7
3. Mount and Install the Control Panel
Unpack the control panel and place the panel on the upper base module discharge header such that the mounting studs on the upper header can pass
through the holes located on the bottom of the control panel . Using the hardware found in the accessory kit (remove Hardware Bag #2), place washer,
then lock washer and nut on each stud and tighten each nut down firmly .
Each pump comes equipped with a pre wired electrical whip . At the end of the electrical whip is a quick connection fitting which will be attached to a mating
piece located on the left side edge of the panel . The connections and the electrical whips are marked with the pump they are associated with . For each pump
whip, open the dust cover protecting the panel side connection, plug in the whip and close the cam lock on the panel side connection (see Figure 3) .
Finally, connect the pressure transducer cable (extends from the panel and has a package fitting at the end) to the transducer via the snap fitting .
4. Connect Site Power to the Control Panel
The control panel contains two (2) hot leads, L1 & L2 for 230VAC, 60 Hz electric supply . Failure to properly wire the
unit and changing the wiring of the unit can result in serious bodily harm, death and major equipment damage .
The electrical system consists of the control panel, pumps, and pressure transducer . The control panel consists of an HMI, PLC, and electrical
components, such as fuse protections, panel and motor disconnects, and system wiring .
The control panel must be provided a 230VAC, 1P dedicated circuit feed . Any circuit that is shared for other systems could cause potential issues with
the power of this system . This wiring should be completed by a certified electrician .
Bring 230VAC wiring and a ground wire to the control panel . Pass through the appropriate hole on the right side of the panel . L1 and L2 are terminated
directly to the disconnect switch shown in Figure 4 and G is connected to the grounding stud on the back panel .
Figure 3
Figure 4
L1
Site power connections to
remote disconnect switch
To grounding stud
on back panel
L2
G
WARNING