![Freedom 458 Series COMBI Скачать руководство пользователя страница 7](http://html1.mh-extra.com/html/freedom/458-series-combi/458-series-combi_owners-manual_2329797007.webp)
3
Introduction
When the external AC power source is disconnected, the
transfer switch allows automatic switching back to the in-
verter.
Automatic 3-Stage Battery Charging
The Freedom Inverter/Charger is designed to rapidly and
optimally charge wet, gel, or Absorbed Glass Mat cell deep-
cycle batteries. The battery charger automatically proceeds
through the bulk, acceptance, and float charging stages,
resulting in an efficient, complete charge.
Additionally, you can use Remote Control Panel or the LINK
instrument to manually equalize wet cell batteries. Equalizing
restores your wet cell batteries to their optimal, operating
condition.
Unit Protection
Fast-acting electronic circuits protect your Freedom Inverter/
Charger from overloads and short circuits. Your unit also has
low and high battery voltage cutoff, and automatic shutdown
if it gets too hot.
Neutral Bonding
The Freedom Inverter/Charger automatically bonds the
internal AC output neutral (white) to the internal AC output
ground (green), when the unit is off or in the inverter mode.
No additional wiring is needed for this process.
When incoming AC power is applied and the transfer switch
engages, and the internal neutral-to-ground bond is automati-
cally lifted.
This insures safety in all conditions and meets the National
Electrical Code (NEC) requirements.
Power Sharing
When the unit is connected to an external AC source, the
battery charger and transfer functions are engaged. A unique
Power Sharing feature automatically reduces the AC power
consumption of the battery charger. This allows the necessary