Installation
30
Test the inverter function
1. With no loads connected to the output of the inverter, turn
the inverter on by pressing the INVERT button for three
seconds. The INVERT LED should be steady.
If you are using a remote control, turn on the inverter with
the button on the Remote Control Panel or LINK instru-
ment.
The Freedom unit will produce a slight tick-tick sound. If
using a Remote Control Panel or LINK instrument the
INVERT/CHARGE LEDs will illuminate and the voltage
indicator will display the battery voltage. The DC Amps
LED will not be lit because the unit is in the idle mode.
2. Add a load of 7 watts or more to the output of the inverter.
A 40-watt incandescent light bulb will work fine. The DC
Amps LEDs on the remote control will indicate the DC
draw from the battery through the inverter.
3. Leave the load connected and turn off the inverter by:
•
Pressing INVERT on the unit again
•
If you are using a remote control, turning off the
INVERT mode on the Remote Control Panel or LINK
instrument
Test the transfer function
1. Check that the unit is off, i.e., the INVERT and CHARGE
LEDs are not illuminated.
If you are using a remote control, check that both the
INVERT and CHARGE LEDs are off.
2. Apply shore power.
3. There will be an 3-second delay. Then the unit should
transfer shore power and power the load. If this does not
happen, do not proceed.
Check for back-feed when the LOW BATTERY and OVER-
LOAD/OVERTEMP LEDs both blink rapidly. If you are
using a remote control, check the panel for a back-feed
indication; the panel will show an overload condition.