5. Site Piping to the Package

Do not over tighten piping connections on the fittings used to connect the site plumbing to each header as this could 
damage the equipment and/or headers .

As mentioned earlier, the site water (suction and discharge) can be connected to either end of the suction and discharge manifolds .
User installed isolation valves are required near the inlet and outlet to the packaged assembly . This will allow the user to isolate the entire package 
from the site plumbing network which can be helpful in simulating the different site demand loads during start up and also to prevent draining of the 
discharge piping during times of major maintenance to the unit .
The pressure tank supplied on the package is sized to allow adequate pressure sensing for smooth pump operation . It is not meant to be a buffer tank 
and in cases where sudden large demand swings occur, an external pressure tank may be needed to minimize any drops in pressure on the discharge 
side of the pump package .
Finally, install an appropriately sized pressure relief valve sized discharge piping from the pressure relief valve to an appropriate drain with the pipe 
sized for the max pump outlet at the relief valve discharge pressure . A 1-1/4” NPT female connection is provided on Discharge Header End Cap for 
installing the relief valve . If the relief valve is placed in a different area in the system, this connection will need to be closed using the 1-1/4” plug 
provided in the Accessory Kit .

UNIT OPERATION

1. How the System Works

The pump system is controlled by a pressure control loop . When the measured pressure is below the user setpoint, the control panel will enable pump 
operations based on set up selections made by the user in the control program .

2. Turning the Unit On

Once site power has been provided to the control panel and those feeds are live, there will be energized electrical 
lines in the control panel up to the remote disconnect terminals even when the panel’s remote disconnect switch is 
off . Always de-energize the site power feeding the control panel when opening the panel otherwise an electrical 
shock hazard will still exist which can cause serious injury, death and major property damage .

Prior to turning the unit on, the following should be checked .

a . The electrical incoming voltage should be verified that it meets the electrical requirements and that an adequate ground connection exists .
b . The overall system should be inspected to verify no damage was found during shipment or installation .
c . After plumbing the system, pressurize the booster system Suction Header with site water . To remove any trapped air in the package, start with  
  the pump isolation valves closed on all but one pump . Air can be vented by loosening the 1-1/4” plug located on the Discharge Header End Cap  
  or, if a relief valve is installed there, by lifting the relief valve poppet . After venting, close an isolation valve on the first pump, open both    
  isolation valves on the next pump to be vented, and repeat the air venting process . Continue venting air in this manner until all pumps have  
  been vented . After the air has been removed from all pumps, tighten the plug . 
d . If there are any water leaks, isolate the location and tighten the connections . If the leaks are at the threaded connections in the pump piping  
  circuits, tighten down each fitting in the other pump piping circuits by an equal amount to ensure that the suction and discharge manifolds are  
  maintained at a uniform distance . 
e . Engage the fused disconnections for each pump, close the control panel door and turn the remote disconnect to the 1 (or ON) position .

3. System Control

When the control panel is powered up by turning the electrical disconnect on, the PLC panel will turn on and display the SYSTEM screen . The screen 
name is shown in the upper right corner of this screen .
An overall On/Off selection switch is shown on the right side of the SYSTEM screen as shown in Figure 5 . Touching the green light will activate the 
system and allow it to operate while touching the red light will stop the system operation . The light associated with the current selection will be 
illuminated to show which state the system is currently in .

CAUTION

WARNING

Содержание 1IL-2301414-T1S

Страница 1: ...INLINE 1100 SPECPAK Owner s Manual Meets the Requirements of NSF ANSI 372 ...

Страница 2: ......

Страница 3: ...3 TABLEOFCONTENTS Specifications 4 Installing the Unit 5 Unit Operation 8 Troubleshooting 11 Replacement Parts 16 Wiring Diagram 18 ...

Страница 4: ...80 60 230 V 26 5 Duplex with CP and pressure transducer 574705902 2IL 23033 G1T 32 1 8 44 3 16 14 1 2 64 1 2 3 Groove 4 8 Gal 13 41 8 25 2 80 60 230 V 26 5 Triplex with CP and pressure transducer 574705903 3IL 23033 G1T 42 1 8 44 3 16 14 1 2 68 1 2 3 Groove 4 8 Gal 13 41 8 25 3 120 60 230 V 38 5 Quad with CP and pressure transducer 574705904 4IL 23033 G1T 51 1 8 44 3 16 14 1 2 68 1 2 3 Groove 4 8 ...

