Step 1. Choosing a Location for the Inverter/Charger
Installation
CAUTION
DANGER
CAUTION:
Some models of the inverters are heavy. Use proper lifting
techniques during installation to prevent personal injury.
FIRE AND EXPLOSION HAZARD
Do not install this equipment in compartments containing batteries or
flammable materials, or in locations that require ignition-protected
equipment because this equipment contains components that could
produce arcs or sparks. This includes any space containing gasoline-
powered machinery, fuel tanks, or joints, fittings, or other connections
between components of the fuel system.
Failure to follow these instructions will result in death or serious injury.
WARNING
The inverter should not be installed in an area that allows dust, fumes,
insects or rodents to enter or block the inverter’s ventilation
openings.
This area also must be free from any risk of condensation, water or any
other liquid that can enter or fall on the inverter.
The entire line of inverters has been processed with a conformal
coating on the PCB, making it water, rust, and dust resistant.
While these units are designed to withstand corrosion from the salty
air, they are not splash proof.
The inverter’s life is uncertain if used in these types of environments,
and inverter failures under these conditions are not covered under
CAUTION
HEAT HAZARD
Do not cover or obstruct the ventilation openings. Do not install this
equipment in a compartment with limited airflow. Overheating may result.
Failure to follow these instructions can result in minor or moderate injury.
Applicable installation codes vary depending on the specific location
and application of the installation. Some examples are:
• The U.S. National Electrical Code (NEC)
• The Canadian Electrical Code (CEC)
• Canadian Standards Association (CSA) and RV Industry Association
(RVIA) for installation in RVs.
Please follow the code that is in effect at the time of installation.
Follow all the local regulations to install the inverter.
Please install the equipment in an INDOOR location of Dry, Clean, Cool
with good ventilation.
Working temperature: -10°C to 40°C(-14°Fto 104°F)
Storage temperature: -40 to 70°C(-40°Fto 158°F)
Relative Humidity: 0% to 95%,non-condensing
Cooling: Forced air