Pump Sensor (Code C1 and C2)
The program for the pump pressure sensor(s) is self calibrating. There are no
adjustments that can be made to the sensors. When the calibration program is activated
it looks at the signal from the sensor(s), assumes this to be 0 PSI and sets the program.
Note:
If there is pressure in the plumbing where the sensor is mounted this
will cause the program to be calibrated to a false 0. To avoid this:
Drain the pump and plumbing to ensure there is no residual pressure before
running the calibration procedure.
1. Apply power to the display module.
2. Enter the calibration password. (See Calibration Programs.)
3. Scroll to code
C1
or
C2, use
the
INC
or
DEC
button.
4. Press the
MENU
button,
D.Sensor or I.Sensor Set P=0?
flashes.
5. Press the
MENU
button again to set
Press=0
.
6. Press and hold the
SILENCE
button for 3 seconds to save the setting
into memory.
7. Press the
SILENCE
button when the program (C) code is flashing to exit
calibration. Press the
MENU
button to enter the next program. Press the
INC
or
DEC
buttons to scroll through program codes.