15
SPECIFICATIONS
Table 2
– Specifications.
Specifications
Size: 11.125W X 5.625H X 2.625D, Inches Nominal, Shipping Weight: 6 Lbs.
Input Power: 110-250 VDC or 90-264 VAC (50/60 Hz). Power consumption is 60 VA max.
Recommended External Fuse Rating: 3.15 Amp Slow-Blow
Operating Temperature: -40˚C to +65˚C
Alarm Relay Contact: One form C, 1 amp at 30 VDC, 2 amps at 250 VAC rating.
Analog Sensor Input Accuracy: ±1% max, ±0.5% typical
Pluggable Connector Wire Size: 12 to 24 AWG
Data Storage- Non-volatile memory with capacity of:
10,000 Application Events
10,000 Alarm Events
5000 Circuit Breaker Monitoring Events
5000 SF₆ Gas Parameter data points
750 Daily Summary logs
5000 3 phase Line Current (measured and scaled from bushing CT secondaries)
1000 Line Voltage Measurements (as measured at power input)
5000 Ambient Temperature Measurements (as measured at the monitor)
Test Standards:
IEEE C37.10
CISPR 16-2-1 (Conducted Emissions)
CISPR 16-2-3 (Radiated Emissions)
IEC61000-4-2 (ESD)
IEC61000-4-3 (Radiated RF)
IEC61000-4-4 (EFT)
IEC61000-4-5 (Surge)
IEC61000-4-6 (Conducted RF)
IEC 61000-4-11 (Voltage Dips & Interrupts)
IEC 61000-4-12 (Damped oscillatory wave- Power Ports)
FCC Part 15, Subpart B; ICES-003 (Emissions)