and floors using heavy insulation to prevent 

noise problems.

• 

Ensure that supply and exhaust air ducts are 

suitably insulated to avoid condensation.

Frequency band

63

125

250

500

1000

2000

4000

8000

Total

Total sound level

68

To environment

46

36

35

32

30

29

23

15

36 dB(A)

Atmospheric air

50

47

48

48

44

35

19

7

48 dB(A)

Supply air

60

56

58

61

62

62

57

54

67 dB(A)

Frequency band

63

125

250

500

1000

2000

4000

8000

Total

Total sound level

64

To environment

52

38

37

30

27

22

16

5

34 dB(A)

Atmospheric air

56

49

50

46

41

28

12

-3

47 dB(A)

Supply air

66

59

61

59

58

55

50

43

62 dB(A)

Sound data FRX 

110

S

Sound data FRX 

200

S

• 

Prior to connecting the unit, ensure that voltage 

readings correspond to the unit’s specification. 

Incoming cables are provided with suitable switches 

that comply with applicable requirements for 

electrical installations and are connected to the 

terminal in the unit.

• 

Install the unit’s temperature sensor GT1 for 

supply air. This should be mounted as far away 

from the unit as possible, but before the first 

branch.

5. Operation/Control & Rules

• 

See separate manual

6. Annual maintenance

The following points should be reviewed at least once 

per year. Prior to maintenance work commencing, 

ensure that the unit is free from electricity.

• 

Turn off the unit with the control panel (User meny)

• 

Wait until the fans have stopped (approx. 3 min) 

and heating element have cooled down.

• 

Unplug the unit.

Содержание FRX 110S

Страница 1: ...www fresh se FRX 110S 200S INSTALLATION DISASSEMBLY Swedish manufactured heat recovery units E kodesign 20 1 6 ErP 2016...

Страница 2: ...ntenance 6 06 Disassembly and recycling 7 08 Warranty All equipment manufactured by us is trialled and tested before leaving the factory and is sent in good condition We provide a 2 year warranty from...

Страница 3: ...st not be used for any other purpose Do not use the unit in explosive environments or in connection with combustible aggressive and easily flammable gases Never use the unit without a filter Prior to...

Страница 4: ...m Bag filter On the supply air class F7 filters are used and on the extract air a class M5 bag filter is used Dimensions FRX 110S mm Dimensions FRX 200S mm 3 Technical data Connection options The pict...

Страница 5: ...ical data Capacity The diagram shows the maximum external pressure to comply with the Ecodesign requirement this applies to electric heaters when using water heaters or coolers assume this has a press...

Страница 6: ...noise problems Ensure that supply and exhaust air ducts are suitably insulated to avoid condensation Frequency band 63 125 250 500 1000 2000 4000 8000 Total Total sound level 68 To environment 46 36 3...

Страница 7: ...emoved by disconnecting the quick connector and then removing the battery If the manual overheating protection fails the unit must be disconnected from the mains electricity supply Wait until the heat...

Страница 8: ...fans from mounting plates wrench Section Material Handling Panels and doors Plate AZ185 and rock wool insulation Recycling after separation Metal parts Plate AZ185 steel galvanized steel powder coate...

Отзывы: