32
Technical Data, Specifications
Main Enclosure
Hinged door NEMA 4X/IP 66, ABS plastic rated
for indoor use, 5.9” wide x 5.9” high x 3.5” deep
with stainless steel wall mount feet, plastic
hinges and latches. Outdoor rated enclosure
Flame Retardant PC/PBT Alloy is available at
additional cost.
Sensor Enclosure:
NEMA 4X 4” x 4” on 7” x 7”
mounting plate, standard 25-ft, up to 2,000 ft
available, #22 AWG 2-conductor shielded
cable. Suitable for outdoor use.
Sun / Weather Guard
A sun / weather guard is available to protect the
detector in outdoor installations.
Outdoor
installations require non-standard UV
stabilized enclosures.
Battery Backup:
A separate 300VA external
battery backup / UPS is available, part #FX-
BB110
Gas Sensors Available
Gas Sensor
Standard
Range
Warning
Danger
Chlorine
0-10 ppm
0.5
1.0
Sulfur Dioxide
0-10 ppm
1.0
3.0
Ammonia
0-100 ppm
35
50
Oxygen
0-25%
18%
16%
Carbon Monoxide
0-500 ppm
35
50
Chlorine Dioxide
0-1 ppm
0.1
0.3
Hydrogen Sulfide
0-10 ppm
1.0
3.0
Ozone
0-2 ppm
0.05
0.1
Nitric Oxide
0-50 ppm
15
25
Nitrogen Dioxide
0-10 ppm
1.0
3.0
Hydrogen Cyanide
0-10 ppm
1.0
3.0
Hydrogen Chloride
0-10 ppm
0.7
2.0
Other gas ranges and non-standard alarm levels are available optionally.
Содержание FX-Mini
Страница 2: ...2 Page intentionally left blank...
Страница 30: ...30 Gas Sensor Components See page 26 for Ammonia Ozone and Hydrogen Cyanide sensor components...
Страница 35: ...35...