Страница 5: ...ol mounting hardware 2 Location Selection and Mounting The pump pack is heavy and may require additional technicians to support and move the unit during installation Use extreme caution in selecting an appropriate vertical surface to mount the unit and consult with a structural professional to verify that the selected wall can safely support the weight of the unit Identify a suitable wall location...

Страница 6: ... manifolds are attached tighten down all of the lag screws 2 Header End Cap Installation 1 Discharge End Cap Header This end cap piece is equipped with the bladder tank and a 1 1 4 open threaded port and is configured for installation on the left end of the discharge header If the end cap is to be installed on the right end the bladder tank can be easily moved to the open 1 1 4 port Attach the Dis...

Страница 7: ...the snap fitting 4 Connect Site Power to the Control Panel The control panel contains two 2 hot leads L1 L2 for 230VAC 60 Hz electric supply Failure to properly wire the unit and changing the wiring of the unit can result in serious bodily harm death and major equipment damage The electrical system consists of the control panel pumps and pressure transducer The control panel consists of an HMI PLC...

Страница 8: ... de energize the site power feeding the control panel when opening the panel otherwise an electrical shock hazard will still exist which can cause serious injury death and major property damage Prior to turning the unit on the following should be checked a The electrical incoming voltage should be verified that it meets the electrical requirements and that an adequate ground connection exists b Th...

Страница 9: ... button can be selected A red background to the MODBUS field indicates the controller is in local control while a GREEN background indicates the unit is operated remotely PUMP COUNTER A time counter provided below each pump icon indicates the number of days a pump has been in active operation running and not just available for operation These timers can be reset for one or more of the pumps by pre...

Страница 10: ...s selection can be made by pressing the time button immediately to the left of the PUMP SHUTDOWN TIMER label This timer will enable for a smooth transfer between the lead pumps immediately following a rotation TheusercanreturntotheSYSTEMscreenbypressingtheSYSTEMbuttonlocatedatthelowerrightsideofthescreenortheycangotoSETUPPAGE2Screen SETUP PAGE 2 screen is shown in Figure 7 and contains a number of...

Страница 11: ...tional issues with the package pumps Figure 8 Fault Possible Causes Corrective Action PLC Screen Does Not Turn On Site power to the control panel may be interrupted MaincontrolpaneldisconnectmaybeintheOFF 0 position The main fuses may be blown The fuses for the PLC may be blown PLC may be malfunctioning Verify that site power is live to the panel Turn control panel disconnect to the ON 1 position ...

Страница 12: ...Lead lag or parallel pump operation i e Duplex triplex or quadplex pump operation Use this selection to pick the method of controlling the lead pump rotation when operating the pumps in a lead lag format Selecting 1 will allow the user to start and stop the pumps using buttons on the system screen under the pump icons note the pumps must be made available by selecting the pump available unavailabl...

Страница 13: ...er in psi in this input box While on the system screen press Enter a pressure differential off of pressure set point for each lag pump in these fields Theprogramwillimmediatelypausepumpoperationifthetransducerreadingdropsbelow3 8ma Thispreventsrunawayoperationincaseofabadsensor Theusercandelaythispausefromoccurring byupto10secondsbyusingthisfieldtopreventnuisanceshutdownsfromtransientmareadings Go...

Страница 14: ...k on because of a minor drop in pressure after shutoff Use this field to define the time period between stop and start cycles which would indicate that hunting is occurring usually 1 5 seconds If the system has a stop and start cycle within this time period it will index a counter by 1 and when the counter hits the number inputted in the next field the higher set point will be activated for one st...

Страница 15: ...x based on model Register 0243h Pump System State 0 Maintenance 1 Commissioning 2 Manual 3 Time Based 4 Day Time Based Register 0244h Pump 1 State OP 0 Off 1 On Register 0245h Pump 2 State OP 0 Off 1 On Register 0246h Pump 3 State OP 0 Off 1 On Register 0247h Pump 4 State OP 0 Off 1 On Read Coils Register0240h System Alarm Register 0241h Pump System State 0 System Off 1 System On Writing Multiple ...

