background image

The foot valve strainer can be installed onto the bottom of 
a 34’ long tail pipe, rather than the bottom of the packer, 
to prevent over pumping of a low yield well. Soak the 
packer assembly in warm water for 1 hour to make the 
leathers soft and pliable. Lower or push the packer 
assembly into the well on 1¼” suction piping. It should be 
set at least 3’ below the lowest dynamic water level if you 
are not using a tail pipe below the packer.The foot valve 
strainer should be no closer than 3’ from the bottom of 
the well. 

WELL ADAPTER INSTALLATION
Packer systems require a well adapter (ordered 
separately) at the top of the well.  The well adapter 
makes the transition from the vertical suction pipe and 
well casing, to the horizontal suction and drive water 
connections. The 1¼” suction pipe from the well must be 
terminated with a 1¼” male NPT connection. Attach the 
well adapter to this 1¼” male NPT fitting. Make sure the 
OD of the well casing is smooth and clean.  With the 
gland bolts loosened, the rubber seal ring should slide 
over the 2” well casing.  With the well adapter in place, 
tighten the 3 gland bolts uniformly to compress the seal 
ring to the well casing OD. The Convertible VersaJet 
pump can be attached directly to the well adapter using 
the two 3/8”-16 x 1” bolts with flat washers supplied with 
the well adapter kit, and the rubber gasket provided with 
the suction flange kit. The pump may be separated from 
the well adapter with horizontal offset suction and drive 
water piping.
(see “HORIZONTAL OFFSET PIPING” above).
Priming will be easier if you fill the pipes with water 
before attaching the pump. Make sure that all piping 
slopes upward towards the pump and that no point is 
above the pump suction. Connect the suction and drive 
water pipes to the threaded connections on the pump 
suction flange. Always double clamp barbed connectors.
Go to “DEEP WELL DISCHARGE PIPING” below

DEEP WELL DISCHARGE PIPING (FIGURE 5)

All deep well jet pumps require back pressure to properly 
operate the jet assembly. To insure that you have the 
required back pressure or drive water pressure, you must 
provide a pressure control valve in the discharge line as 
close to the pump as possible. Failure to install and adjust 
a pressure control valve will result in loss of prime during 
peak usage situations. Franklin Electric recommends the 
use of a 1” control valve (Franklin Electric control valve 
P/N 91980359) installed directly in the pump discharge 
that has an alternate ¼” NPT pressure switch connection. 
This alternate pressure switch connection allows the 
switch to read the pressure on the outbound side of the 
valve, rather than inside the pump case. Install the control 
valve in the pump discharge.  Remove the plastic tubing 
from the quick connect fittings supplied on the pump. 
Remove the quick connect fitting from the pump case and 
move it to the ¼” NPT connection on the control valve.  
Plug the ¼” NPT pump case hole with the plug provided 
in the control valve kit.  Install the new plastic hose 
between the pressure switch and the control valve (cut it 
to the proper length if necessary).  Make sure you push 
the plastic hose completely into the quick connect fittings 
to insure a good water seal.  See “ADJUSTING THE 
CONTROL VALVE” below for adjustment procedures of 
this valve.
The arrangement shown in 

FIGURE 5 is typical and 

suitable for any pipe material, but all components shown 
are not required for proper use. The gate valves save 
draining the entire system when servicing the pump or 
pressure tank. There should be unions or other breakable 
pipe connections close to the pump to allow for easy 
accessibility when servicing.  If the side discharge ports 
in the pump case are used for discharge plumbing then 
the top discharge port can be used for priming. If the top 
port is used for discharge plumbing, priming can be done 
through the top of the control valve installed in this port.

PRIMING THE PUMP

SHALLOW WELL PUMPS 
Priming the pump means filling the pump and suction 
piping with water.  Priming is completed when you start 
the pump, and all the air is removed from the piping 
system, but before you energize the pump you must 
manually fill the pump and suction piping with water.  If 
you used one of the side discharge connections on the 
pump, you can easily fill the pump and piping with water 
through the 1” top port.  If you used the top port for 
discharge plumbing, you may need to provide a priming 
tee for filling with water.  Please also remove the ¼” pipe 
plug on top of the shallow well injector for venting 
purposes while filling.  Once this ¼” vent hole produces 
only water, it should be plugged, and continue filling the 
pump with water until full.  All horizontal offset piping 
should slope up from the well to the pump to ensue that it 
is filled with water.  Plug the filling hole and open slightly 
a faucet close to the pump.  Do not open it too much, 
which will allow too much water to escape when you 

Pressure Switch

Union

Service Pipe

Gate Valve

Pressure Tank

Check Valve

Pump & Motor

Assembly

Priming Port

Pressure Control Valve

Alternate Pressure Switch

Tubing Connection

Содержание VersaJet Series

Страница 1: ...otor or tank WARNING Hazardous voltage Can shock burn or cause death Ground pump before connecting to power supply Disconnect power before working on pump motor or tank WARNING CAUTION CAUTION WARNING...

Страница 2: ...to make sure there is no damage or broken parts that may have occurred in shipping If damage is evident report this immediately to your shipping carrier and dealer The shipping carrier assumes full r...

Страница 3: ...y have to be increased in diameter to reduce pressure loss The pressure loss in a system increases 1 As the flow rate increases 2 As the piping size decreases Consult included friction loss tables App...

Страница 4: ...pumping of a low yield well Lower the injector assembly into the well It should be set at least 3 below the lowest dynamic water level if you are not using a tail pipe below the injector The foot val...

Страница 5: ...e that has an alternate NPT pressure switch connection This alternate pressure switch connection allows the switch to read the pressure on the outbound side of the valve rather than inside the pump ca...

Страница 6: ...mply with National Electric Code NEC or Canadian Electric Code CEC and all applicable local codes All dual voltage units come factory preset for 230 volts Figure 6 Disconnect power at electrical panel...

Страница 7: ...filling the pump case completely full of water as damage may occur to the seal and other internal components if run dry PRESSURE SWITCH ADJUSTMENT EXAMPLE ASSUMES PRESSURE SWITCH IS INITIALLY SET WITH...

Страница 8: ...g bolted to front of the pump If you need to service the impeller motor or seal use the following procedure going as far as needed to correct the problem 1 Disconnect the power to the unit 2 Disconnec...

Страница 9: ...NT in this manual Increase size or clean out suction piping to pump Clear nozzle or impeller of clogging debris See PUMP DISASSEMBLY in manual Convert a shallow well application into a deep well arran...

Страница 10: ...4 305374907 305374905 2 Studs B 305465901 3 Bracket 4 O Ring F 305465902 5 Fasteners C 305465903 6 Pressure Switch D 305465904 7 Pressure Hose Fitting 8 Pressure Hose Tubing 9 Plugs E 305465905 10 Mec...

Страница 11: ...applicable codes ordinances and good trade practices 3 Product was not installed by a Franklin Certified Contractor or Franklin Key Dealer or 4 Product was damaged as a result of negligence abuse acc...

Страница 12: ...106580101 Rev 2 07 13 9255 Coverdale Road Fort Wayne IN 46809 Tel 260 824 2900 Fax 260 824 2909 www franklinwater com...

Отзывы: