MOTOR RUN-TIME METRICS
VOLTAGE MODE
In Voltage sensor mode, the Run Time Threshold is 3% of the programmed voltage range. Above this threshold the motor is
considered running, below it, the motor is considered off.
On the Action Page, the Preset Run Time (hrs.) function allows the user to preset the Optimizer3 counter to match the mechanical
Motor Run Hours counter on the breaker.
Monitor Run Metrics, shown on the Sensors Page:
1. Voltage = Present scaled input measurement.
2. Accumulated Run Time (hrs.) = Totalized running time for all starts (logged in database after each Run).
3. Average Run Time (sec.) = Running time for the last 10 runs averaged (logged in database after each Run).
4. Average Time Between Runs (hrs.) = “OFF Times”, measured from the end of one run to the beginning of the next, for the
last 10 runs averaged (logged in database after each Run).
5. Run Frequency (avg. runs per day) = 30-day average number of starts (logged in database after each Run).
Monitor Continuous Voltage, shown on the Sensors Page:
1. Voltage = Same as above.
2. Today’s Average = Average voltage since the previous MIDNIGHT (logged in database once a day).
3. Today’s Minimum = Lowest measured voltage since the previous MIDNIGHT (logged in database once a day – with date/time
stamp when they occurred).
4. Today’s Maximum = Highest measured voltage since the previous MIDNIGHT (logged in database once a day – with date/
time stamp when they occurred).
5. Sample Count = Number of voltage samples since the previous MIDNIGHT.
CURRENT MODE
In Current sensor mode, the Run Time Threshold is 3% of the programmed current range. Above this threshold the motor is
considered running, below it, the motor is considered off.
On the Action Page, the Preset Run Time (hrs.) function allows the user to preset the Optimizer3 counter to match the mechanical
Motor Run Hours counter on the breaker.
Current is sampled at a high rate but averaged in roughly 1-second time buckets. These 1-second buckets are used in all
calculations.
Monitor Run Metrics, shown on the Sensors Page:
1. Current (A) = Present scaled input measurement of the last 1-second time bucket.