
Framery Q (UL) Meeting Maggie
3.5 Seismic anchoring requirements
Note:
When installing the product, take into consideration all local laws, rules and
regulations concerning seismic anchoring and seismic safety.
For installations in the U.S., in buildings located in Seismic Design Categories A and B,
anchoring to the floor is optional. In buildings located in Seismic Design Categories C, D, E
or F, anchoring to the floor is required.
When anchoring to the floor, plans that address seismic design categories must be
prepared by a registered design professional. The plans prepared by the registered design
professional must also address the type, size and location of anchors and installation
limitations. Additionally, installation must be in accordance with the applicable codes [IBC,
IFC, IMC, NFPA 70 and, when installed with a sprinkler, NFPA 13].
20
Installation instructions
Содержание Q
Страница 1: ...Framery Q UL Meeting Maggie Installation instructions English Version 5 0 Tampere Finland 21 6 2022 ...
Страница 2: ......
Страница 6: ...Framery Q UL Meeting Maggie ...
Страница 146: ...Framery Q UL Meeting Maggie 146 Installation instructions info frameryacoustics com ...
Страница 147: ...Framery Q UL Meeting Maggie ...
Страница 148: ...Framery Q UL Meeting Maggie Installation instructions Patamäenkatu 7 33900 Tampere FINLAND VAT FI 23527139 ...