27
Therefore, in the case of three SF₆ pressure or density sensors used on three separate poles, the Total Weight of SF₆ Gas given on
the nameplate must be divided by three. 360 ÷ 3 = 120 lbs. See Figure 29.
Figure 28
– Fill Weight for IPO Breakers
Terminal to Terminal Circuit Breaker Open.................1300 KV
Total weight of breaker w/ gas............29707 lbs.............13475kg
Total weight of SF6 gas ............................ 360 lbs.............13475kg
Normal SF6 gas pressure at 20° C........ 80.0 PSIG.........0.55 MPaG
Alarm SF6 gas pressure at 20° C...........75.5 PSIG........ 0.52 MPaG
Minimum SF6 gas pressure at 20° C.....72.5 PSIG........0.50 MPaG
SF₆ GIL (GAS INSULATED TRANSMISSION LINE) APPLICATION
Optimizer3 is a useful SF₆ gas monitoring system for GIL. There are 8 sensor inputs which all may be used for SF₆ density or
pressure measurement, using analog Temperature-Compensated sensors.
Figure 29
– Gas Insulated Line (GIL)
In Figure 29, a three-pole GIL was monitored. Each pole was made up of two SF₆ gas zones. An SF₆ gas density sensor is installed on
each riser, making up a total of 6 gas zones. The GIL manufacturer supplies the following information: