Table 4
– Gas Insulated Line Fill Weight
Compartment Gas Volume (ft
3
), Weight (lbs), and Length (ft)
Circuit 1
Phase
A
B
C
Zone 101
Zone
Volume
365.25
352.42
339.59
Zone Weight
701.79
677.14
652.49
Zone Length
341.67
329.67
317.67
Circuit 1
Phase
A
B
C
Zone 102
Zone
Volume
365.25
378.07
390.90
Zone Weight
701.79
726.44
751.09
Zone Length
341.67
353.67
365.67
Figure 30
– Optimizer3 Settings for Gas Insulated Lines
SF
6
GAS SYSTEM SPECIFICATIONS
Compressed Gas Insulated
Transmission Bus
Fill Pressure is 55 PSIG, Warning Alarm is 50 PSIG, and Danger Alarm is 43.5 PSIG.
The Fill Weight is the average of all six compartments since they are all slightly different.
Fill Weight = (701.79 + 677.14 + 652.49 + 701.79 + 726.44 + 751.09) ÷ 6 = (4211 ÷ 6) = 702.0 lbs
Nominal Gas Density
Nominal Gas Pressure at 20° C
1
ST
ALARM Gas Pressure at 20° C
2
ND
ALARM Gas Pressure at 20° C
1.92 lb/ft
3
55.0 psig
50.0 psig
43.5 psig