High and Low Alarm Relay Outputs:
The FX-1000p is equipped with two electromechanical relays. Two sets of SPDT relay outputs, one
for high alarm and one for low alarm. They energize upon alarm conditions and are located on the
bottom circuit board.
The relay outputs are not powered. The line power used to power the system may also be used to
power the alarm or control devices with these relay contacts. Always check control wiring to ensure
that line power will not be shorted by the relay switching action, and that wiring conforms to local
codes.
Important: Do Not Overload Relays. 1 amp Maximum, @ 125 VAC. Circuit Board damage will occur
if relays are overloaded.
Output Relays
Figure 18
Figure 19
Installation (Electrical)