Страница 16: ...16 REPLACEMENTPARTS System Replacement Parts 5 14 8 6 11 12 7 2 3 9 9 10 4 11 10 1 1 13 ...

Страница 17: ...ead lag alternating pump control 5 Pressure Tank 10 3 gal tank with rubber bladder 6 Mounting Frame 304SS 12 gauge 8 frame pieces welded to manifolds 7 Pressure Switch 8 Capped 1 1 2 NPT Male Conn for OPT RV Provided by Others 9 Pressure Gauge 10 Drain Valve 3 4 SS drain valve 11 Isolation Valve 1 1 2 SS full port ball valve 12 Check Valve 1 1 2 SS inline spring check valve 13 Pump Connection 1 1 ...

Страница 18: ...0 30 AMP CC FU3 FU4 600AC 300DC Bussman FNQ R 15 15 AMP CC FU5 FU6 600AC 300DC Bussman FNQ R 15 15 AMP CC FU7 FU8 600AC 300DC Bussman FNQ R 5 5 AMP CC Samba Jumper Settings Jumper Setting 1 B PNP Source all inputs 5 B Analog input on input 10 6 B Analog input on input 11 3 B AN0 input 4 A AN1 input ...

Страница 19: ...st cover 1648128 Heavycon socket female insert B6 series 6 POS screw connection 5 Mean Well Ent or Equal MDR 60 24 60 watt 24VDC 2 5 AMP power supply unit with enclosure 6 Unitronics Samba SM43 J T20 PLC with HMI 7 Edison CHCC2DU 2P 30A 600V rated fuse holder for use with CC class fuses 8 Lovato FBO1G1P 1P 30A 600V rated fuse holder for use with class CC fuses 9 Wiegmann or Equal N1C121206 Enclosu...

Страница 20: ...VAC Bussman FNQ R 15 15 AMP CC FU5 FU6 500VAC Bussman FNQ R 15 15 AMP CC FU7 FU8 500VAC Bussman FNQ 15 15 AMP CC FU9 FU10 600AC 300DC Bussman LP CC 5 5 AMP CC Samba Jumper Settings Jumper Setting 1 B PNP Source all inputs 5 B Analog input on input 10 6 B Analog input on input 11 3 B AN0 input 4 A AN1 input ...

Страница 21: ...male insert B6 series 6 POS screw connection 5 Mean Well Ent or Equal MDR 60 24 60 watt 24VDC 2 5 AMP power supply unit with enclosure 6 Unitronics Samba SM 45 J T20 PLC with HMI 7 Edison CH60J2 2P 60A 600V rated fuse holder for use with CC class fuses 8 Lovato FBO1G1P 1P 30A 600V rated fuse holder for use with class CC fuses 9 Wiegmann or Equal N1C121206 Enclosure 16x16x6in wallmount steel ANSI61...

Страница 22: ... Bussman LP J 60SP 60 AMP J FU3 to FU10 500VAC Bussman FNQ R 15 15 AMP CC FU11 FU12 600AC 300DC Bussman LP CC 5 5 AMP CC Samba Jumper Settings Jumper Setting 1 B PNP Source all inputs 5 B Analog input on input 10 6 B Analog input on input 11 3 B AN0 input 4 A AN1 input ...

Страница 23: ...ale insert B6 series 6 POS screw connection 5 Mean Well Ent or Equal MDR 60 24 60 watt 24VDC 2 5 AMP power supply unit with enclosure 6 Unitronics Samba SM43 J T20 PLC with HMI 7 Edison CH60J2 2P 60A 600V rated fuse holder for use with CC class fuses 8 Lovato FBO1G1P 1P 30A 600V rated fuse holder for use with class CC fuses 9 Wiegmann or Equal N1C121206 Enclosure 16x16x6in wallmount steel ANSI61 S...

Страница 24: ...9255 Coverdale Road Fort Wayne IN 46809 Tel 260 824 2900 Fax 260 824 2909 www franklinwater com Form 106983101 Rev 001 06 18 ...

Отзывы: